PRODUCT INFORMATION
Product Overview
The General Electric IS420YAICS1B is an Analog I/O Pack designed for the Mark VI / Mark VIe series. It interfaces between up to two Ethernet networks and an associated analog terminal board. Data transmits and receives through dual RJ45 Ethernet connectors. The pack handles up to ten analog input channels. Two channels support plus or minus 1 mA or 4-20 mA current inputs. The remaining eight channels accept voltage or 4-20 mA current loops. Supported voltage inputs include plus or minus 5 V or 10 V.
The assembly consists of a common BPPC processor board and a data acquisition board. Diagnostic fault detection is handled solely through the data acquisition board. The unit operates in simplex or Triple Modular Redundant configurations. Dual redundancy applications are not supported. Compatible terminal boards include the TBAISIC and STAIS2A models. Power-up self-tests check flash memory, RAM, processor hardware, and Ethernet ports. The pack also continuously monitors internal power supplies.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Ambient Temperature Range | -40 to 158 °F |
|---|
| Compatible Firmware | V05.01 or Later |
|---|
| ControlST Software Suite Version | V06.01 and Later Versions |
|---|
| Dimensions | H 3.25 in x W 1.65 in x D 4.78 in |
|---|
| Functional Abbreviation | YAIC |
|---|
| Input Converter Resolution | 16-bit ADC |
|---|
| Power Consumption | 5.3 Watts Typical |
|---|
| Processor Board | BPPC |
|---|
TECHNICAL INFORMATION
Features
- Interfaces with up to two Ethernet networks using dual RJ45 ports.
- Converts up to ten analog inputs via a 16-bit analog-to-digital converter.
- Supports two inputs configured for plus or minus 1 mA or 4-20 mA.
- Handles eight inputs configured for voltage or 4-20 mA current loops.
- Executes diagnostic fault detection solely on the dedicated data acquisition board.
- Supports simplex and Triple Modular Redundancy system architectures.
- Performs power-up self-tests on memory, Ethernet ports, and processor circuitry.
TECHNICAL INFORMATION
Applications
- Mark VIe turbine control system analog data acquisition.
- Simplex turbine I/O monitoring configurations.
- Triple Modular Redundant turbine control and protection architectures.
TECHNICAL INFORMATION
Connections / Interfaces
- Dual RJ45 Ethernet communication connectors.
- Direct interface connection to compatible TBAISIC or STAIS2A terminal boards.
TECHNICAL INFORMATION
Installation Guidelines
- Mount the pack directly onto compatible TBAISIC or STAIS2A terminal boards.
- Maintain operating temperatures within the specified -40 to 158 °F range.
TECHNICAL INFORMATION
Configuration Guidelines
- Configure network communication via ControlST Software Suite Version V06.01 or later.
- Operate hardware using compatible firmware version V05.01 or later.
TECHNICAL INFORMATION
Compatibility
- Compatible with TBAISIC terminal boards.
- Compatible with STAIS2A terminal boards.
- Requires ControlST Software Suite Version V06.01 or later.
- Requires firmware version V05.01 or later.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSCompatible with TBAISIC terminal boards. Compatible with STAIS2A terminal boards. Requires ControlST Software Suite Version V06.01 or later. Requires firmware version V05.01 or later.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What redundancy configurations does the IS420YAICS1B support?
The pack supports simplex and Triple Modular Redundant configurations. It cannot operate in dual redundancy applications.
Which terminal boards connect to the IS420YAICS1B pack?
The pack interfaces directly with Mark VIe TBAISIC and STAIS2A terminal boards.
What analog input types can the IS420YAICS1B process?
It handles two configurable current inputs and eight inputs for voltage or current loops.
What software suite is required to configure the IS420YAICS1B?
The unit requires ControlST Software Suite Version V06.01 or later versions.