PRODUCT INFORMATION
Product Overview
The General Electric IC660BRD020 is a Genius I/O block designed for industrial automation control architectures. This unit manages up to 16 output circuits across an operating voltage range of 18 to 56 VDC. Maximum voltage ripple is rated at 10 percent during routine operation. Peak current draw reaches 300 milliamps under normal operational loads. The device tolerates power supply dropouts lasting up to 10 milliseconds without operational interruption.
Electrical isolation between blocks is rated at 1500 VAC to protect connected equipment from common-mode transients. Selectable input filtering ranges from 10 to 100 milliseconds for signal noise suppression. Diagnostic indicators include a primary Unit OK LED and individual status LEDs for each circuit. Thermal dissipation reaches 90 watts, and the module mounts directly to a backplane. Operational ambient temperatures span 0°C to 60°C in relative humidity up to 95 percent non-condensing.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Weight | 3.25 lbs (1.47 kg) |
|---|
| UPC | 799705805705 |
|---|
| Output Circuits | 16 circuits |
|---|
| Maximum Ripple | 10% |
|---|
| Maximum Current Draw | 300 milliamps |
|---|
| Operating Voltage | 18 to 56 Volts DC |
|---|
| Power Supply Dropout Tolerance | 10 ms |
|---|
| Block-to-Block Isolation Voltage | 1500 V AC |
|---|
| Input Filtering Options | 10 ms to 100 ms |
|---|
| Status Indication | Unit OK LED + per-channel LEDs |
|---|
| Operating Temperature Range | 0°C to 60°C |
|---|
| Storage Temperature Range | −40°C to 85°C |
|---|
| Humidity Range | 5% to 95% non-condensing |
|---|
| Heat Dissipation | 90 W |
|---|
| Mounting Style | Backplane mounted |
|---|
TECHNICAL INFORMATION
Features
- Controls up to 16 output circuits within a DC electrical network.
- Operates over an input supply range of 18 to 56 volts DC.
- Provides 1500 VAC galvanic isolation between individual blocks.
- Supports configurable input filter response times from 10 ms to 100 ms.
- Includes a Unit OK LED and dedicated per-channel status indicators.
- Withstands complete power supply interruptions lasting up to 10 milliseconds.
TECHNICAL INFORMATION
Installation Guidelines
- Mount the block securely to a compatible backplane assembly.
- Maintain ambient operating temperatures between 0°C and 60°C.
- Allow adequate panel ventilation to manage thermal dissipation up to 90 watts.
- Ensure non-condensing relative humidity stays between 5% and 95%.
TECHNICAL INFORMATION
Configuration Guidelines
- Set the input filter response window between 10 ms and 100 ms based on noise conditions.
- Verify that external DC source voltage remains within 18 to 56 VDC.
- Inspect the Unit OK LED and channel indicators during startup testing.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the operating voltage range for the IC660BRD020 block?
The IC660BRD020 operates on a DC power source ranging from 18 to 56 volts DC.
How long of a power dropout can the IC660BRD020 tolerate?
The block maintains normal operation through brief power supply dropouts of up to 10 milliseconds.
What visual indicators are provided on the IC660BRD020?
The module includes a primary Unit OK LED alongside individual status LEDs for each output circuit.