PRODUCT INFORMATION
Product Overview
The General Electric DS200TBCAG1AAB is an Analog I/O Terminal Board for Mark V Speedtronic systems. This board provides field signal termination for gas, steam, and wind turbine control applications. It interfaces directly with the central turbine automation architecture through designated cable assemblies. The unit incorporates two blocks of ninety signal wire terminals for field device wiring. Two 50-pin ribbon cable connectors link incoming signals to internal system processors.
The board represents a revised release of the original DS200TBCAG1 parent terminal assembly. It incorporates three specific revision increments denoted by the AAB suffix. Normal PCB coating protects the circuit traces across industrial operating environments. The standard hardware design contains no manually configurable jumpers or switches. Field replacement requires transferring wiring directly to identical terminal block locations.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| PCB Coating | Normal Coating |
|---|
TECHNICAL INFORMATION
Features
- Two terminal blocks provide a total of 180 signal wire connection points.
- Two 50-pin connectors facilitate ribbon cable links to system processing cards.
- Connector JCC routes RTD signals 1 through 15 to the R5 core.
- Connector JDD routes RTD signals 16 through 30 to the R5 core.
- Standard assembly contains no manually movable hardware jumpers.
- Normal protective coating covers the printed circuit board assembly.
TECHNICAL INFORMATION
Applications
- General Electric Mark V Speedtronic gas turbine control systems.
- Steam turbine automation and protection panels.
- Industrial wind turbine management systems.
TECHNICAL INFORMATION
Connections / Interfaces
- Two terminal blocks provide 90 screw terminals each for field wiring.
- Two 50-pin connectors interface with internal Mark V ribbon cabling.
- Connector JCC handles RTD input channels 1 through 15.
- Connector JDD handles RTD input channels 16 through 30.
TECHNICAL INFORMATION
Installation Guidelines
- Only qualified personnel should install or replace this terminal board.
- Disconnect all power sources to the cabinet prior to servicing.
- Locate emergency power shut-off controls before opening the equipment enclosure.
- Use an electrostatic discharge protective surface and wear a grounded wrist strap.
- Move field wiring one wire at a time to match existing terminal assignments.
TECHNICAL INFORMATION
Compatibility
- Compatible with General Electric Mark V Speedtronic control panels.
- Direct replacement for earlier revision iterations of the DS200TBCAG1 board series.
TECHNICAL INFORMATION
Lifecycle / Replacement Information
- Replaces earlier revisions of the parent DS200TBCAG1 terminal board.
- Retains backwards compatibility with original terminal wiring and connector assignments.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSCompatible with General Electric Mark V Speedtronic control panels. Direct replacement for earlier revision iterations of the DS200TBCAG1 board series.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the function of the General Electric DS200TBCAG1AAB?
The DS200TBCAG1AAB terminates field analog wiring in GE Mark V Speedtronic turbine control systems.
How many field wiring connections are available on the DS200TBCAG1AAB?
The board contains two terminal blocks with 90 screw terminals each, providing 180 wiring points.
Does the DS200TBCAG1AAB board require jumper configuration?
No hardware jumpers or configurable switches are present on the DS200TBCAG1AAB terminal board.
What ribbon cable connectors are located on the board?
The board includes two 50-pin connectors, including JCC and JDD for RTD signal communication.