PRODUCT INFORMATION
Product Overview
The General Electric IS200TRPGH1B is a primary trip terminal board for Mark VI and Mark VIe turbine control systems. This board interfaces with turbine protection relays to drive up to three electrical trip devices. It incorporates three voting relays per trip solenoid to support Triple Modular Redundant configurations. It also accepts inputs from up to eight Geiger-Mueller flame detectors in gas turbine operations.
During standard operation, the unit cooperates with the emergency trip board to provide system shutdown capability. Internal relay ladder logic provides hardware two-out-of-three voting for the protection solenoids. The I/O controller monitors relay coil driver current lines and contact health continuously. Connectors include onboard electronic identification devices to prevent hardware mismatch faults during installation.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Trip Solenoids | 3 |
|---|
| Solenoid Rated Voltage/Current | 125 V dc |
|---|
| Solenoid Response Time | L/R time constant is 0.1 sec |
|---|
| Current Suppression | Metal oxide varistor |
|---|
| Control Relay Coil Voltage Supply | 28 V |
|---|
| Flame Detector Supply Voltage/Current | 335 V dc |
|---|
| Flame Detectors | 8 |
|---|
TECHNICAL INFORMATION
Features
- Supports Triple Modular Redundant architectures using three voting relays per trip solenoid.
- Provides direct connection interfaces for three 125 V dc primary electrical trip devices.
- Supplies 335 V dc excitation and signal conditioning for eight Geiger-Mueller flame detectors.
- Incorporates metal oxide varistors for electrical current suppression across the trip circuits.
- Integrates diagnostic feedback for relay coil driver status, bus voltages, and contact positions.
TECHNICAL INFORMATION
Applications
- Primary overspeed and turbine trip protection circuits in General Electric Mark VI gas turbine control systems.
- Trip relay interface and voting logic in General Electric Mark VIe turbine automation platforms.
- Optical flame monitoring and trip valve solenoid management in industrial gas turbine power generation installations.
TECHNICAL INFORMATION
Connections / Interfaces
- First I/O terminal block connects wiring for up to three electrical trip solenoids.
- Second terminal block provides direct connection points for up to eight flame detectors.
- J1 connector receives 125 V dc supply power for the trip solenoids.
- J2 connector routes power through to the companion TREG emergency trip terminal board.
- J3, J4, and J5 connectors deliver operating power to the flame detection channels.
- JR1, JS1, and JT1 connectors interface with I/O controllers and contain diagnostic ID chips.
TECHNICAL INFORMATION
Installation Guidelines
- Mount the terminal board in the designated control enclosure according to GEH-6421J manual instructions.
- Connect trip solenoid field wiring directly to the first terminal block.
- Terminate flame detector signal wiring at the dedicated second terminal block.
- Confirm connector cables with molded plugs seat securely into JR1, JS1, and JT1 sockets.
TECHNICAL INFORMATION
Configuration Guidelines
- Verify that the system architecture matches the H1B hardware group configured for TMR voting operation.
- Ensure the matching I/O processor correctly reads the electronic ID devices on the board connectors.
- Configure flame detector channel thresholds within the Mark VI or Mark VIe engineering workstation software.
TECHNICAL INFORMATION
Compatibility
- General Electric Mark VI systems using the VTUR turbine interface board within a VME chassis.
- General Electric Mark VIe systems using PTUR I/O packs mounted on TTURH1C terminal assemblies.
- General Electric TREG terminal boards for combined primary and emergency trip interface operation.
TECHNICAL INFORMATION
Lifecycle / Replacement Information
- The IS200TRPGH1B serves as the TMR-configured hardware group within the TRPG primary trip board series.
- Group H1B uses three voting relays per solenoid and cannot directly replace simplex H2A or H2B models.
- Hardware replacement requires matching the terminal board revision ID chip queried by system diagnostics.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSGeneral Electric Mark VI systems using the VTUR turbine interface board within a VME chassis. General Electric Mark VIe systems using PTUR I/O packs mounted on TTURH1C terminal assemblies. General Electric TREG terminal boards for combined primary and emergency trip interface operation.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the primary function of the IS200TRPGH1B terminal board?
The board operates primary trip solenoids and interfaces with eight flame detectors in turbine control systems.
What is the difference between TRPG H1 and H2 board types?
H1 versions feature three voting relays per trip solenoid for TMR systems. H2 versions have one relay per solenoid.
How does the IS200TRPGH1B interface with Mark VI and Mark VIe systems?
Mark VI uses cables connecting to VTUR boards. Mark VIe systems connect via PTUR packs on TTURH1C assemblies.
What diagnostics run on the IS200TRPGH1B?
The I/O board monitors solenoid driver feedback, relay contacts, power buses, flame excitation, and board ID chips.