PRODUCT INFORMATION
Product Overview
The ABB ACS580-01-023A-4+K454 3AUA0000222927 is an ACS580 series AC drive. This wall-mounted variable frequency unit operates with an input voltage range between 380 and 500 V AC. It supports a three-phase supply network running at 50 or 60 Hz line frequency. The drive delivers an apparent power output of 19 kVA within an R2 physical frame size.
This drive provides an output rating of 15 HP and 23 A under light-overload conditions. For heavy-duty operations, it supplies 10 HP continuous power with 14 A output current. The enclosure conforms to NEMA Type 1 and IP21 environmental standards for wall mounting. An integrated +K454 option provides PROFIBUS DP fieldbus communication capabilities via an internal adapter module.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Input Voltage (Uin) | 380 to 500 V AC, 3-phase |
|---|
| Frequency | 50/60 Hz |
|---|
| Output Power (Light-Overload, UL) | 15 HP |
|---|
| Output Current (Light-Overload, UL) | 23 A |
|---|
| Output Power (Heavy-Duty, UL) | 10 HP |
|---|
| Output Current (Heavy-Duty, UL) | 14 A |
|---|
| Apparent Power Output | 19 kVA |
|---|
| Frame Size | R2 |
|---|
| Enclosure Type | NEMA Type 1 / IP21 |
|---|
| Mounting Type | Wall-mounting |
|---|
| Efficiency Level | IE2 |
|---|
| Standby Loss | 14 W |
|---|
| Temperature Rating | Maximum 40 °C (104 °F) |
|---|
| Communication | PROFIBUS DP via adapter module |
|---|
TECHNICAL INFORMATION
Features
- Supplies 15 HP and 23 A output under light-overload operating limits.
- Delivers 10 HP and 14 A output for heavy-duty industrial demand.
- Features an R2 frame size designed for wall-mounting installation.
- Operates on a 3-phase input voltage from 380 V to 500 V AC.
- Includes a PROFIBUS DP communication adapter indicated by the +K454 configuration code.
- Maintains an IE2 international efficiency classification during operation.
- Produces a low standby power loss of 14 W when inactive.
TECHNICAL INFORMATION
Connections / Interfaces
- Provides terminal connections for three-phase AC input and three-phase motor output.
- Incorporates a dedicated PROFIBUS DP adapter module for external fieldbus communication.
TECHNICAL INFORMATION
Installation Guidelines
- Mount the R2 frame unit vertically onto a flat, non-flammable wall surface.
- Ensure ambient operational temperatures do not exceed 40 °C (104 °F).
- Verify the enclosure meets NEMA Type 1 or IP21 environmental protection requirements.
- Connect a three-phase input power line within the verified 380 to 500 V AC range.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the power rating of the ABB ACS580-01-023A-4+K454 drive?
The drive provides 15 HP for light-overload use and 10 HP for heavy-duty industrial duty.
What fieldbus communication protocol does the +K454 option include?
The +K454 code designates an integrated adapter module configured for PROFIBUS DP network communication.
What is the reference price for the 3AUA0000222927 drive?
Market observations indicate a reference price of approximately $2,496.00 for factory-new condition. This figure is an indicative market reference only and does not constitute a final quotation.
What frame size and enclosure rating does this drive feature?
The unit is built in an R2 frame size with a NEMA Type 1 and IP21 rated enclosure.