PRODUCT INFORMATION
Product Overview
The General Electric IC200MDD840 is an I/O Module for the VersaMax control platform. This combination discrete unit provides twenty inputs and twelve relay outputs. The input circuits operate at a nominal 24 VDC rating. They are arranged into two groups of ten positive logic channels. Backplane power draw is rated at 375 mA maximum. The module interfaces through a VersaMax carrier into a central processor or network interface unit.
The twelve relay outputs feature Form A normally open silver alloy contacts. These outputs are divided into two isolated groups of six circuits each. Each output group supports total load currents up to 8 A. Switched loads require an external AC or DC power supply. Configurable input filter times help eliminate electrical and contact noise during signal transitions.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Weight | 1.50 lbs (0.68 kg) |
|---|
| Product Description | Combination Discrete Input and Output Module |
|---|
| No. of I/O channels | Thirty-Two (32) |
|---|
| Bulletin | IC200 |
|---|
| No. of input channels | Twenty (20) |
|---|
| Input signal, nominal | 24 VDC |
|---|
| Number of I/O Points | 32 |
|---|
| Input signal, range | 0-30 VDC |
|---|
| Inputs | 20 |
|---|
| On state current | 2.0-5.5 mA |
|---|
| Outputs | 12 |
|---|
| No. of Output channels | Six (6) Form A relay contacts |
|---|
| Types of Input Points | Positive-Logic/Sourcing |
|---|
| Channel Isolation | Two (2) groups of Six (6) outputs each |
|---|
| Input Voltage | 24 V DC |
|---|
| Output Voltage | 0 to 125 V DC |
|---|
| External Power supply | 0-125 VDC, 5/24/125 VDC nominal; 0-265 VAC (47-63 Hz), 120/240 VAC nominal |
|---|
| Off-State Current | 0-0.5 mA |
|---|
| Current Draw | 375 mA, maximum |
|---|
| LED indicators | Individual channel LED indicators; OK LED; |
|---|
TECHNICAL INFORMATION
Features
- Provides 20 positive logic 24 VDC discrete inputs arranged in two groups of ten.
- Supplies 12 Form A normally open relay outputs organized in two groups of six.
- Supports configurable input filter times of 0 ms, 0.7 ms, and 1.0 ms.
- Handles output switching up to 265 VAC or 125 VDC using external field power.
- Includes individual channel status indicators alongside an active OK LED indicator.
TECHNICAL INFORMATION
Applications
- Interfacing field limit switches and pushbuttons to a VersaMax controller.
- Direct control of motor starter coils, indicator lamps, and interposing relays.
- Mixed discrete input and relay output control within compact machine enclosures.
TECHNICAL INFORMATION
Connections / Interfaces
- Inputs wire as sourcing devices returning current to common terminals.
- Output contacts require external power wiring to switch user loads.
- Terminal connections are made through the underlying VersaMax I/O carrier.
TECHNICAL INFORMATION
Installation Guidelines
- Seat the module firmly onto the compatible VersaMax carrier on the DIN rail.
- Provide external fusing for field wiring because the module contains no internal fuses.
- Ensure adequate clearance around the carrier for thermal dissipation.
TECHNICAL INFORMATION
Configuration Guidelines
- Configure input filter delays in system software to 0 ms, 0.7 ms, or 1.0 ms.
- Default input filter time is set to 1.0 ms for standard noise rejection.
TECHNICAL INFORMATION
Compatibility
- Installs into standard VersaMax carrier bases.
- Operates with VersaMax CPUs and Network Interface Units.
TECHNICAL INFORMATION
Lifecycle / Replacement Information
- The IC200MDD840 is part of the legacy GE Fanuc VersaMax automation product line.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSInstalls into standard VersaMax carrier bases. Operates with VersaMax CPUs and Network Interface Units.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What types of input signals does the IC200MDD840 accept?
It accepts 24 VDC nominal sourcing inputs with an operational range from 0 to 30 VDC.
What are the contact ratings for the relay outputs?
Contacts support up to 2.0 A at 265 VAC or 30 VDC for resistive loads.
Does the IC200MDD840 provide internal fuse protection?
No, the module does not include internal fuses. External circuit protection must be supplied by the user.
Can the input response time be adjusted on this module?
Yes, input filter times can be configured to 0 ms, 0.7 ms, or 1.0 ms.