PRODUCT INFORMATION
Product Overview
The Allen-Bradley 2711P-T15C4D8 is a PanelView Plus 6 1500 Operator Terminal in the PanelView series. This visualization hardware provides a 15-inch color active-matrix TFT display for process monitoring and equipment control. It features an analog resistive touchscreen rated for at least one million actuations.
The operator interface delivers 1024 x 768 resolution with 18-bit color graphics and 300 nits typical brightness. The internal assembly integrates a 2711P-RDT15C display module and a 2711P-RP8D logic module. This unit operates on direct current input power ranging from 18 to 32 volts DC. It includes 512 MB of RAM and 512 MB of non-volatile flash memory for application runtime storage.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| UPC | 612598876785 |
|---|
| Weight | 9.31 lbs (4.22 kg) |
|---|
| Backlight | CCFL, 50,000 hours min at 25 ° C (77 °F), field replaceable |
|---|
| Display Type | Color active-matrix TFT |
|---|
| Display Size | 15.0 inches |
|---|
| Operator Input | Touch |
|---|
| Lifecycle status | End of life |
|---|
| Display Area | 304 x 228 mm (12.0 x 9.0 in.) |
|---|
| Resolution | 1024 x 768, 18-bit color graphics |
|---|
| Touch | 1 million presses |
|---|
| Internal memory | 512MB Flash Memory / 512 MB Random Access Memory |
|---|
| Integrated ports | Ethernet, RS-232, 2 USB host |
|---|
| Input Voltage range | 18-30VDC |
|---|
| Input Type | Touchscreen |
|---|
| Communication | Ethernet and RS-232 ports |
|---|
| Input Power | 18 to 32 Volts DC |
|---|
| Memory | 512 MB RAM |
|---|
| Communication Cable | 2711-NC13 |
|---|
| Enclosure Rating | NEMA/UL Type 12,13, 4X and IEC IP54, IP65 |
|---|
| Display Module | 2711P-RDT15C |
|---|
| Logic Module | 2711P-RP8D |
|---|
| Mounting Hardware | 2711P-RTMC |
|---|
| Size | 15 inch (1500 color) |
|---|
| Panel Cutout Height | 305 mm (12.00 in) |
|---|
| Panel Cutout Width | 419 mm (16.50 in) |
|---|
| Terminal Height | 330 mm (12.97 in) |
|---|
| Terminal Width | 469 mm (18.46 in) |
|---|
| Terminal Overall Depth | 65 mm (2.55 in) |
|---|
| Terminal Mounted Depth | 93 mm (3.65 in) |
|---|
| Display Size (Diagonal) | 15 in. |
|---|
| Viewing Area | 304 x 228 mm (12.0 x 9.0 in.) |
|---|
| Display Resolution | 1024 x 768, 18-bit color graphics |
|---|
| Typical Brightness | 300 cd/m2 (Nits) |
|---|
TECHNICAL INFORMATION
Features
- Provides a 15-inch color active-matrix TFT display with 1024 x 768 resolution and 18-bit color graphics.
- Features an analog resistive touchscreen rated for at least one million actuations.
- Equipped with a field-replaceable CCFL backlight rated for 50,000 hours minimum at 25 degrees Celsius.
- Offers built-in connectivity through an Ethernet port, an RS-232 serial port, and two USB host ports.
- Contains 512 MB of system RAM and 512 MB of non-volatile flash memory for application storage.
- Operates using a nominal direct current power supply across an 18 to 32 VDC range.
TECHNICAL INFORMATION
Applications
- Industrial human-machine interface applications requiring graphic process monitoring and touch control.
- Distributed machine control architectures communicating over local Ethernet and serial networks.
- Hazardous location control panels requiring Class I Div 2 or Class II Div 2 ratings.
TECHNICAL INFORMATION
Connections / Interfaces
- An integrated Ethernet port connects to controllers and supervisory networks over EtherNet/IP.
- The Ethernet interface supports communication parameter configuration, application transfers, and network printing.
- One RS-232 serial communication port supports point-to-point controller links using a 2711-NC13 communication cable.
- Two USB host ports accommodate compatible external peripheral devices.
TECHNICAL INFORMATION
Installation Guidelines
- Flush mount the operator terminal into an enclosure cutout measuring 305 mm high by 419 mm wide.
- Secure the terminal inside the enclosure using 2711P-RTMC mounting hardware.
- The enclosure must meet NEMA or UL Type 12, 13, 4X indoor, or IEC IP54, IP65 ratings.
- Connect the unit to an isolated DC power source supplying between 18 and 32 volts DC.
TECHNICAL INFORMATION
Configuration Guidelines
- Access the on-screen configuration menus to adjust network settings for the integrated Ethernet port.
- Configure serial communication settings to match connected PLC or controller specifications.
TECHNICAL INFORMATION
Compatibility
- Compatible with Allen-Bradley 2711-NC13 communication cables for RS-232 connectivity.
- Utilizes the 2711P-RDT15C display module and the 2711P-RP8D logic module.
TECHNICAL INFORMATION
Lifecycle / Replacement Information
- The manufacturer lifecycle status for catalog number 2711P-T15C4D8 is end of life.
- Hardware modules comprise the 2711P-RDT15C display module and the 2711P-RP8D logic module.
- Replacement backlights can be serviced in the field to extend terminal operating life.
TECHNICAL INFORMATION
Compliance and Certifications
- Rated for Class I Div 2 Groups A, B, C, D hazardous locations.
- Rated for Class II Div 2 Groups F and G hazardous locations.
- Rated for Class III hazardous locations.
- Enclosure protection complies with NEMA and UL Type 12, 13, 4X indoor, and IEC IP54 and IP65.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSCompatible with Allen-Bradley 2711-NC13 communication cables for RS-232 connectivity. Utilizes the 2711P-RDT15C display module and the 2711P-RP8D logic module.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What logic module and display module are used in the 2711P-T15C4D8?
The unit integrates a 2711P-RP8D logic module and a 2711P-RDT15C display module. Both modules form the complete 15-inch DC terminal assembly.
What are the power requirements for the 2711P-T15C4D8 terminal?
The terminal requires direct current power. It operates across an input voltage range of 18 to 32 volts DC.
What is the panel cutout size required for installation?
The panel cutout requires a height of 305 mm (12.00 in) and a width of 419 mm (16.50 in).
What communication ports are built into the 2711P-T15C4D8?
The terminal includes an Ethernet port, an RS-232 serial port, and two USB host ports. Ethernet supports EtherNet/IP protocol communication.
What is the current lifecycle status and pricing for the 2711P-T15C4D8?
The terminal lifecycle status is end of life. Any pricing figures are indicative market reference pricing only and are not a final quotation.