PRODUCT INFORMATION
Product Overview
The General Electric IC695CMM002 is a serial communications module for the PACSystems RX3i series. This unit provides two independent and isolated serial ports for host control communication. Each serial port supports RS-232 and RS-422/485 physical interface standards. The ports use standard RJ-45 modular connectors for external serial connections. An RX3i control system supports up to six IC695CMM002 modules per backplane.
The module supports Modbus Master, Modbus Slave, DNP3 Master, DNP3 Slave, CCM Slave, and Serial I/O protocols. When configuring DNP3 on one port, the second port must also use DNP3 communication. Selectable transmission baud rates range from 1200 baud up to 115.2 kb. The unit features upgradable flash memory and reports watchdog, RAM, and flash faults. Diagnostic LED indicators display module health, port fault conditions, and active communication status.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Weight | 1.44 lbs (0.65 kg) |
|---|
| Product Description | Serial Communications Module |
|---|
| No of ports | Two (2) RS232 / RS422 / RS485 |
|---|
| Serial Ports | 2 |
|---|
| Supported Protocols | MODBUS Master, MODBUS Slave, CCM Slave, DNP3 Master, DNP3 Slave, or Serial I/O protocol |
|---|
| Interface | RJ-45 |
|---|
| Selectable Baud rates | 1200, 2400, 4800, 9600, 19.2K, 38.4K, 57.6K, 115.2K |
|---|
| Serial Protocols | RS-232, RS-485/422 |
|---|
| Connectors | RJ45 |
|---|
| Default Flow Control | Full duplex |
|---|
| No. of installations per rack | Up to Six (6) modules |
|---|
| Power Requirements | 0.7 Amps at 3.3 Volts DC, 0.115 Amps at 5 Volts DC |
|---|
| Status LED indicators | Module OK, Port Fault, Port Status |
|---|
| Maximum Overvoltage Rating | +/-25 Volts DC |
|---|
| Current rating | 0.7 mA at 3.3 VDC, 0.115 mA at 5 VDC |
|---|
| Operating Temperature | 0 to 60 degrees Celsius |
|---|
| Parity | Even, odd, none |
|---|
| Data bits | 7, 8 |
|---|
| Stop bits | 1, 2 |
|---|
| Isolation rating | Port to Backplane and to frame ground: 250Vac continuous; 1500Vac for 1 minute, 2550Vdc for one second. Port to port: 500Vdc continuous, 710Vdc for one minute. |
|---|
TECHNICAL INFORMATION
Features
- Provides two isolated serial ports configurable for RS-232, RS-422, and RS-485.
- Supports Modbus Master/Slave, DNP3 Master/Slave, CCM Slave, and Serial I/O protocols.
- Allows software selection of baud rates from 1200 to 115200 baud.
- Integrates diagnostics for watchdog, RAM failure, and flash memory faults.
- Operates with full-duplex flow control or half-duplex with firmware version 1.32 or later.
- Permits hot-swappable installation in PACSystems RX3i backplanes.
TECHNICAL INFORMATION
Connections / Interfaces
- Provides two RJ-45 serial interfaces on the front faceplate.
- Serial ports support RS-232, RS-422, and RS-485 signaling modes.
- RS-232 operation supports RTS/CTS and RFR/CTS hardware handshaking.
- Input impedance exceeds 96 kiloohms for RS-485 and RS-422 communication circuits.
TECHNICAL INFORMATION
Installation Guidelines
- Install up to six serial communications modules within a single PACSystems RX3i rack.
- The module supports hot-swappable replacement during live backplane operation.
- Ensure ambient operating temperatures remain between 0 and 60 degrees Celsius.
TECHNICAL INFORMATION
Configuration Guidelines
- Configure port settings using Machine Edition Release 5.90 SP1 SIM 6 or later.
- Select parity modes from Even, Odd, or None.
- Configure data bits to 7 or 8 and stop bits to 1 or 2.
- Assigning DNP3 to one port limits the secondary port to DNP3 Master or Slave.
TECHNICAL INFORMATION
Compliance and Certifications
- Complies with CE, ATEX, UL/UCK 508, and 1604 standards.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What protocols are supported on the IC695CMM002 serial ports?
The module supports Modbus Master, Modbus Slave, DNP3 Master, DNP3 Slave, CCM Slave, and Serial I/O protocols.
Can the two serial ports run different protocols simultaneously?
Yes, unless DNP3 is chosen. Selecting DNP3 on one port requires DNP3 on the second port.
What is the maximum number of IC695CMM002 modules per rack?
A single PACSystems RX3i backplane can host up to six IC695CMM002 communications modules.
Does the module support half-duplex communication?
Half-duplex flow control is supported on modules running firmware 1.32 or later with Machine Edition 5.90 SP1 SIM 6.