PRODUCT INFORMATION
Product Overview
The ABB DI831 3BSE013212R1 is a 16-channel digital input module for S800 I/O systems. It operates at a nominal rating of 48 V d.c. using current sinking signal circuitry. The normal input voltage range spans 36 to 60 V d.c. during active operation. Each input channel draws a nominal current of 4 mA at 48 V d.c.
Each channel includes current limiting, EMC protection components, an optical isolation barrier, and an input state LED. The module cyclically executes internal self-diagnostics to verify process voltage and time synchronization. Digital input filter times can be adjusted from 0 to 100 ms to reject noise pulses. It supports Sequence of Events recording with a resolution of 0.4 ms.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Signal specification | 48 V d.c. |
|---|
| Number of channels | 16 |
|---|
| Signal type | Current sinking |
|---|
| HART | No |
|---|
| SOE | Yes |
|---|
| Redundancy | No |
|---|
| High integrity | No |
|---|
| Intrinsic safety | No |
|---|
| Mechanics | S800 |
|---|
| Input voltage range, "0" | -60 .. +10 V |
|---|
| Input voltage range, "1" | 30 .. 60 V |
|---|
| Input impedance | 9.6 kΩ |
|---|
| Isolation | Groupwise isolated from ground |
|---|
| Filter times (digital, selectable) | 0...100 ms |
|---|
| Current limiting | Sensor power can be current limited by the MTU |
|---|
| Maximum field cable length | 600 meters (656 yards) |
|---|
| Event recording accuracy | -0.3 ms...+0.7 ms |
|---|
| Event recording resolution | 0.4 ms |
|---|
| Rated insulation voltage | 50 V |
|---|
| Dielectric test voltage | 500 V a.c. |
|---|
| Power dissipation | Typ. 3.2 W |
|---|
| Current consumption +5 V Modulebus | Typ. 100 mA, Max. 120 mA |
|---|
| Current consumption +24 V Modulebus | 0 |
|---|
| Front LED’s | F(ault), R(un), W(arning), Channel 1-16 ("0" or "1") |
|---|
| Supervision | Process voltage, 1 per group; Event queue full; Time synchronization missing |
|---|
| Status indication of supervision | Module Error, Module Warning, Channel error |
|---|
| CE mark | Yes |
|---|
| Electrical safety | EN 61010-1, UL 61010-1, EN 61010-2-201, UL 61010-2-201 |
|---|
| Hazardous Location | C1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2 |
|---|
| Marine certification | ABS, BV, DNV, LR, CCS |
|---|
| Temperature, Operating | 0 to +55 °C (+32 to +131 °F), approvals are issued for +5 to +55 °C |
|---|
| Temperature, Storage | -40 to +70 °C (-40 to +158 °F) |
|---|
| Pollution degree | Degree 2, IEC 60664-1 |
|---|
| Corrosion protection | ISA-S71.04: G3 |
|---|
| Relative humidity | 5 to 95 %, non-condensing |
|---|
| Max ambient temperature | 55 °C (131 °F), for vertical mounting in compact MTU 40 °C (104 °F) |
|---|
| Protection class | IP20 according to IEC 60529 |
|---|
| EMC | EN 61000-6-4 and EN 61000-6-2 |
|---|
| Overvoltage categories | IEC/EN 60664-1, EN 50178 |
|---|
| RoHS compliance | EU RoHS, UAE RoHS, CN RoHS |
|---|
| WEEE compliance | DIRECTIVE/2012/19/EU |
|---|
| Use with MTU | TU810, TU812, TU814, TU818, TU830, TU833, TU838, TU850 |
|---|
| Keying code | BD |
|---|
| Width | 45 mm |
|---|
| Depth | 102 mm, 111 mm including connector |
|---|
| Height | 119 mm |
|---|
| Weight | 0.22 kg |
|---|
TECHNICAL INFORMATION
Features
- Provides 16 digital input channels configured for 48 V d.c. current sinking operation.
- Features high-resolution Sequence of Events recording with 0.4 ms resolution.
- Selectable digital input filtering adjustable between 0 and 100 ms.
- Includes optical isolation barriers providing groupwise separation from system ground.
- Front panel LEDs indicate Run, Fault, Warning, and individual channel logic states.
- Cyclic self-diagnostics supervise group process voltage, event queues, and time synchronization.
TECHNICAL INFORMATION
Applications
- Digital state monitoring in S800 I/O installations.
- High-speed event timestamping and Sequence of Events recording across industrial processes.
- Supervision of 48 V d.c. field sensors, contacts, and switching circuits.
TECHNICAL INFORMATION
Connections / Interfaces
- Communicates across the Modulebus backplane using 5 V d.c. power.
- Mounts onto compatible S800 Module Termination Units using keying code BD.
- Supports field cable runs reaching up to 600 meters in length.
TECHNICAL INFORMATION
Installation Guidelines
- Plug the module onto a compatible S800 Module Termination Unit.
- Verify the mechanical keying code matches code BD before inserting the module.
- Maintain ambient operating temperatures below 55 °C for standard horizontal mounting orientations.
- Derate maximum ambient operating temperature to 40 °C when mounting vertically in compact MTUs.
TECHNICAL INFORMATION
Configuration Guidelines
- Set digital filter durations between 0 and 100 ms per channel.
- Configure Sequence of Events recording parameters and time synchronization settings.
- Supervise alarm status for group voltage dropouts and event queue overflow.
TECHNICAL INFORMATION
Compatibility
- Mounts on Module Termination Units TU810, TU812, TU814, and TU818.
- Mounts on Module Termination Units TU830, TU833, TU838, and TU850.
- Operates within S800 I/O Modulebus communication systems.
TECHNICAL INFORMATION
Compliance and Certifications
- Meets electrical safety requirements of EN 61010-1, UL 61010-1, EN 61010-2-201, and UL 61010-2-201.
- Certified for hazardous locations under Class I Division 2, Class I Zone 2, and ATEX Zone 2.
- Carries marine approvals from ABS, BV, DNV, LR, and CCS.
- Complies with EMC standards EN 61000-6-2 and EN 61000-6-4.
- Conforms to EU RoHS, UAE RoHS, CN RoHS, and WEEE directives.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSMounts on Module Termination Units TU810, TU812, TU814, and TU818. Mounts on Module Termination Units TU830, TU833, TU838, and TU850. Operates within S800 I/O Modulebus communication systems.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the primary function of the ABB DI831 3BSE013212R1 module?
The DI831 acquires 16 channels of 48 V d.c. current sinking digital signals for S800 I/O.
Does the DI831 module support Sequence of Events recording?
Yes, the module supports Sequence of Events recording with a 0.4 ms resolution.
Which Module Termination Units are compatible with the DI831?
Compatible MTUs include TU810, TU812, TU814, TU818, TU830, TU833, TU838, and TU850.
What is the maximum field wiring length supported by the DI831?
The module supports field cable runs up to 600 meters.