PRODUCT INFORMATION
Product Overview
The Allen-Bradley 1797-PS2E2 is an intrinsically safe power supply module for the FLEX I/O architecture. This unit isolates incoming electrical circuits from hazardous area control networks. It prevents electrical fault propagation from the input side to the output terminals. The unit provides four intrinsically safe limited output channels. Each channel delivers up to 8.5 Watts of DC power. The module requires an input voltage ranging from 18 to 32 Volts DC.
The power supply is enclosed in an IP65 and NEMA 7B flame-proof housing. Input connections include four terminals for dual redundant power inputs. One M20x1.5 cable gland secures incoming power cables between 6 and 12 millimeters in diameter. Four M16x1.5 output glands accommodate field cables measuring 4 to 8 millimeters across. The unit supports module removal and insertion under power during active operations in classified locations.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| UPC | 612598293667 |
|---|
| Weight | 14.25 lbs (6.46 kg) |
|---|
| Input Connectors | 24V DC |
|---|
| Voltage Range | 18-32V |
|---|
| Current Consumption | 3.1-1.6 A |
|---|
| Ripple | 5% ac |
|---|
| Output Power | 4 x 8.5 W |
|---|
| Voltage | 9.5V |
|---|
| Power Dissipation | 21 W |
|---|
| Thermal Dissipation | 71.67 BTU/hr |
|---|
| Input Power | 55 W |
|---|
TECHNICAL INFORMATION
Features
- Provides four independently limited intrinsically safe output channels.
- Supplies 8.5 Watts of output power per channel.
- Accepts wide input voltage ranges from 18 to 32 Volts DC.
- Includes redundant power input terminals for backup DC power connections.
- Housed in an IP65 and NEMA 7B flame-proof enclosure.
- Supports removal and insertion under power in hazardous locations.
TECHNICAL INFORMATION
Connections / Interfaces
- Input DC terminals located at positions 1, 2, 4, and 5 for redundant wiring.
- One M20x1.5 input cable gland accepting 6 to 12 millimeter cable diameters.
- Four M16x1.5 output cable glands accepting 4 to 8 millimeter cable diameters.
TECHNICAL INFORMATION
Installation Guidelines
- Mount the unit securely within the specified hazardous environment.
- Route input cabling through the M20x1.5 flame-proof gland.
- Ensure field wiring adheres to intrinsically safe installation standards.
- Verify input voltage stays between 18 and 32 Volts DC before energizing.
TECHNICAL INFORMATION
Compliance and Certifications
- IECEx certified for explosive atmospheres.
- IP65 environmental ingress protection rating.
- NEMA 7B flame-proof enclosure rating.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the primary function of the Allen-Bradley 1797-PS2E2?
It delivers intrinsically safe isolated DC power to FLEX Ex system components in hazardous locations.
How many outputs does the 1797-PS2E2 supply provide?
The module provides four independent intrinsically safe outputs delivering 8.5 Watts each.
Can the 1797-PS2E2 be replaced while powered?
Yes, it supports removal and insertion under power in classified hazardous environments.
What type of enclosure protects the 1797-PS2E2 module?