PRODUCT INFORMATION
Product Overview
The Allen-Bradley 1746-NO4V is an analog output module for the SLC 500 series. It mounts directly into any available slot in a 1746 chassis. The module provides four distinct analog voltage output channels. Supported voltage ranges include -10 to 10 VDC and 0 to 10 VDC. Channels also support 0 to 5 VDC and 1 to 5 VDC ranges.
Backplane current draw is 55 mA at 5V DC and 145 mA at 24V DC. An external 24V DC power supply option is also supported. All four outputs update in parallel within 512 microseconds. Isolation between backplane and field wiring is rated at 500V DC. Connections use a removable terminal block accepting up to #14 AWG wire.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Backplane Current Draw at 24V | 145 mA |
|---|
| Backplane Current Draw at 5V | 55 mA |
|---|
| Backplane to Field Wiring Isolation Rating | 500V DC |
|---|
| External Power Supply Option | 24V DC power supply supported |
|---|
| External Power Switch Option | 24V DC Switch |
|---|
| GTIN | 10662073735929 |
|---|
| Individual Output Isolation | Not Included |
|---|
| Location | 1746 Chassis |
|---|
| Max. Wire Size | #14 AWG |
|---|
| Number of Outputs | 4 Outputs |
|---|
| Operating Temperature | 0 to 60 degrees Celsius |
|---|
| Recommended Cable Type | Shielded Belden #8761 Cable |
|---|
| Removable Terminal Block | Included |
|---|
| Update Time for All Outputs In Parallel | 512 microseconds |
|---|
| Voltage Ranges | -10 to 10 Volts DC, 0 to 10 Volts DC, 0 to 5 Volts DC, 1 to 5 Volts DC |
|---|
| Weight | 0.56 lbs (0.26 kg) |
|---|
TECHNICAL INFORMATION
Features
- Provides four analog voltage output channels.
- Supports voltage ranges of -10 to 10V, 0 to 10V, 0 to 5V, and 1 to 5V DC.
- Updates all four output channels in parallel within 512 microseconds.
- Features backplane to field wiring isolation rated at 500V DC.
- Includes a removable terminal block for field wiring.
- Supports an optional external 24V DC power supply.
TECHNICAL INFORMATION
Applications
- Voltage reference control for variable frequency motor drives.
- Command signaling for proportional valves and positioning actuators.
- Interface signaling for industrial process control instrumentation.
TECHNICAL INFORMATION
Connections / Interfaces
- Connects to field devices via a removable terminal block.
- Accommodates wire sizes up to a maximum of #14 AWG.
- Requires shielded Belden #8761 cable for field connections.
- Interfaces with SLC 500 processors across the 1746 backplane.
TECHNICAL INFORMATION
Installation Guidelines
- Install the module into an open slot within a 1746 chassis.
- Remove chassis and field power before inserting or removing the module.
- Maintain an ambient operating temperature between 0 and 60 degrees Celsius.
- Ground cable shields at the chassis to reduce electrical noise.
TECHNICAL INFORMATION
Configuration Guidelines
- Configure the voltage output range for each channel during application setup.
- Select backplane or external 24V DC power to manage chassis power budgets.
TECHNICAL INFORMATION
Compatibility
- Installs in standard Allen-Bradley 1746 chassis assemblies.
- Compatible with Allen-Bradley SLC 500 processor systems.
TECHNICAL INFORMATION
Lifecycle / Replacement Information
- Maintained for existing Allen-Bradley SLC 500 control systems.
- Uses the standard 1746 modular form factor.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSInstalls in standard Allen-Bradley 1746 chassis assemblies. Compatible with Allen-Bradley SLC 500 processor systems.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What output voltage ranges does the 1746-NO4V module support?
It supports -10 to +10V, 0 to 10V, 0 to 5V, and 1 to 5V DC ranges.
Does the 1746-NO4V provide individual output isolation?
No, individual channels are not isolated. Backplane to field wiring isolation is rated at 500V DC.
What is the update speed of the 1746-NO4V outputs?
All four analog outputs update simultaneously in parallel within 512 microseconds.
What wire size and cable type does the module require?
The removable terminal block accepts up to #14 AWG wire using shielded Belden #8761 cable.