PRODUCT INFORMATION
Product Overview
The General Electric IC697MDL340 is a discrete Output Module for the Series 90-70 programmable controller platform. This module features sixteen output points organized into four isolated groups. Each output group operates at a rated voltage of 120 Volts AC. The isolated architecture permits distinct groups to run across separate phases of an AC power source. Individual output channels supply up to 2 Amps continuous current. Internal thermal dissipation limits the total load capacity of each group to 4 Amps.
This module handles up to 10x inrush current for inductive and incandescent field devices. It controls equipment such as solenoids, indicators, motor starters, and most Size 4 contactors. Each isolated group contains an independent 10 Amp protective fuse. Top-mounted LEDs indicate point status on the PLC side and report blown fuse conditions. Built-in mechanical keying ensures correct module replacement in the field. Reference assignment is completed through software without using physical jumpers or DIP switches.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Weight | 2.38 lbs (1.08 kg) |
|---|
| Rated Voltage | 120 V AC |
|---|
| Outputs | 16 |
|---|
| Output Current/Point | 2 A |
|---|
| Output Current/Group | 4 A |
|---|
| Current Required | 0.25 A |
|---|
| Frequency | 47-63 Hz |
|---|
| DC Power | No |
|---|
| AC Power | Yes |
|---|
| LED Indicators | Yes |
|---|
TECHNICAL INFORMATION
Features
- Provides sixteen 120 V AC discrete outputs organized into four isolated groups.
- Allows independent groups to operate on separate phases of an AC power system.
- Delivers a continuous rating of 2 Amps per point and 4 Amps per group.
- Accommodates up to 10x inrush current for inductive and incandescent loads.
- Incorporates a individual 10 Amp fuse for each of the four output groups.
- Displays channel operating status and fuse failure alerts using top-mounted LED indicators.
- Employs mechanical keying to enforce correct module alignment during replacement.
- Configures I/O references entirely through software without jumpers or DIP switches.
TECHNICAL INFORMATION
Applications
- Switching control coils for Size 4 contactors and industrial motor starters.
- Operating AC solenoid valves in pneumatic and hydraulic process systems.
- Powering incandescent indicator lamps and annunciator panels in manufacturing lines.
TECHNICAL INFORMATION
Connections / Interfaces
- Sixteen discrete 120 V AC load terminals arranged across four isolated groups.
- Dedicated fuse access points corresponding to each 10 Amp group fuse.
TECHNICAL INFORMATION
Installation Guidelines
- Verify mechanical key alignment before inserting the module into the Series 90-70 rack.
- Ensure total operating current per group does not exceed 4 Amps to manage heat dissipation.
- Confirm external supply wiring matches the isolation requirements across separate phases.
TECHNICAL INFORMATION
Configuration Guidelines
- Assign I/O addresses using programming software instead of setting hardware switches.
- Confirm that load phase connections align with system isolation and fusing plans.
TECHNICAL INFORMATION
Compatibility
- Operates in General Electric Series 90-70 I/O racks.
- Compatible with AC-rated pilot loads, motor starters, solenoids, and most Size 4 contactors.
TECHNICAL INFORMATION
Lifecycle / Replacement Information
- Mechanical keying ensures replacement only with an identical module type.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSOperates in General Electric Series 90-70 I/O racks. Compatible with AC-rated pilot loads, motor starters, solenoids, and most Size 4 contactors.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the maximum current rating for the IC697MDL340?
Each point supports 2 Amps continuous current, with a total limit of 4 Amps per group.
Can the output groups on the IC697MDL340 operate on different AC phases?
Yes, the four isolated output groups can operate on separate phases of an AC power supply.
Does the IC697MDL340 require DIP switch settings for address configuration?
No, I/O references are configured via software without the need for jumpers or DIP switches.
What protection does the IC697MDL340 provide for output groups?
Each of the four groups contains an individual 10 Amp fuse with LED blown-fuse indication.