PRODUCT INFORMATION
Product Overview
The ABB DI811 3BSE008552R1 is a 48 V d.c. Digital Input Module designed for the S800 I/O system. It provides 16 current sinking digital input channels arranged in two individually isolated groups of eight. Each channel incorporates optical isolation barriers, current limiting components, and individual state indication LEDs. In addition, built-in process voltage supervision monitors field supply integrity and flags voltage loss via the ModuleBus interface.
This module features selectable digital filter times of 2, 4, 8, or 16 ms. It dissipates 2.7 W typically and draws 50 mA from the 5 V ModuleBus supply. The unit mounts onto standard S800 Module Termination Units using mechanical keying code BD. Field wiring lengths can extend up to 600 meters under compliant installation practices.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Number of Channels | 16 |
|---|
| Signal Specification | 48 V d.c. |
|---|
| Signal Type | Current sinking |
|---|
| Input Voltage Range, '0' | -60 to +10 V |
|---|
| Input Voltage Range, '1' | 30 to 60 V |
|---|
| Input Impedance | 11 kΩ |
|---|
| Digital Filter Times | 2, 4, 8, 16 ms (selectable) |
|---|
| Channel Isolation | Groupwise isolated from ground, 2 groups of 8 channels |
|---|
| Rated Insulation Voltage | 50 V |
|---|
| Dielectric Test Voltage | 500 V a.c. |
|---|
| Power Dissipation | Typ. 2.7 W |
|---|
| Current Consumption (+5 V ModuleBus) | 50 mA |
|---|
| Maximum Field Cable Length | 600 m (656 yd) |
|---|
| Operating Temperature | 0 to +55 °C (+32 to +131 °F) |
|---|
| Ingress Protection | IP20 (IEC 60529) |
|---|
| Mechanical Keying Code | BD |
|---|
TECHNICAL INFORMATION
Features
- Offers 16 current sinking channels organized into two isolated groups of eight.
- Includes one process voltage supervision input per channel group for supply monitoring.
- Provides selectable input digital filter response times of 2, 4, 8, or 16 milliseconds.
- Equipped with front panel LED indicators for Fault, Run, Warning, and individual channel logic states.
- Supports maximum field wiring cable lengths up to 600 meters.
- Conforms to ISA-S71.04 G3 corrosion protection standards for harsh environments.
TECHNICAL INFORMATION
Applications
- Supervision of field contact switches and pushbuttons operating on 48 V d.c. control circuits.
- Signal acquisition in distributed automation panels using S800 I/O stations.
- Process automation installations requiring groupwise channel isolation and supply voltage monitoring.
TECHNICAL INFORMATION
Connections / Interfaces
- Connects to field wiring through compatible S800 Module Termination Units.
- Interfaces with the station controller via the internal ModuleBus backplane.
- Accepts two independent external field power supply feeds for group supervision.
TECHNICAL INFORMATION
Installation Guidelines
- Mounts directly onto designated S800 MTU bases using mechanical keying code BD.
- Maintain ambient temperature below 40 °C when mounting vertically in compact MTU housings.
- Ensure maximum ambient operating temperature does not exceed 55 °C in horizontal mounting.
- Verify grounding integrity to meet Class I equipment protection requirements.
TECHNICAL INFORMATION
Configuration Guidelines
- Configure digital filter delay times to 2, 4, 8, or 16 ms within the engineering tool.
- ModuleBus reads channel supervision error signals directly upon field power loss.
TECHNICAL INFORMATION
Compatibility
- Compatible with S800 Module Termination Units TU810, TU812, TU814, and TU818.
- Compatible with extended Module Termination Units TU830, TU833, TU838, and TU850.
- Operates across ABB Advant and 800xA control systems supporting S800 I/O.
TECHNICAL INFORMATION
Compliance and Certifications
- Electrical Safety: EN 61010-1, UL 61010-1, EN 61010-2-201, UL 61010-2-201
- Hazardous Locations: cULus Class I Div 2, Class I Zone 2, ATEX Zone 2
- Marine Certifications: ABS, BV, DNV, LR, CCS
- EMC Compliance: EN 61000-6-4, EN 61000-6-2
- Environmental Compliance: EU RoHS, UAE RoHS, CN RoHS, WEEE DIRECTIVE/2012/19/EU
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSCompatible with S800 Module Termination Units TU810, TU812, TU814, and TU818. Compatible with extended Module Termination Units TU830, TU833, TU838, and TU850. Operates across ABB Advant and 800xA control systems supporting S800 I/O.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the primary function of the ABB DI811 3BSE008552R1 module?
The ABB DI811 3BSE008552R1 interfaces 16 sinking 48 V d.c. digital input signals with the S800 I/O system.
Which Module Termination Units are compatible with the DI811?
The DI811 fits TU810, TU812, TU814, TU818, TU830, TU833, TU838, and TU850 termination units with keying code BD.
How does the DI811 supervise field power supplies?
Each isolated group of eight channels contains a voltage supervision input detecting field voltage loss.
What are the selectable filter times for DI811 inputs?
The DI811 provides selectable digital input filter times of 2 ms, 4 ms, 8 ms, and 16 ms.