PRODUCT INFORMATION
Product Overview
The General Electric IC660BBA106 is a 6-channel current-source analog input block for the Genius I/O system. The unit interfaces current transmitters to a supervisory controller over the serial Genius bus. Each channel supports current loops measuring 4 to 20 mA or 0 to 25 mA.
The block provides channel-to-channel isolation across all six input circuits to prevent ground loops. It operates from an incoming supply voltage of 93 to 132 VAC or 105 to 145 VDC. Onboard diagnostic capabilities include monitoring for underrange, overrange, high alarm, low alarm, and open wire conditions.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Block type | Genius current-source analog input block |
|---|
| Analog input channels | 6 |
|---|
| Network | Genius bus |
|---|
| Input ranges | 4–20 mA or 0–25 mA |
|---|
| Channel isolation | Six isolated points; channel-to-channel isolation |
|---|
| Input resolution | 1 µA |
|---|
| Selectable update rate | 16.6–400 ms |
|---|
| Full-scale accuracy | 0.1% |
|---|
| Input diagnostics | Underrange, overrange, high alarm, low alarm, open wire |
|---|
| Operating voltage | 93–132 VAC or 105–145 VDC |
|---|
| Nominal block power | 115 VAC or 125 VDC |
|---|
| Dimensions | 8.83 × 3.50 × 3.94 in (22.44 × 8.89 × 10.00 cm), as listed in the GE catalog |
|---|
TECHNICAL INFORMATION
Features
- Provides six individually isolated current input channels.
- Configurable input ranges include 4 to 20 mA and 0 to 25 mA.
- Selectable conversion update rates span from 16.6 ms to 400 ms.
- High-resolution current conversion measures signals down to 1 µA increments.
- Built-in diagnostics identify open wire, overrange, underrange, and threshold alarm events.
TECHNICAL INFORMATION
Applications
- Current-loop transmitter monitoring in industrial processes.
- Distributed analog input acquisition on Genius bus networks.
- Multi-channel isolated instrumentation interfacing for control systems.
TECHNICAL INFORMATION
Connections / Interfaces
- Screw-terminal connections for six isolated analog input channels.
- Dedicated terminals for 115 VAC or 125 VDC incoming power wiring.
- Genius serial bus communication interface connection terminals.
TECHNICAL INFORMATION
Installation Guidelines
- Mount the block securely within an enclosure meeting application environmental requirements.
- Connect incoming control power to the designated 115 VAC or 125 VDC terminals.
- Terminate field current-loop wiring to the corresponding isolated channel points.
- Maintain serial bus shielding according to standard Genius bus wiring specifications.
TECHNICAL INFORMATION
Configuration Guidelines
- Set the input operating range per channel to 4-20 mA or 0-25 mA.
- Configure the internal scan update rate between 16.6 ms and 400 ms.
- Define high alarm and low alarm reporting thresholds for system monitoring.
TECHNICAL INFORMATION
Compatibility
- Interfaces directly with General Electric Genius I/O bus controllers.
- Compatible with standard 4-20 mA and 0-25 mA current-source field devices.
TECHNICAL INFORMATION
Lifecycle / Replacement Information
- The IC660BBA106 has reached mature lifecycle status with General Electric.
- Replacement units remain available through specialized automation supply channels.
TECHNICAL RESOURCES
Documentation
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSInterfaces directly with General Electric Genius I/O bus controllers. Compatible with standard 4-20 mA and 0-25 mA current-source field devices.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the primary function of the GE IC660BBA106?
The IC660BBA106 is an isolated 6-channel current-source analog input block for the Genius I/O bus. It acquires 4-20 mA or 0-25 mA field signals.
What input power is required to operate the IC660BBA106 block?
The block operates on 93 to 132 VAC or 105 to 145 VDC. Nominal ratings are 115 VAC or 125 VDC.
Does the IC660BBA106 provide channel-to-channel isolation?
Yes, the block features channel-to-channel isolation across all six independent analog input points.
What diagnostics are supported by the IC660BBA106?
Diagnostics include detection of underrange, overrange, open wire, high alarm, and low alarm states.