PRODUCT INFORMATION
Product Overview
The General Electric IC670MDL330 is an AC discrete output module from the Field Control series. It provides 16 sourcing output channels arranged into a single isolated group. The module handles nominal AC loads ranging from 12 to 120 VAC. Operating line frequency spans from 47 to 63 Hz. Each individual output channel supports continuous load currents up to 1 Ampere. Total load current across the entire module cannot exceed 4 Amperes.
A Field Control Bus Interface Unit delivers logic power to the module. The interface unit communicates through a serial data stream containing 16 bits of output data. During transmission, the module loops data back to the interface unit for verification. Individual channel status LEDs indicate the state of each output point. An additional Fuse OK LED monitors the status of the integrated group protection fuse.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Weight | 1.50 lbs (0.68 kg) |
|---|
| Product Description | Discrete Output Module |
|---|
| No. of channels | Sixteen (16) |
|---|
| Number of Outputs | 16 |
|---|
| Output signal, nominal | 12-120 VAC |
|---|
| Discrete Outputs | Yes |
|---|
| Output signal, range | 10-132 VAC |
|---|
| Voltage Type | AC |
|---|
| Output current | 1 A per point; 4 A per module |
|---|
| Voltage Rating | 12 to 120 Volts AC |
|---|
| Current Drawn from BIU power supply | 275 mA, maximum |
|---|
| Current Rating | 1 Amp |
|---|
| User input to logic, user input to frame ground Isolation | 1500 VAC for 1 minute; 250 VAC, continuous |
|---|
| Discrete Output Data | 2 Bytes or 16 Bits |
|---|
| Output grouping | Single group |
|---|
| Output response time | ½ cycle |
|---|
| Protection | Built-in fuse for group protection; Individual RC snubber circuit |
|---|
| Output Voltage Drop | 2.0 volts maximum |
|---|
| Output Leakage Current | less than 2 mA maximum at 120 VAC |
|---|
TECHNICAL INFORMATION
Features
- Provides 16 discrete sourcing AC output points in one common group.
- Delivers 1 Amp continuous current per channel and 4 Amperes total per module.
- Features a half-cycle switching response time for both turn-on and turn-off operations.
- Contains individual resistor-capacitor snubber circuits on every output channel.
- Protects output circuits with an onboard 5 Ampere slow-blow fuse.
- Includes individual point status LEDs and a dedicated blown fuse indicator LED.
- Supports automatic data loopback to the Bus Interface Unit for verification.
TECHNICAL INFORMATION
Applications
- Energizing alternating-current solenoid valves and actuator coils.
- Switching AC motor starter coils and interposing relays.
- Driving industrial panel pilot lights and audible annunciators.
TECHNICAL INFORMATION
Connections / Interfaces
- Operates across an AC load voltage range of 10 to 132 VAC.
- Connects to the backplane via a Field Control Bus Interface Unit.
- Draws a maximum of 275 mA from the Bus Interface Unit power supply.
- Provides 1500 VAC isolation for one minute between field circuits and logic ground.
TECHNICAL INFORMATION
Installation Guidelines
- Ensure external power is disconnected prior to module servicing or fuse replacement.
- Verify the total simultaneous load current does not exceed the 4 Ampere module limit.
- Replace a blown fuse using an exact 5 Ampere slow-blow fuse measuring 5 x 20 mm.
TECHNICAL INFORMATION
Configuration Guidelines
- Configure output default states and fault reporting through the host Bus Interface Unit.
- Allocate two bytes (16 bits) of discrete output memory in the controller configuration.
TECHNICAL INFORMATION
Compatibility
- Integrates directly with General Electric Field Control I/O stations and Bus Interface Units.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSIntegrates directly with General Electric Field Control I/O stations and Bus Interface Units.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the switching capacity of each point on the IC670MDL330?
Each output point handles up to 1.0 Ampere continuous load current across 10 to 132 VAC.
What is the total current limit for the entire IC670MDL330 module?
The complete module has a maximum total current rating of 4 Amperes across all 16 points.
What type of replacement fuse is required for the IC670MDL330?
The module uses a replaceable 5 Ampere slow-blow fuse measuring 5 by 20 mm.
How does the module verify communication with the Bus Interface Unit?
The module automatically loops serial output data back to the Bus Interface Unit for verification.