PRODUCT INFORMATION
Product Overview
The General Electric IC693MDL930 is a Series 90-30 Digital I/O module. It provides eight individually isolated Normally Open Form A relay output circuits. Each output operates across 5 to 30 VDC or 5 to 250 VAC. The module occupies a single slot in any 5-slot or 10-slot backplane. It integrates with Series 90-30 modular and embedded CPU assemblies.
The unit delivers a switching capacity of 4 amperes maximum for resistive loads. Pilot duty loads support up to 2 amperes per point. Total current per module reaches 20 amperes maximum under UL installations. Backplane power consumption is 6 mA from 5 VDC and 70 mA from 24 VDC.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Weight | 1.31 lbs (0.60 kg) |
|---|
| Product Description | Discrete output module |
|---|
| Eight (8), individually isolated | Isolation: |
|---|
| Relay outputs | 8 |
|---|
| 1500 volts between field side and logic side; 500 volts between groups | Output voltage range |
|---|
| Output switching capacity | 4 Amps |
|---|
| No of Channels | Eight (8) |
|---|
| Fuses | No |
|---|
| Nominal output voltage | 24 VDC; 120 VAC / 240 VAC |
|---|
| Output groupings | Individually isolated channels |
|---|
| LED indicators | Yes |
|---|
| Maximum Load | 4 amps resistive maximum per output: 2 amps pilot duty per output 20 amps maximum per module for UL installations |
|---|
| Rated voltage | 24 Volts DC or 120 / 240 Volts AC |
|---|
| Minimum load | 10 mA |
|---|
| Maximum output current | 4 Amperes, maximum for resistive loads per point; 2 Amperes for pilot duty loads per point; 20 Amperes per module for UL installations |
|---|
| Operating voltage | 5 to 30 Volts DC or 5 to 250 Volts AC |
|---|
| Maximum inrush current | 5 Amperes |
|---|
| Response time | 15 ms |
|---|
| Operating temperature | 0 to 50 degrees Celsius |
|---|
| Current draw | 6 mA (all outputs on) from 5 volt bus on backplane; 70 mA (all outputs on) from relay 24V bus on backplane |
|---|
| Operating voltages | 5-30 / 5-250 VAC |
|---|
| Product Lifecycle Status* | Discontinued/Obsolete |
|---|
| On response time, maximum | 15 ms |
|---|
| Switching Frequency | 20 Cycles per minute |
|---|
| Off response time, maximum | 15 ms |
|---|
| Module width | Single slot |
|---|
| Product lifecycle | Obsolete |
|---|
TECHNICAL INFORMATION
Features
- Eight individually isolated Form A normally open relay contacts.
- Supports operating voltages from 5 to 30 VDC and 5 to 250 VAC.
- Provides 4 A resistive load rating and 2 A pilot duty rating per point.
- Includes top-mounted LED indicators for displaying output point status.
- Offers 1500 V isolation between field side and logic side.
TECHNICAL INFORMATION
Applications
- Control of industrial motor starters and contactors.
- Actuation of pneumatic and hydraulic solenoid valves.
- Interfacing with external indicating lamps and signaling alarms.
TECHNICAL INFORMATION
Connections / Interfaces
- Requires user-supplied external power for field loads.
- Each channel includes an independent return terminal for multi-voltage operation.
- Connects to Series 90-30 backplane via single-slot edge connector.
TECHNICAL INFORMATION
Installation Guidelines
- Installs into any available slot of a 5-slot or 10-slot backplane.
- External suppressors are recommended when switching inductive loads.
- Maintain ambient operating temperatures between 0 and 50 degrees Celsius.
TECHNICAL INFORMATION
Compatibility
- Compatible with General Electric Series 90-30 modular and embedded CPU racks.
- Supports PACSystems RX3i and RX7i architectures as distributed I/O.
TECHNICAL INFORMATION
Lifecycle / Replacement Information
- The IC693MDL930 module is classified as obsolete by the original manufacturer.
- Aituos Controls supplies tested replacement modules to sustain legacy installations.
TECHNICAL INFORMATION
Compliance and Certifications
- UL recognized for up to 20 amperes maximum per module.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSCompatible with General Electric Series 90-30 modular and embedded CPU racks. Supports PACSystems RX3i and RX7i architectures as distributed I/O.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the load capacity of each IC693MDL930 output channel?
Each output channel supports 4 amperes for resistive loads and 2 amperes for pilot duty loads.
Does the IC693MDL930 module contain built-in fuses?
No, the IC693MDL930 does not feature internal fuses. External fuse protection must be provided by the user.
Can individual channels switch different voltages simultaneously?
Yes. Each channel is isolated, allowing different operating voltages across the eight separate circuits.
What is the pricing and availability for the IC693MDL930?
Quotations depend on stock condition and destination. Any stated market figures are indicative reference pricing only, not a final quotation.