PRODUCT INFORMATION
Product Overview
The Woodward 8440-1884 easYgen Controller provides generator set control and package protection. The unit supports up to 16 gensets in island operation. It also manages a genset operating in parallel with utility mains. Multiple connectivity options allow integration into established plant automation networks. It operates on a nominal 12/24VDC supply.
Operators configure control modes through discrete inputs including Auto, Stop, Manual, and test selections. Breaker management includes slip frequency synchronization and open-close supervision. Load transfer capabilities include open or closed transition and soft loading. Engine warm-up can follow elapsed run time or coolant temperature measurements. The unit features an interactive graphical display.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Power Supply | 12/24VDC |
|---|
| Analog Resolution | 11 Bit |
|---|
| Monitoring Accuracy | ≤ 1 % |
|---|
| Overvoltage (≤ 2 min) | 80 Vdc |
|---|
| Rated Frequency | Rated frequency +/- 2 % |
|---|
| Storage Temperature | -30 to 80 degrees Celsius |
|---|
| Operation Temperature | -20 to 70 degrees Celsius |
|---|
| Humidity Rating | 95% Non-condensing |
|---|
TECHNICAL INFORMATION
Features
- Supports up to 16 generator sets in isolated island networks
- Provides parallel operation support between a generator set and utility mains
- Offers operating modes including Auto, Stop, Manual, Load test, and No Load test
- Performs breaker open-close control, phase matching synchronization, and slip frequency synchronization
- Executes load interchange, mains parallel transfer, and soft loading or unloading routines
- Regulates engine warm-up sequences using an internal timer or monitored coolant temperature
- Enables setpoint adjustment for power, reactive power, voltage, speed, frequency, and power factor
- Features a 128 x 64 dot graphical LC display with interactive soft keys and 11 configurable languages
TECHNICAL INFORMATION
Applications
- Multi-unit generator power management in isolated island grids
- Utility paralleling and base-load peak shaving installations
- Automated emergency standby power transfer systems
TECHNICAL INFORMATION
Connections / Interfaces
- Interactive 128 x 64 dot graphical LC screen with soft keys
- Discrete inputs for operating mode selection and sequence triggers
- Analog and discrete interface channels for remote setpoint adjustments
TECHNICAL INFORMATION
Installation Guidelines
- Mount within an environment maintaining operating temperatures between -20 and 70 degrees Celsius.
- Maintain non-condensing relative humidity levels at or below 95 percent.
- Verify the DC power supply wiring provides nominal 12/24VDC operating voltage.
TECHNICAL INFORMATION
Configuration Guidelines
- Select the active user interface language from 11 internal language configurations.
- Define breaker synchronization limits for phase matching and slip frequency windows.
- Program load transfer ramps and warm-up parameters based on coolant temperature or timer values.
TECHNICAL INFORMATION
Compatibility
- Compatible with easYgen family generator power distribution topologies
- Integrates into island networks containing up to 16 parallel generator sets
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSCompatible with easYgen family generator power distribution topologies Integrates into island networks containing up to 16 parallel generator sets
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What power supply is required for the Woodward 8440-1884?
The controller operates on a nominal 12/24VDC power supply and withstands 80 Vdc overvoltage for up to two minutes.
How many generator sets can the 8440-1884 controller manage in an island configuration?
The controller supports power management and protection for up to 16 generator sets operating together in island mode.
Which synchronization methods does the Woodward 8440-1884 provide for breaker control?
The unit performs phase matching synchronization and slip frequency synchronization alongside complete open and close breaker monitoring.
Can the 8440-1884 accept remote control adjustments?
Yes. Remote systems adjust power, reactive power, voltage, frequency, speed, and power factor via analog or discrete inputs.