PRODUCT INFORMATION
Product Overview
The ABB DI830 3BSE013210R1 is a 16-channel 24 V d.c. digital input module for S800 I/O systems. Each input channel operates with a current sinking configuration drawing 6 mA at 24 V d.c. Each channel includes current limiting components, EMC protection, an optical isolation barrier, and an LED. The module cyclically performs internal self-diagnostics. Digital filter times can be selected in the range from 0 to 100 ms. Pulses shorter than the configured filter time are filtered out.
This module supports Sequence of Events recording with 0.4 ms resolution. Event recording accuracy ranges from -0.3 ms to +0.7 ms. The module communicates across the Modulebus backplane using 5 V d.c. power. Typical internal power dissipation is 2.3 W during operation. The unit provides groupwise isolation from ground. It carries marine approvals and certifications for hazardous locations. The module mounts on compatible S800 Module Termination Units using keying code AA.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Signal specification | 24 V d.c. |
|---|
| Number of channels | 16 |
|---|
| Signal type | Current sinking |
|---|
| HART | No |
|---|
| SOE | Yes |
|---|
| Redundancy | No |
|---|
| High integrity | No |
|---|
| Intrinsic safety | No |
|---|
| Mechanics | S800 |
|---|
| Input voltage range, "0" | -30..+5 V |
|---|
| Input voltage range, "1" | 13..30 V |
|---|
| Input impedance | 3.2 kΩ |
|---|
| Isolation | Groupwise isolated from ground |
|---|
| Filter times (digital, selectable) | 0...100 ms |
|---|
| Current limiting | Sensor power can be current limited by the MTU |
|---|
| Maximum field cable length | 600 meters (656 yards) |
|---|
| Event recording accuracy | -0.3 ms...+0.7 ms |
|---|
| Event recording resolution | 0.4 ms |
|---|
| Rated insulation voltage | 50 V |
|---|
| Dielectric test voltage | 500 V a.c. |
|---|
| Power dissipation | Typ. 2.3 W |
|---|
| Current consumption +5 V Modulebus | Typ. 100 mA, Max 120 mA |
|---|
| Current consumption +24 V Modulebus | 0 |
|---|
| Current consumption +24 V external | 0 |
|---|
| Front LED’s | F(ault), R(un), W(arning), Channel 1-16 ("0" or "1") |
|---|
| Supervision | Process voltage, 1 per group ; Event queue full; Time synchronization missing |
|---|
| Status indication of supervision | Module Error, Module Warning, Channel error |
|---|
| CE mark | Yes |
|---|
| Electrical safety | EN 61010-1, UL 61010-1, EN 61010-2-201, UL 61010-2-201 |
|---|
| Hazardous Location | C1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2 |
|---|
| Marine certification | ABS, BV, DNV, LR, CCS |
|---|
| Temperature, Operating | 0 to +55 °C (+32 to +131 °F), approvals are issued for +5 to +55 °C |
|---|
| Temperature, Storage | -40 to +70 °C (-40 to +158 °F) |
|---|
| Pollution degree | Degree 2, IEC 60664-1 |
|---|
| Corrosion protection | ISA-S71.04: G3 |
|---|
| Relative humidity | 5 to 95 %, non-condensing |
|---|
| Max ambient temperature | 55 °C (131 °F), for vertical mounting in compact MTU 40 °C (104 °F) |
|---|
| Protection class | IP20 according to IEC 60529 |
|---|
| EMC | EN 61000-6-4 and EN 61000-6-2 |
|---|
| Overvoltage categories | IEC/EN 60664-1, EN 50178 |
|---|
| RoHS compliance | EU RoHS, UAE RoHS, CN RoHS |
|---|
| WEEE compliance | DIRECTIVE/2012/19/EU |
|---|
| Use with MTU | TU810, TU812, TU814, TU818, TU830, TU833, TU838, TU850 |
|---|
| Keying code | AA |
|---|
| Width | 45 mm |
|---|
| Depth | 102 mm, 111 mm including connector |
|---|
| Height | 119 mm |
|---|
| Weight | 0.22 kg |
|---|
TECHNICAL INFORMATION
Features
- Provides 16 current-sinking 24 V d.c. digital input channels.
- Supports Sequence of Events recording with 0.4 ms resolution.
- Features selectable digital input filter times from 0 to 100 ms.
- Offers groupwise galvanic isolation from ground rated at 50 V.
- Integrates cyclic self-diagnostics for process voltage and event queues.
- Includes front status LEDs for fault, run, warning, and channels.
TECHNICAL INFORMATION
Applications
- S800 I/O process automation architectures requiring Sequence of Events recording.
- Class I Division 2 and ATEX Zone 2 hazardous location installations.
- Marine installations requiring ABS, BV, DNV, LR, or CCS type approvals.
TECHNICAL INFORMATION
Connections / Interfaces
- Connects to the S800 Modulebus backplane via compatible Module Termination Units.
- Field wiring terminates on compatible MTUs including TU810, TU812, TU814, and TU830.
- Supports maximum field cabling distances up to 600 meters.
TECHNICAL INFORMATION
Installation Guidelines
- Align the module keying code AA with the compatible Module Termination Unit.
- Operate within 0 to +55 °C for standard horizontal mounting.
- Limit maximum ambient temperature to 40 °C when mounting vertically in compact MTUs.
- Ensure installation complies with IP20 ingress protection requirements.
TECHNICAL INFORMATION
Configuration Guidelines
- Configure digital filter times between 0 and 100 ms to filter short pulses.
- Assign Sequence of Events monitoring parameters within system control software.
TECHNICAL INFORMATION
Compatibility
- Compatible with ABB S800 I/O communication interfaces and controllers.
- Mounts on MTU models TU810, TU812, TU814, TU818, TU830, TU833, TU838, and TU850.
TECHNICAL INFORMATION
Compliance and Certifications
- Certified to EN 61010-1, UL 61010-1, EN 61010-2-201, and UL 61010-2-201.
- Approved for Class I Division 2, Class I Zone 2, and ATEX Zone 2.
- Holds marine certifications from ABS, BV, DNV, LR, and CCS.
- Meets ISA-S71.04 G3 corrosion protection and IP20 ingress standards.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSCompatible with ABB S800 I/O communication interfaces and controllers. Mounts on MTU models TU810, TU812, TU814, TU818, TU830, TU833, TU838, and TU850.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the primary function of the ABB DI830 3BSE013210R1?
The ABB DI830 captures 16 digital input signals with Sequence of Events time stamping.
Which Module Termination Units work with the DI830?
The module works with TU810, TU812, TU814, TU818, TU830, TU833, TU838, and TU850 MTUs.
What is the digital filter range for DI830 input channels?
The digital filter time is selectable from 0 to 100 ms for field signals.
What is the market reference price for the DI830 module?
Observed market reference pricing is approximately 589 USD for used units. Pricing figures are indicative market reference pricing only and are not a final quotation.