PRODUCT INFORMATION
Product Overview
The Allen-Bradley 1746-ITV16 is an SLC 500 fast response discrete input module. This module provides 16 fast-response discrete input points for industrial control systems. It operates across a voltage range of 10 to 30 VDC with a 24 VDC nominal rating. The module uses a source wiring configuration for connected sensing hardware.
The 1746-ITV16 delivers maximum signal delays of 0.3 milliseconds for ON and 0.5 milliseconds for OFF transitions. Internal filter circuitry and optical coupling reduce electrical noise across the input circuits. Backplane current consumption measures 85 milliamps at 5 VDC and zero milliamps at 24 VDC. A removable terminal block allows field wiring maintenance without disconnecting individual field conductors.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Applications | Combination 120 Volts AC I/O |
|---|
| Backplane Current (5 Volts DC) | 85 milliamps |
|---|
| Backplane current consumption | 0.085 A |
|---|
| Category | PLCs |
|---|
| Input Voltage Range | 10-30 VDC |
|---|
| Inputs | 16 |
|---|
| Module Type | Fast response discrete input module |
|---|
| Nom Input Voltage | 24VDC |
|---|
| Nominal input current | 8 mA at 24VDC |
|---|
| Off State Current | 1.5 milliamps |
|---|
| Off-state Voltage, max | 5VDC |
|---|
| Off-state current, max | 1.0 mA |
|---|
| Signal delay | 0.3 or 0.5 milliseconds |
|---|
| Signal delay, max. | On = 0.3 ms; Off = 0.5 ms |
|---|
| UPC | 662468070539 |
|---|
| Voltage Range | 10-30 Volts DC Source |
|---|
| Weight | 1.25 lbs (0.57 kg) |
|---|
| Wiring configuration | Source wiring configuration |
|---|
TECHNICAL INFORMATION
Features
- 16 fast response discrete input channels arranged in a single group.
- Source wiring configuration compatible with 24 VDC sourcing field inputs.
- Maximum signal delay of 0.3 ms ON and 0.5 ms OFF.
- Removable terminal block for efficient field maintenance and installation.
- Built-in filter circuitry and optical coupling to suppress electrical noise.
- Status LEDs providing real-time visual monitoring of each input point.
- Backplane current draw of 85 mA at 5 VDC.
TECHNICAL INFORMATION
Applications
- High-frequency binary switching devices such as counters and encoders.
- Totalizer and data logger input integration.
- Conveyor position monitoring requiring fast response detection.
TECHNICAL INFORMATION
Connections / Interfaces
- Removable terminal block for field wiring connection.
- Direct backplane interface to SLC 500 chassis.
TECHNICAL INFORMATION
Installation Guidelines
- Insert module into any compatible SLC 500 chassis slot.
- Maintain ambient operating temperatures between 0 and 60 degrees Celsius.
- Operate within noncondensing relative humidity levels from 5 to 95 percent.
- Disconnect system power before seating or removing the terminal block.
TECHNICAL INFORMATION
Configuration Guidelines
- Access input channel status through SLC 500 processor ladder logic data tables.
- Verify that input field devices match the 10 to 30 VDC source specification.
TECHNICAL INFORMATION
Compatibility
- Allen-Bradley modular SLC 500 chassis and processors.
- Allen-Bradley fixed SLC 500 expansion systems.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSAllen-Bradley modular SLC 500 chassis and processors. Allen-Bradley fixed SLC 500 expansion systems.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the wiring configuration of the Allen-Bradley 1746-ITV16?
The 1746-ITV16 uses a source wiring configuration. It operates at 10 to 30 VDC with 24 VDC nominal voltage.
What are the signal delay ratings for the 1746-ITV16 module?
The module has a maximum signal delay of 0.3 ms for ON and 0.5 ms for OFF transitions.
Does the 1746-ITV16 module have isolated input channels?
No. The 1746-ITV16 has a single group of 16 inputs without individual channel-to-channel isolation.
What is the backplane current consumption for the 1746-ITV16?
The module consumes 85 mA at 5 VDC and 0 mA at 24 VDC from the backplane.