PRODUCT INFORMATION
Product Overview
The General Electric IC200MDD845 is a VersaMax mixed module providing discrete input and output processing capabilities. This unit operates within a VersaMax distributed station or connects with native CPU modules. It provides 24 total points divided into two input groups and one output group. Sixteen inputs accept positive logic signals at a nominal 24 VDC. Eight Form A relay contact outputs handle external control loads across alternating or direct current circuits.
The module draws up to 270 mA maximum current from the system backplane power source. Channel-to-channel isolation protects each Form A relay output point individually. Field loads connected to the outputs require an external power supply. Local channel LEDs display actuation states, while an OK LED confirms operational backplane power. Installation requires a compatible IC200CHS carrier base mounted inside the system rack.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Weight | 1.06 lbs (0.48 kg) |
|---|
| Product Description | Combination Discrete Input and Output Module |
|---|
| No. of I/O channels | Twenty-Four (24) |
|---|
| Bulletin | IC200 |
|---|
| No. of input channels | Sixteen (16) |
|---|
| Input signal, nominal | 24 VDC |
|---|
| I/O Points | 24 |
|---|
| Input signal, range | 18-30 VDC |
|---|
| Inputs | 16 |
|---|
| On state current | 2.0-5.5 mA |
|---|
| Outputs | 8 |
|---|
| Off-state current | 0-0.5 mA |
|---|
| Output Logic | 1 |
|---|
| No. of Output channels | Eight (8) Form A relay contacts |
|---|
| CPU | Active |
|---|
| Channel Isolation | Output channels are individually isolated |
|---|
| Input Voltage | 24 V DC |
|---|
| Output Voltage Range | 0 to 125 V DC, 0 to 265 V AC |
|---|
| Output voltage | 0-125 VDC, 5/24/125 VDC nominal; 0-265 VAC (47-63 Hz), 120/240 VAC nominal |
|---|
| Frequency | 47 to 63 Hz |
|---|
| External Power supply | 0-125 VDC, 5/24/125 VDC nominal; 0-265 VAC (47-63 Hz), 120/240 VAC nominal |
|---|
| Current Draw | 270 mA, maximum |
|---|
| LED indicators | Individual channel LED indicators; OK LED; |
|---|
TECHNICAL INFORMATION
Features
- Contains 16 positive logic discrete input points arranged in two groups of eight.
- Provides 8 individually isolated Form A normally open relay contact outputs.
- Supports input signal voltages from 18 to 30 VDC with 24 VDC nominal operation.
- Handles contact output voltages from 0 to 125 VDC and 0 to 265 VAC.
- Delivers typical transition response times of 0.5 ms for turn-on and 10 ms for turn-off.
- Includes individual channel status indicators and an operational OK LED.
TECHNICAL INFORMATION
Applications
- Distributed input and output interfacing across GE Fanuc VersaMax control networks.
- Direct switching of mixed alternating current and direct current industrial field actuators.
- Sensing of 24 VDC discrete operator controls and field limit switches.
TECHNICAL INFORMATION
Connections / Interfaces
- Field wiring terminates at an IC200CHS series carrier base.
- Sixteen discrete input circuits configure as positive logic connections.
- Eight isolated Form A relay contacts switch external load paths.
TECHNICAL INFORMATION
Installation Guidelines
- Mount the module directly onto a compatible IC200CHS series carrier base.
- Ensure total system backplane capacity accommodates the 270 mA maximum consumption.
- Provide external fusing or suppression since the module contains no internal fuses or snubbers.
TECHNICAL INFORMATION
Configuration Guidelines
- Verify field input voltage conforms to the 18 to 30 VDC operating window.
- Confirm connected load currents meet the 10 mA minimum switching threshold.
TECHNICAL INFORMATION
Compatibility
- Installs on GE VersaMax IC200CHS series carrier bases.
- Integrates with VersaMax CPUs and distributed communication network interface units.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSInstalls on GE VersaMax IC200CHS series carrier bases. Integrates with VersaMax CPUs and distributed communication network interface units.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What point configuration does the IC200MDD845 provide?
The module provides 16 discrete 24 VDC inputs and 8 isolated Form A relay outputs.
Does the IC200MDD845 include internal circuit protection?
No. The module contains no internal fuses or snubber circuits for the relay contacts.
What mounting hardware is required for this module?
The module requires an IC200CHS series carrier base for physical mounting and wiring.