PRODUCT INFORMATION
Product Overview
The ABB TU830V1 3BSE013234R1 is an extended Module Termination Unit designed for the S800 I/O system. This passive base unit connects field wiring to individual I/O modules. It routes ModuleBus signals directly between neighboring units in the station. The unit provides connection points for up to 16 input or output channels. Process power connects across two isolated groups, each protected by an individual 6.3 A fuse.
Fifty-six field terminal points accommodate signal connections and zero-potential reference returns. The termination unit supports maximum process voltages up to 50 V. Each individual I/O channel handles maximum continuous currents up to 2 A. Automatic slot addressing occurs by shifting outgoing position signals to the next module termination unit. The mechanical assembly supports DIN-rail or panel mounting within industrial control cabinets.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Number of Channels | 16 |
|---|
| Process Connections | 56 terminals |
|---|
| Maximum Voltage | 50 V |
|---|
| Maximum Current per Channel | 2 A |
|---|
| Maximum Process Connection Current | 5 A |
|---|
| Process Protection | Two isolated groups with 6.3 A fuses |
|---|
| Dielectric Test Voltage | 500 V AC |
|---|
| Solid Conductor Size | 0.2 to 4 mm² (24 to 12 AWG) |
|---|
| Stranded Conductor Size | 0.2 to 2.5 mm² (24 to 12 AWG) |
|---|
| Terminal Tightening Torque | 0.5 to 0.6 Nm |
|---|
| Stripping Length | 7 mm |
|---|
| Operating Temperature | 0 to +55 °C (+32 to +131 °F) |
|---|
| Storage Temperature | -40 to +70 °C (-40 to +158 °F) |
|---|
| Relative Humidity | 5 to 95 %, non-condensing |
|---|
| Pollution Degree | Degree 2 (IEC 60664-1) |
|---|
| Corrosion Protection | ISA-S71.04: G3 |
|---|
| Protection Class | IP20 (IEC 60529) |
|---|
TECHNICAL INFORMATION
Features
- Accommodates up to 16 I/O channels across 56 process terminal connections.
- Includes two individually isolated process voltage groups with 6.3 A fuse protection.
- Supports maximum operating voltage of 50 V and 2 A per channel.
- Propagates ModuleBus communications and shifts position signals for physical addressing.
- Accepts solid conductors up to 4 mm² and stranded wire up to 2.5 mm².
- Complies with ISA-S71.04 G3 severity levels for corrosive industrial environments.
TECHNICAL INFORMATION
Applications
- Field signal termination for S800 I/O digital, analog, and pulse modules.
- Distributed process interface in ABB Advant and System 800xA control systems.
- Cabinet installations requiring ISA-S71.04 G3 corrosion resistance and hazardous area certification.
TECHNICAL INFORMATION
Connections / Interfaces
- 56 screw terminal connections for field wiring and process voltage feeds.
- Integrated ModuleBus backplane connector for communication and addressing signals.
- Two isolated process voltage inputs with 5 A total connection capacity.
TECHNICAL INFORMATION
Installation Guidelines
- Mount the unit on standard DIN rail or mount directly to a panel.
- Operate the hardware within ambient temperature limits from 0 to 55 °C.
- Strip wiring to 7 mm and torque screw terminals to 0.5 - 0.6 Nm.
- Ensure wiring matches the assigned channel groupings and process fuse ratings.
TECHNICAL INFORMATION
Configuration Guidelines
- Address assignment functions automatically through internal ModuleBus position signal shifting.
- Insert compatible S800 I/O modules into the unit based on system design schedules.
TECHNICAL INFORMATION
Compatibility
- Analog input modules: AI810, AI815, AI820, AI830, AI830A, AI835, AI835A, AI843, AI845.
- Analog output modules: AO810, AO810V2, AO815, AO820, AO845, AO845A.
- Digital input modules: DI810, DI811, DI814, DI818, DI830, DI831, DI840, DI880, DI885.
- Digital output modules: DO810, DO814, DO815, DO818, DO840, DO880.
- Pulse counter modules: DP820, DP840.
TECHNICAL INFORMATION
Compliance and Certifications
- CE Marked
- Electrical Safety: EN 61010-1, UL 61010-1, EN 61010-2-201, UL 61010-2-201
- Hazardous Location: Class I Division 2 cULus, Class I Zone 2 cULus, ATEX Zone 2
- Marine Standards: ABS, BV, DNV, LR, CCS
- Electromagnetic Compatibility: EN 61000-6-4, EN 61000-6-2
- Environmental Compliance: RoHS EN 50581:2012, WEEE 2012/19/EU
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSAnalog input modules: AI810, AI815, AI820, AI830, AI830A, AI835, AI835A, AI843, AI845. Analog output modules: AO810, AO810V2, AO815, AO820, AO845, AO845A. Digital input modules: DI810, DI811, DI814, DI818, DI830, DI831, DI840, DI880, DI885. Digital output modules: DO810, DO814, DO815, DO818, DO840, DO880. Pulse counter modules: DP820, DP840.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the function of the ABB TU830V1 3BSE013234R1?
The TU830V1 is a passive termination unit connecting field wiring to S800 I/O modules and extending ModuleBus signals.
What wire sizes are supported by the TU830V1 terminal blocks?
The terminals accept solid conductors from 0.2 to 4 mm² and stranded conductors from 0.2 to 2.5 mm².
How does the TU830V1 handle module addressing?
The unit generates physical module addresses by shifting outgoing position signals along the ModuleBus to adjacent units.
What is the reference price for the ABB TU830V1 3BSE013234R1?
Commercial sources indicate an observed reference price of $159.00 USD. This figure is indicative market reference pricing only and is not a final quotation.