The Allen-Bradley 1746-IA4 is a 4-channel digital AC input module for the SLC 500 platform. This module operates with an input voltage range between 85 and 132 Volts AC at 47 to 63 Hertz. It provides four discrete AC inputs designed for general-purpose automation interfacing in a single chassis slot. Nominal input current is 12 milliamps at 129 Volts AC.
The unit draws 35 milliamps of backplane current at 5 Volts DC and 0 milliamps at 24 Volts DC. Signal delay times specify a maximum of 35 milliseconds for turn-on and 45 milliseconds for turn-off. The maximum off-state current is 2 milliamps, with a maximum off-state voltage rating of 30 Volts AC. It features an open-style enclosure, built-in status displays, and operates from 32 to 140 degrees Fahrenheit.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Backplane Current (5 Volts DC) | 35 milliamps |
|---|
| Category | PLCs |
|---|
| I/O Connection | 1746-HT and 1746-HCA |
|---|
| Inputs | 4 |
|---|
| Module Type | Digital AC Input Module |
|---|
| Off State Current | 2 milliamps |
|---|
| Signal delay | 35 or 45 milliseconds |
|---|
| Slots | 1 |
|---|
| Step Response | 100 milliseconds in, 2.5 milliseconds out |
|---|
| UPC | 662073521198 |
|---|
| Voltage Range | 85-132 Volts AC |
|---|
| Weight | 0.38 lbs (0.17 kg) |
|---|
TECHNICAL INFORMATION
Features
- Offers four discrete AC input channels for field signal detection.
- Supports an operating voltage range of 85 to 132 Volts AC.
- Draws 35 milliamps of backplane current at 5 Volts DC.
- Provides visual status display indicators for active channel diagnostics.
- Installs in a single slot of an SLC 500 chassis.
TECHNICAL INFORMATION
Applications
- General-purpose AC discrete input monitoring in SLC 500 control racks.
- Interfacing 120V AC switches, pushbuttons, and industrial field sensors.
TECHNICAL INFORMATION
Connections / Interfaces
- Connects via 1746-HT and 1746-HCA wiring connection interfaces.
- Direct backplane interface to SLC 500 chassis backplane bus.
TECHNICAL INFORMATION
Installation Guidelines
- Insert the module into any available slot within an SLC 500 chassis.
- Maintain ambient operating temperatures between 32 and 140 degrees Fahrenheit.
TECHNICAL INFORMATION
Compatibility
- Compatible with Allen-Bradley SLC 500 chassis and controller systems.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSCompatible with Allen-Bradley SLC 500 chassis and controller systems.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the operational voltage range for the 1746-IA4?
The module operates on a line voltage range of 85 to 132 Volts AC at 47 to 63 Hertz.
What is the backplane current consumption for the 1746-IA4?
The 1746-IA4 draws 35 milliamps at 5 Volts DC and 0 milliamps at 24 Volts DC.
How many chassis slots does the 1746-IA4 require?
The 1746-IA4 occupies exactly one slot in an SLC 500 I/O chassis.