PRODUCT INFORMATION
Product Overview
General Electric IS220PTCCH1A is a Thermocouple Input Module designed for Mark VI / Mark VIe control systems. The module interfaces one or two Ethernet networks with a thermocouple input terminal board. It contains an AMD-K6 300 MHz processor board common to distributed packs. It also incorporates an acquisition board specific to thermocouple temperature measurement.
The pack handles up to 12 thermocouple inputs across E, J, K, and S types. Two packs can combine on a TBTCH1C terminal board to service 24 inputs. A Triple Modular Redundant configuration uses three packs on a TBTCH1B terminal board. Output connects to the terminal board through a DC-37 pin connector. Dual RJ45 Ethernet ports handle communication with the system controllers.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Function | Thermocouple Input Module |
|---|
| Number of Channels | 12 |
|---|
| Thermocouple Types | E, J, K, S |
|---|
| Span | -8 mV to +45 mV |
|---|
| A/D Converter | 16-bit |
|---|
| Common Mode Voltage | +5 Volts |
|---|
| Normal Mode Rejection | 250mV |
|---|
| Microprocessor | AMD-K6 300 MHz |
|---|
| Operating temperature | -30 to 65 °C |
|---|
| Size | 8.26 cm wide x 4.19 cm |
|---|
| Technology | Surface Mount |
|---|
TECHNICAL INFORMATION
Features
- Direct connection to terminal boards via a DC-37 pin connector.
- Dual independent 10/100 RJ45 Ethernet ports support control network communication.
- Onboard 16-bit analog-to-digital converter provides signal digitization.
- Supports thermocouple sensor types E, J, K, and S.
- Includes an intrinsic soft-start feature to control power inrush current.
- Visual diagnostic LEDs and a local infrared serial port provide hardware diagnostics.
TECHNICAL INFORMATION
Applications
- Distributed temperature data acquisition in GE Mark VIe distributed control systems.
- Triple Modular Redundant thermocouple configurations with TBTCH1B terminal boards.
- Dual-pack 24-channel temperature acquisition configurations on TBTCH1C terminal boards.
TECHNICAL INFORMATION
Connections / Interfaces
- Dual RJ45 10/100 Ethernet ports connect to control network switches.
- A three-pin power input connector receives pack operating power.
- A DC-37 pin connector mates directly to the terminal board.
- An infrared port provides local serial diagnostic communications.
TECHNICAL INFORMATION
Installation Guidelines
- Secure the selected terminal board inside the control cabinet.
- Mount the pack directly to the terminal board DC-37 connector.
- Fasten the threaded studs into the terminal board mounting bracket.
- Align the bracket to prevent right-angle stress on the DC-37 connector.
- Connect one or two Ethernet cables to the dual RJ45 ports.
- Attach the power cable directly without de-energizing the supply circuit.
- The integrated soft-start circuit safely limits inrush current during connection.
TECHNICAL INFORMATION
Configuration Guidelines
- Configure input pack parameters using the GE ToolboxST software application.
- Assign ENET1 to the primary R controller communication network when applicable.
TECHNICAL INFORMATION
Compatibility
- Compatible with GE Mark VIe distributed control system architectures.
- Directly mates with TBTCH1B and TBTCH1C thermocouple terminal boards.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSCompatible with GE Mark VIe distributed control system architectures. Directly mates with TBTCH1B and TBTCH1C thermocouple terminal boards.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
How many thermocouple channels does the IS220PTCCH1A support?
The pack supports up to 12 thermocouple input channels directly.
Which thermocouple sensor types work with the IS220PTCCH1A?
The module supports thermocouple types E, J, K, and S.
Can the IS220PTCCH1A module be plugged in while powered?
Yes. An internal soft-start circuit controls inrush current during live cable connection.
What software is required to configure the IS220PTCCH1A module?
System engineers configure the pack using the GE ToolboxST software application.
What is the reference price for the IS220PTCCH1A module?
Pricing figures are indicative market reference pricing only and are not a final quotation.