PRODUCT INFORMATION
Product Overview
The Allen-Bradley 2711-B5A10L1 is a PanelView 550 Mono/Touch/Keypad terminal in the PanelView series. It operates using an external nominal 24V DC power supply with an input range of 18 to 32V DC. The terminal features a 5.5-inch monochrome blue mode LCD screen with 256 by 128 resolution. Its active display area measures 120 by 60 millimeters. The unit provides dual operator input via a membrane keypad and a 128-cell touch screen.
Internal memory includes 170 KB of application runtime RAM and 240 KB of nonvolatile memory. The nonvolatile flash storage retains application objects, text, and graphic bitmaps. Network communication is handled through an integrated DeviceNet port. A dedicated RS-232 port provides connection for an external alarm and message printer. The display backlight offers an estimated operating life of 100,000 hours. Configuration and screen design are managed using PanelBuilder32 programming software.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Product Line | Panelview 550 |
|---|
| UPC | 662072682487 |
|---|
| Weight | 2.06 lbs (0.94 kg) |
|---|
| Backlight | 100,000 hr LED backlight life |
|---|
| Input Type | Keypad / Touch |
|---|
| Display Type | Monochrome LCD blue mode display |
|---|
| Display Area | 120 x 60 mm (4.75 x 2.38 in.) |
|---|
| Resolution | 256 x 128 |
|---|
| Touchscreen | Touch cells: 128 Actuation: 1 million presses |
|---|
| Keypad function keys | 10 function keys (F1…F10) |
|---|
| Application memory | 170 KB application runtime; 240 KB nonvolatile memory (application objects plus text and bitmaps) |
|---|
| Communication ports | DeviceNet; RS232 (printer) |
|---|
| Input Voltage range | 18…32V DC (24V DC nominal supply) |
|---|
| Accessories | function key legend inserts; Anti-glare overlays; backlight replacements; Real-time clock replacements; Mounting hardware; Power supply and terminal block; interface modules; |
|---|
| Display Size | 5.5 in. |
|---|
| Display Color | Monochrome LCD blue mode |
|---|
| Communication | DeviceNet Communication and RS-232 Printer Port |
|---|
| Input Power | 24V DC |
|---|
| Memory | 170 KB application runtime |
|---|
| Communication Cable | 2711-NC13 |
|---|
| Product Lifecycle Status* | Discontinued/Obsolete |
|---|
TECHNICAL INFORMATION
Features
- Dual input system includes a 128-cell touch matrix and a 10-key membrane keypad.
- Monochrome LCD blue mode display offers 256 by 128 resolution across 5.5 inches.
- Integrated backlight provides an operational life of up to 100,000 hours.
- Keypad contains 10 functional keys labeled F1 through F10 for operator inputs.
- Dedicated DeviceNet communication port connects the terminal to industrial field networks.
- RS-232 serial printer port supports local logging of system messages and alarms.
- Internal memory consists of 170 KB runtime memory and 240 KB nonvolatile memory.
TECHNICAL INFORMATION
Applications
- Industrial machine interface and operational parameter entry.
- Local message printing and alarm recording over dedicated serial connections.
- Process visualization and distributed terminal control on DeviceNet networks.
TECHNICAL INFORMATION
Connections / Interfaces
- One DeviceNet port for connection to industrial network devices.
- One RS-232 serial port dedicated to external alarm and message printers.
- DC power terminal block supporting an input range of 18 to 32V DC.
- Compatible with catalog number 2711-NC13 communication cables.
TECHNICAL INFORMATION
Installation Guidelines
- Mount the unit in an enclosure that provides appropriate environmental protection.
- Maintain operating ambient temperatures between 0 and 55 degrees Celsius.
- Operate the terminal at altitudes at or below 2000 meters.
- Supply 24V DC nominal power within the specified 18 to 32V DC limits.
TECHNICAL INFORMATION
Configuration Guidelines
- Program screens and operational logic using PanelBuilder32 software.
- Assign DeviceNet network parameters and node addresses within the application file.
- Configure RS-232 serial printer transmission parameters to match printer requirements.
TECHNICAL INFORMATION
Compatibility
- Integrates with industrial control equipment over DeviceNet communication networks.
- Connects to serial logging printers via RS-232 communication cables.
- Uses replacement backlight catalog number 2711-NL1.
TECHNICAL INFORMATION
Lifecycle / Replacement Information
- Rockwell Automation has declared the 2711-B5A10L1 terminal obsolete and discontinued.
- Maintenance stock, parts, and replacement units remain accessible through industrial supply channels.
TECHNICAL RESOURCES
Documentation
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSIntegrates with industrial control equipment over DeviceNet communication networks. Connects to serial logging printers via RS-232 communication cables. Uses replacement backlight catalog number 2711-NL1.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What communication interfaces are included on the 2711-B5A10L1?
The unit features a DeviceNet network communication port and an RS-232 serial printer port.
What software is used to configure the 2711-B5A10L1?
Applications for this terminal are created and configured using Rockwell Automation PanelBuilder32 software.
What are the input power specifications for the 2711-B5A10L1?
The terminal operates on nominal 24V DC power with an operating range of 18 to 32V DC.
What input options does the terminal provide for machine operators?
The unit provides a 128-cell touch screen membrane and a 10-key tactile membrane keypad.
What is the current lifecycle status of the 2711-B5A10L1?
Rockwell Automation has declared the 2711-B5A10L1 terminal discontinued and obsolete.