PRODUCT INFORMATION
Product Overview
The General Electric IC610MDL106 is a 16-point DC input module for the GE Series One system. It interfaces field input devices operating at a nominal voltage of 24 VDC. Each discrete input channel draws an operating current of 16 mA. The module tolerates a maximum open circuit voltage of up to 36 VDC. Internal circuit architecture supports discrete signal monitoring across automation assemblies.
This hardware detects an ON level from 0 to 3 VDC. The OFF state covers the range between 18 and 36 VDC. Signal transition response time ranges from 4 to 15 milliseconds for both switching directions. Backplane power loading equals 3 units at 9 VDC and 21 units at 24 VDC. The unit has an assembled shipping weight of 2.00 lbs.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Input Current | 16 mA |
|---|
| Maximum Open Circuit Voltage | 36 VDC |
|---|
| Number of Inputs | 16 |
|---|
| OFF Level Voltage | 18 to 36 VDC |
|---|
| ON Level Voltage | 0 to 3 VDC |
|---|
| Product | Input Module |
|---|
| Product Line | Series One |
|---|
| Response Time (OFF to ON and ON to OFF) | 4 to 15 ms |
|---|
| Units of Load at 24 VDC | 21 Units |
|---|
| Units of Load at 9 VDC | 3 Units |
|---|
| Voltage | 24 VDC |
|---|
| Weight | 2.00 lbs (0.91 kg) |
|---|
TECHNICAL INFORMATION
Features
- Provides 16 discrete input channels for 24 VDC field devices.
- Draws a consistent input current of 16 mA per channel.
- Withstands a maximum open circuit voltage rating of 36 VDC.
- Features a signal transition response time between 4 and 15 milliseconds.
- Presents a backplane load of 3 units at 9 VDC and 21 units at 24 VDC.
TECHNICAL INFORMATION
Applications
- Interfacing field limit switches and pushbuttons into GE Series One PLC racks.
- Monitoring discrete DC level sensors within industrial automation assemblies.
TECHNICAL INFORMATION
Connections / Interfaces
- Direct backplane bus interface for GE Series One chassis slots.
- Field wiring terminal points supporting 16 discrete input circuits.
TECHNICAL INFORMATION
Installation Guidelines
- Verify the rack power supply is disconnected before inserting or removing the module.
- Seat the module firmly into the selected GE Series One slot to ensure bus engagement.
- Connect 24 VDC field wiring ensuring input voltages remain within operational thresholds.
TECHNICAL INFORMATION
Configuration Guidelines
- Map the 16 discrete input addresses in the system program according to rack slot allocation.
TECHNICAL INFORMATION
Compatibility
- Compatible with General Electric Series One programmable controller racks.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSCompatible with General Electric Series One programmable controller racks.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What are the voltage thresholds for the IC610MDL106 input channels?
An input voltage between 0 and 3 VDC registers as ON. Voltages between 18 and 36 VDC indicate an OFF state.
What is the switching response speed of the IC610MDL106A module?
Signal transitions between OFF and ON or ON and OFF occur within 4 to 15 milliseconds.
How much backplane power does the IC610MDL106 consume?
The module requires 3 units of load at 9 VDC and 21 units of load at 24 VDC.