PRODUCT INFORMATION
Product Overview
The Allen-Bradley MVI69E-MBTCP CompactLogix Communication Module provides Modbus TCP/IP connectivity for 1769 control architectures. This single-slot module transfers input and output data between Modbus networks and the CompactLogix backplane. It features one RJ45 Ethernet communication port supporting 10/100 Base-T speeds. The module interfaces directly with compatible Modbus TCP/IP client and server devices.
The module provides up to 10,000 words of internal data memory for register handling. Selectable backplane I/O sizes include 60, 120, or 240 sixteen-bit integers. System layout requires mounting within a power supply distance rating of 4 slots. Installations with 1769-L43 or 1769-L45 controllers require placement in the first two slots. Configuration requires ProSoft Configuration Builder and ProSoft Discovery Service software tools.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Weight | 1.00 lbs (0.45 kg) |
|---|
| Available Data | 10,000 words |
|---|
| I/O Size | 60/120/240 - 16 bit integers |
|---|
| Module width | Single slot |
|---|
| Compatible rack | 1769 CompactLogix |
|---|
| Floating point data | Floating point data movement supported, including configurable support for Enron, Daniel®, and other implementations |
|---|
| Power Supply distance rating | 4 |
|---|
| Communication port | One (1) RJ45 interface |
|---|
| Data Rate | 10 / 100 Mbps |
|---|
| LED indicators | Configuration Status, Application Status, Backplane Connectivity Status, Module Status |
|---|
| Operating Temperature | 32° F to 140° F (0° C to 60° C) |
|---|
| Storage Temperature | -40° F to 185° F (-40° C to 85° C) |
|---|
| Operating Shock | 30 g |
|---|
| Relative humidity | 5% to 95% (without condensation) |
|---|
| Backplane Current load | 500 mA @ 5.1 VDC |
|---|
| Configuration | ProSoft Configuration Builder |
|---|
| Modbus Client Connections | 20 |
|---|
| Commands per Client Connection | 16 max. |
|---|
| Current Load | 500 mA @ 5 VDC |
|---|
TECHNICAL INFORMATION
Features
- Supports both Modbus TCP/IP Client and Server connectivity across industrial networks.
- Provides one RJ45 Ethernet communication port supporting 10/100 Base-T data rates.
- Maintains up to 20 Modbus Client connections with up to 16 commands per connection.
- Includes internal register storage capacity of up to 10,000 words.
- Supports floating-point data movement including Enron and Daniel implementations.
- Provides LED indicators for module status, backplane activity, Ethernet status, and configuration.
TECHNICAL INFORMATION
Applications
- Interfacing CompactLogix systems with external Modbus TCP/IP client devices.
- Connecting 1769 architectures to Modbus TCP/IP server field equipment.
- Facilitating bidirectional data transfer between Modbus networks and CompactLogix backplanes.
TECHNICAL INFORMATION
Connections / Interfaces
- Provides one RJ45 communication port supporting 10/100 Base-T Ethernet rates.
- Requires Category 5 or higher twisted-pair cabling for network connections.
- Connects directly to the 1769 CompactLogix backplane across one slot.
TECHNICAL INFORMATION
Installation Guidelines
- Install the module into a compatible 1769 CompactLogix rack with one free slot.
- Maintain a maximum power supply distance rating of 4 module slots.
- Install the unit in the first two slots when using 1769-L43 or 1769-L45 controllers.
- Ensure the hardware setup jumper remains in the factory default OFF position.
- Secure the module firmly to the rack to prevent backplane integration faults.
TECHNICAL INFORMATION
Configuration Guidelines
- Configure data mapping and network parameters using ProSoft Configuration Builder.
- Identify hardware nodes on the local Ethernet network using ProSoft Discovery Service.
- Select I/O data transfer sizes of 60, 120, or 240 sixteen-bit integers.
TECHNICAL INFORMATION
Compatibility
- Operates in 1769 CompactLogix racks with compatible system power supplies.
- Supports connection with standard Modbus TCP/IP client and server devices.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSOperates in 1769 CompactLogix racks with compatible system power supplies. Supports connection with standard Modbus TCP/IP client and server devices.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the primary function of the MVI69E-MBTCP module?
The module enables Modbus TCP/IP communication between external devices and Allen-Bradley 1769 CompactLogix controllers.
What are the slot placement rules for the MVI69E-MBTCP?
It requires a power supply distance of 4 slots. With 1769-L43 or 1769-L45 controllers, install it in the first two slots.
How many Modbus Client connections does the module support?
The module supports up to 20 Modbus Client connections with a maximum of 16 commands each.
What software is required to configure the MVI69E-MBTCP?
Configuration requires ProSoft Configuration Builder and ProSoft Discovery Service software utilities.