PRODUCT INFORMATION
Product Overview
The General Electric IC694ALG222 is an Analog input voltage module for the PACSystems RX3i platform. This module accepts unipolar signals from 0 to 10 Volts. It also accepts bipolar signals from -10 to +10 Volts. Users can configure up to sixteen single-ended channels or eight differential channels. Single-ended wiring references signals to ground and maximizes available channel density. Differential wiring uses two signal leads to provide increased resistance to electrical interference.
The module features optical isolation rated at 250 Volts AC continuous to the backplane. Isolation withstands 1500 Volts AC for one minute. Channel update rates reach 6 milliseconds for single-ended mode and 3 milliseconds for differential mode. Diagnostic indicators include a Module OK LED and an internal power supply status LED. Field signals terminate at a removable twenty-terminal connector block included with the module.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Weight | 1.50 lbs (0.68 kg) |
|---|
| Product Description | Analog input module |
|---|
| No of Channels | Single-ended: Sixteen (16) input channels Differential: Eight (8) input channels |
|---|
| Input Channels | 16 |
|---|
| Nominal Input signal | -10 V to ±10 V and 0 to 10 V |
|---|
| Input Voltage Range | 0 to 10 Volts, -10 to +10 Volts |
|---|
| Channel update rate | 13 ms |
|---|
| Wiring configuration | Single-ended / Differential |
|---|
| Calibration at 0 to 10 Volts | 2.5 millivolts per count |
|---|
| Digital Resolution | 12 bit |
|---|
| Analog input signal | 0 to 10 V (unipolar); -10 to +10 V (bipolar) |
|---|
| Calibration at -10 to 10 Volts | 5 millivolts per count |
|---|
| Analog resolution | 5 mV/20 µA/bit for ±10 V signal and 5 mV/20 µA/bit for 0-10 V |
|---|
| Resolution | 2.5 mV (1 LSB = 2.5 mV) at 0-10VDC; 5 mV (1 LSB = 5 mV) at -10V to +10V |
|---|
| Power Requirement at 5 Volts DC | 112 milliamps |
|---|
| Accuracy | 0.25% at 25ºC (77ºF) |
|---|
| Update rate | 6 milliseconds (all 16 single-ended channels); 3 milliseconds (all 8 differential channels) |
|---|
| Power Requirement at 24 Volts DC | 41 milliamps |
|---|
| Input filter response | 200 Hz |
|---|
| Calibration | 2.5 mV per count on 0 V to +10 V (unipolar) range; +/10.25% of full scale @ 25°C (77°F); +/-0.5% of full scale over specified operating temperature range |
|---|
| Operating Temperature | 0 to 60 degrees Celsius |
|---|
| Current draw | 112 mA @ 5 VDC; 4150 mA @ 24 VDC (user supplied) |
|---|
| Linearity | < 1 Least Significant Bit |
|---|
| Input impedance | 250 ohms |
|---|
| Module connector type | Terminal Block (20 screws), included with module. |
|---|
| Internal Power Consumption | 112 mA from the isolated +24 VDC supply 41 mA from +5 VDC bus on the backplane |
|---|
| Product Lifecycle Status | Active |
|---|
| Isolation, Field to Backplane (optical) and to frame ground | 250 VAC continuous; 1500 VAC for 1 minute |
|---|
TECHNICAL INFORMATION
Features
- Configurable for 16 single-ended channels or 8 differential input channels.
- Supports unipolar 0 to 10 Volts and bipolar -10 to +10 Volts ranges.
- Provides 12-bit digital resolution across all configured input channels.
- Offers optical isolation rated at 250 Volts AC continuous.
- Delivers update rates of 3 milliseconds differential and 6 milliseconds single-ended.
- Equipped with Module OK and internal power supply status diagnostic LEDs.
TECHNICAL INFORMATION
Applications
- Analog voltage signal acquisition in PACSystems RX3i programmable automation systems.
- Process monitoring requiring differential signal connections for high noise immunity.
- High-density unipolar and bipolar voltage telemetry across industrial machinery.
TECHNICAL INFORMATION
Connections / Interfaces
- Includes a removable 20-screw terminal block for field wiring terminations.
- Requires an external 24 Volts DC supply connected to backplane terminal TB1.
- Communicates directly through the PACSystems RX3i universal backplane bus.
TECHNICAL INFORMATION
Installation Guidelines
- Insert the module into any available I/O slot in the RX3i rack.
- Connect external 24 Volts DC to terminal TB1 when mounted in standard backplanes.
- Expansion backplanes supply the necessary 24 Volts DC power automatically.
- Confirm that the Module OK LED lights up during system startup.
TECHNICAL INFORMATION
Configuration Guidelines
- Configure channels individually for 0 to 10 Volts or -10 to +10 Volts.
- Select differential mode for noisy environments or single-ended mode for maximum channels.
- Factory calibration provides 2.5 millivolts per count on 0 to 10 Volt ranges.
- Factory calibration provides 5 millivolts per count on -10 to +10 Volt ranges.
TECHNICAL INFORMATION
Compatibility
- Compatible with General Electric PACSystems RX3i baseplates and expansion racks.
TECHNICAL INFORMATION
Lifecycle / Replacement Information
- Active lifecycle status recorded under original product manufacturing documentation.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSCompatible with General Electric PACSystems RX3i baseplates and expansion racks.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
How many input channels does the IC694ALG222 module provide?
The IC694ALG222 supports sixteen single-ended input channels or eight differential input channels.
What input voltage ranges does the IC694ALG222 support?
The module supports 0 to 10 Volts unipolar and -10 to +10 Volts bipolar input ranges.
What external power does the IC694ALG222 require in a standard rack?
Main rack installation requires an external 24 Volts DC supply connected to backplane terminal block TB1.
What is the indicative reference price for the IC694ALG222?
Pricing varies by market availability and condition. Stated figures are indicative market reference pricing only and are not a final quotation.