PRODUCT INFORMATION
Product Overview
The General Electric IC693MDL940 is a Series 90-30 Relay Output Module. This unit features 16 total outputs organized into four groups. Each group contains four outputs for device control. Nominal operating voltages are 24V DC or 120/240V AC. The module supports an operational DC voltage range of 5 to 30 volts. The AC operational range spans 5 to 250 volts at standard 50 or 60 Hz frequencies.
Each individual output manages a maximum load current of up to 2 Amps. The total load per common reaches a maximum of 4 Amps. Connected devices require a minimum load current of 10 mA for activation. The module withstands inrush currents up to 5 Amps. Maximum response time for both turn-on and turn-off operations is 15 milliseconds. The module has a total weight of 1.50 lbs.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Weight | 1.50 lbs (0.68 kg) |
|---|
| Module Type | Relay Output Module |
|---|
| Maximum Load Current per Output | 2A |
|---|
| Maximum Load Current per Common | 4A |
|---|
| Nominal Rated DC Voltage | 24V DC |
|---|
| Nominal Rated AC Voltage | 120/240V AC |
|---|
| DC Operating Voltage | 5-30V DC |
|---|
| AC Operating Voltage | 5-250V AC, 50/60 Hz |
|---|
| Total Number of Outputs | 16 Outputs |
|---|
| Output Groups | 4 Groups of 4 Outputs Each |
|---|
| Minimum Load Current | 10 mA |
|---|
| Maximum Inrush Current | 5A |
|---|
| Maximum Response Time (On and Off) | 15 ms |
|---|
TECHNICAL INFORMATION
Features
- Provides 16 relay outputs arranged in four groups of four points.
- Supports operating voltage ranges of 5 to 30V DC and 5 to 250V AC.
- Delivers up to 2 Amps maximum load current per output.
- Accommodates up to 4 Amps maximum load current per common.
- Withstands surge inrush currents up to 5 Amps.
- Operates with maximum on and off response times of 15 milliseconds.
TECHNICAL INFORMATION
Connections / Interfaces
- Configured with 16 outputs divided across four isolated groups.
- Each output group contains four individual control points.
- Each group operates with an assigned common connection.
TECHNICAL INFORMATION
Installation Guidelines
- Verify that individual output load currents remain at or below 2 Amps.
- Ensure that shared group loads do not exceed 4 Amps per common.
- Confirm connected loads meet the 10 mA minimum operational current requirement.
TECHNICAL INFORMATION
Compatibility
- Operates within the General Electric Series 90-30 platform family.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSOperates within the General Electric Series 90-30 platform family.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the maximum current rating for the IC693MDL940?
Each output supports up to 2 Amps. Each common terminal supports up to 4 Amps maximum load.
What voltage ranges does the IC693MDL940 support?
The module operates from 5 to 30V DC or 5 to 250V AC at 50/60 Hz.
What is the response time for the IC693MDL940?
Maximum response time for both switching on and switching off is 15 milliseconds.