PRODUCT INFORMATION
Product Overview
The General Electric IC695ETM001 is an Ethernet interface module for the PACSystems RX3i series. This module provides two 10/100 Mbps Ethernet communication ports with auto-negotiation capabilities. It occupies a single slot across compatible RX3i universal backplanes. The unit features an internal 200 MHz communications processor. It facilitates communication between RX3i controllers and platforms like Series 90 and VersaMax systems.
The module executes communication protocols over a four-layer TCP/IP network stack. Supported protocols include Service Request Transport Protocol, Modbus TCP, and Ethernet Global Data. It acts as both a Modbus TCP client and a Modbus TCP server. System time can synchronize to an SNTP time server over Ethernet. Hot insertion and removal are supported when the controller operates with compatible firmware versions.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Weight | 1.13 lbs (0.51 kg) |
|---|
| Compatibility | PACSystems RX3i |
|---|
| Ethernet Ports | 2x 10/100 Mbps |
|---|
| Serial RS-232 | Yes |
|---|
| Serial Data Rates | 1200 bps to 115200 bps |
|---|
| Hot-swappable | Yes |
|---|
| Autosensing Ports | Yes |
|---|
| Ethernet Processor speed | 200 MHz |
|---|
| Non-volatile memory | Yes – Allows daisy-chaining of Ethernet nodes |
|---|
| Transmission Rate | 10/100 Mbps |
|---|
| Ethernet Connectors | 8-pin female shielded RJ45 |
|---|
| Serial Connector | 9-pin female D-connector |
|---|
| Duplex Modes | Half and full duplex |
|---|
TECHNICAL INFORMATION
Features
- Provides two 10/100 Mbps autosensing Ethernet ports using shielded 8-pin RJ45 connectors.
- Features an internal 200 MHz processor for dedicated communications handling.
- Includes an RS-232 serial port offering baud rates from 1200 to 115200 bps.
- Supports Ethernet Global Data, Modbus TCP client and server, and SRTP communication protocols.
- Enables network time synchronization using Simple Network Time Protocol services.
- Allows hot-swap insertion and removal under system power with appropriate firmware.
- Includes front-panel LED indicators for Ethernet status, LAN status, and individual port links.
TECHNICAL INFORMATION
Applications
- Plant-wide communication between PACSystems RX3i controllers and legacy Series 90 or VersaMax platforms.
- Distributed control networks requiring deterministic data transfer using Ethernet Global Data exchange.
- Industrial Modbus TCP supervisory integration connecting field devices, PLCs, and SCADA systems.
TECHNICAL INFORMATION
Connections / Interfaces
- Two 8-pin female shielded RJ45 ports supporting 10/100Base-T Ethernet cabling.
- One 9-pin female D-sub connector providing RS-232 serial communication.
- Serial port supports Station Manager access for diagnostics, monitoring, and supervisory control.
TECHNICAL INFORMATION
Installation Guidelines
- Install into an unpowered PACSystems RX3i backplane slot during routine system maintenance.
- Hot-swap module insertion under power requires PACSystems RX3i firmware revision 2.51 or higher.
- Firmware upgrades are supported in the field using official vendor programming tools.
TECHNICAL INFORMATION
Configuration Guidelines
- Configure Ethernet port speed, duplex mode, and crossover settings through PACSystems programming software.
- Use the built-in Station Manager for supervisory diagnostic polling, logs, and password administration.
TECHNICAL INFORMATION
Compatibility
- Compatible with PACSystems RX3i backplane models IC695CHS007, IC695CHS012, and IC695CHS016.
- Functions with standard RX3i central processing units except for the CPE400 controller model.
- Integrates with existing Series 90 and VersaMax hardware through supported network protocols.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSCompatible with PACSystems RX3i backplane models IC695CHS007, IC695CHS012, and IC695CHS016. Functions with standard RX3i central processing units except for the CPE400 controller model. Integrates with existing Series 90 and VersaMax hardware through supported network protocols.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What backplanes support the General Electric IC695ETM001?
The IC695ETM001 operates in IC695CHS007, IC695CHS012, and IC695CHS016 PACSystems RX3i backplanes. It occupies a single universal backplane slot.
Does the IC695ETM001 support hot-swapping?
Yes, the IC695ETM001 supports hot-swap insertion and removal under power. The controller requires firmware revision 2.51 or higher to use this capability.
Which industrial communication protocols are supported on this module?
The module supports Modbus TCP client/server, Ethernet Global Data, and SRTP protocols. It also supports time synchronization using SNTP.
What RX3i controller model is incompatible with the IC695ETM001?
The IC695ETM001 is compatible with PACSystems RX3i controllers, except for the CPE400 processor model.