PRODUCT INFORMATION
Product Overview
The General Electric IC695ALG608 is an Analog Input module for the PACSystems RX3i platform. It installs directly into a single slot of an RX3i universal backplane. The unit provides eight single-ended input channels or four differential input channels. It converts process signals using an integrated 24-bit analog-to-digital converter. Users can configure input data as floating point IEEE 32-bit values. Alternatively, the unit delivers 16-bit integer values in a 32-bit field.
This module supports standard current ranges of 0 to 20 mA, 4 to 20 mA, and plus-minus 20 mA. It also accepts voltage signals including plus-minus 10 VDC, 0 to 10 VDC, and 1 to 5 VDC. Channel filter selections include 8 Hz, 12 Hz, 16 Hz, 40 Hz, 200 Hz, and 500 Hz. The hardware performs startup auto-calibration and provides on-board error checking. It operates with RX3i CPU firmware version 3.0 or higher. Configuration requires Machine Edition version 5.0 SP3 or later.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Weight | 1.13 lbs (0.51 kg) |
|---|
| Product Description | Non-isolated analog input module |
|---|
| Module Type | Analog Input |
|---|
| No of Channels | Eight (8) non-isolated, single-ended; Four (4) non-isolated, differential |
|---|
| Number of Inputs | 8 single-ended or 4 differential input channels |
|---|
| Input signals, Current | 0-20 mA; 4-20 mA; +/-20 mA; |
|---|
| Current Range | 0-20 mA, 4-20 mA, +/-20 mA |
|---|
| Input signals, Voltage | +/- 50 mV; +/- 150 mV; +/-10VDC; 0-10 VDC; +/-5VDC; 0-5 VDC and 1 - 5 VDC |
|---|
| Input signals | 10 VDC, 0-10 VDC, +/- 5VDC, 0-5 VDC, 1-5 VDC; 0-20 mA, 4-20 mA, +/- 20 mA |
|---|
| Voltage Range | +/-10V, 0-10V, +/-5V, 0-5V, 1-5V |
|---|
| Configurable Input Filter | 8 Hz, 12 Hz, 16 Hz, 40 Hz, 200 Hz, 500 Hz |
|---|
| Resolution | 24 bit |
|---|
| Internal Power | 3.3V: 450mA, 5V: 600 mA |
|---|
| Module resolution | 24-bit ADC converted to Floating Point or Integer |
|---|
| Output Data Format | Configurable as floating point IEEE 32 bit or 16-bit integer in a 32-bit field |
|---|
| Operating Temperature | 0 to 60 degrees Celsius (32 to 140 degrees Fahrenheit) |
|---|
| Input Data Format | Configurable as floating point IEEE 32-bit or 16-bit integer in a 32-bit field |
|---|
| Filter Options | 8Hz, 12Hz, 16Hz, 40Hz, 200Hz, 500Hz |
|---|
| Storage Temperature | -40 to 85 degrees Celsius (-40 to 185 degrees Fahrenheit) |
|---|
| Overvoltage | ±60 VDC continuous, maximum |
|---|
| Humidity | 5 to 95%, non-condensing |
|---|
| Overcurrent | ±28mA continuous, maximum |
|---|
| Programmer Version | Machine Edition version 5.0 SP3 and later |
|---|
| Open Circuit Detection time | 1 second maximum |
|---|
| Backplane Power consumption | 330 mA maximum @ 5.0V +5% / -2.5%, 600 mA maximum @ 3.3V +5% / -3% |
|---|
| Input Impedance | >100 k? voltage inputs |
|---|
| Power Dissipation | 4.83 watts maximum |
|---|
| Current Input Resistance | 249 ? ±1% |
|---|
| Terminal Blocks | Box-style (IC694TBB032), Extended Box-style (IC694TBB132), Spring-style (IC694TBS032), or Extended Spring-style (IC694TBS132) terminal Block. |
|---|
| Autocalibration | Performed during power-up |
|---|
TECHNICAL INFORMATION
Features
- Supports eight non-isolated single-ended or four non-isolated differential channels.
- Provides onboard 24-bit analog-to-digital conversion resolution.
- Accepts multiple voltage ranges and current ranges without external jumpers.
- Includes user-selectable digital filter rates from 8 Hz to 500 Hz.
- Executes full autocalibration during system power-up.
- Provides open circuit detection within one second maximum.
- Supports channel interrupts, rate of change alarms, and fault reporting.
TECHNICAL INFORMATION
Applications
- Industrial process monitoring with standard 4 to 20 mA instrumentation loops.
- Multichannel voltage sensing in PACSystems RX3i automation systems.
- Signal acquisition requiring floating point or 16-bit integer data formatting.
TECHNICAL INFORMATION
Connections / Interfaces
- Compatible with IC694TBB032 box-style terminal blocks.
- Compatible with IC694TBB132 extended box-style terminal blocks for shielded cabling.
- Compatible with IC694TBS032 spring-style terminal blocks.
- Compatible with IC694TBS132 extended spring-style terminal blocks.
TECHNICAL INFORMATION
Installation Guidelines
- Install the module into any available slot of an RX3i universal backplane.
- Secure the terminal block and ensure the locking lever is engaged.
- Confirm the green terminal block LED illuminates upon proper mechanical seating.
- Maintain ambient operating temperatures between 0 and 60 degrees Celsius.
TECHNICAL INFORMATION
Configuration Guidelines
- Configure module parameters using Machine Edition version 5.0 SP3 or later.
- Ensure RX3i CPU firmware is at version 3.0 or higher.
- Define channel wiring type as single-ended or differential in software.
- Select channel digital filtering rates between 8 Hz and 500 Hz.
TECHNICAL INFORMATION
Compatibility
- PACSystems RX3i universal backplanes.
- PACSystems RX3i CPUs with firmware version 3.0 or later.
- Terminal block models IC694TBB032, IC694TBB132, IC694TBS032, and IC694TBS132.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSPACSystems RX3i universal backplanes. PACSystems RX3i CPUs with firmware version 3.0 or later. Terminal block models IC694TBB032, IC694TBB132, IC694TBS032, and IC694TBS132.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
How many channels does the IC695ALG608 support?
The module provides eight non-isolated single-ended channels or four non-isolated differential channels.
Which software version is required to configure the IC695ALG608?
Configuration requires Machine Edition version 5.0 SP3 or later with CPU firmware 3.0 or higher.
Which terminal blocks are compatible with the IC695ALG608?
It connects to IC694TBB032, IC694TBB132, IC694TBS032, and IC694TBS132 terminal blocks.