The Allen-Bradley 1756-L62 is a ControlLogix Processor Module. It features 4 MB of integrated user memory and 478 KB of I/O memory. The module handles up to 128,000 total digital I/O points and 4,000 analog I/O points. It mounts directly into 1756 chassis including 1756-A4, 1756-A7, 1756-A10, 1756-A13, and 1756-A17.
This controller supports up to 32 tasks with 100 programs per task. An onboard RS-232 serial port provides ASCII, DF1, DH-485, and Modbus communication options. Optional nonvolatile memory expansion uses the 1784-CF128 CompactFlash card. The processor draws 1.2 A at 5.1V DC and 14 mA at 24V DC backplane power.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Category | PLCs |
|---|
| GTIN | 10612598300713 |
|---|
| Weight | 1.31 lbs (0.60 kg) |
|---|
| Fixed Memory | 2, 4, or 8 MB |
|---|
| Module Type | Processor Module |
|---|
| Nonvolatile Memory | Compact Flash Card 1784-CF128 |
|---|
| Maximum I-O | 128,000 |
|---|
| Communication | RS-232 serial port |
|---|
| RS232 Protocols | ASCII DF1 full/half-duplex DF1 radio modem DH-485 Modbus via logic |
|---|
| Maximum Analog I-O | 4,000 |
|---|
| Program Scan Time | 0.08 milliseconds |
|---|
| User Memory | 4MB |
|---|
| Backplane Current (5Volts DC) | 1.2 Amps |
|---|
| Backplane Current (24 Volts DC) | 14 milliamps |
|---|
| UPC | 10612598300713 |
|---|
| Vibration | 10-500 Hertz |
|---|
| Relative Humidity | 5-95 percent |
|---|
| Battery | 1756-BA1, 1756-BATM or 1756-BATA |
|---|
| Full Support | Programming Languages |
|---|
TECHNICAL INFORMATION
Features
- Integrated 4 MB user memory with 478 KB dedicated I/O memory.
- Built-in RS-232 serial port supporting ASCII, DF1, DH-485, and Modbus via logic.
- Support for up to 250 simultaneous controller connections across network modules.
- Execution of up to 32 tasks with 100 programs per task.
- Optional nonvolatile memory storage expansion with 1784-CF128 CompactFlash card.
- Full architectural support for controller redundancy configurations.
TECHNICAL INFORMATION
Applications
- Process and factory automation systems requiring medium to large control architectures.
- Distributed I/O applications using EtherNet/IP and ControlNet networks.
- High-availability control systems requiring controller redundancy.
TECHNICAL INFORMATION
Connections / Interfaces
- Onboard RS-232 serial interface port.
- ControlNet connections via 1756-CN2/A, 1756-CN2/B, 1756-CNB/D, or 1756-CNB/E modules.
- EtherNet/IP network connections via 1756-EN2x and 1756-ENBT communication modules.
- Data Highway Plus, DeviceNet, SynchLink, and Remote I/O network interface support.
TECHNICAL INFORMATION
Installation Guidelines
- Mount module into slot locations within compatible 1756-A4, 1756-A7, 1756-A10, 1756-A13, or 1756-A17 chassis.
- Maintain ambient operating temperatures between 0 and 60 degrees Celsius.
- Ensure noncondensing operating relative humidity remains between 5% and 95%.
TECHNICAL INFORMATION
Configuration Guidelines
- Configure controller properties and download application logic using compatible RSLinx and programming software.
- Configure RS-232 port driver settings for DF1, DH-485, ASCII, or Modbus communication.
- Install the optional 1784-CF128 CompactFlash card for nonvolatile program storage backup.
TECHNICAL INFORMATION
Compatibility
- Compatible with ControlLogix chassis models 1756-A4, 1756-A7, 1756-A10, 1756-A13, and 1756-A17.
- Series A and Series B versions are compatible with RSLinx software.
- Supported by battery part numbers 1756-BA1, 1756-BATM, and 1756-BATA.
TECHNICAL INFORMATION
Lifecycle / Replacement Information
- The 1756-L62 controller entered discontinued lifecycle status on June 01, 2017.
- The designated functional replacement model is the 1756-L72 processor.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSCompatible with ControlLogix chassis models 1756-A4, 1756-A7, 1756-A10, 1756-A13, and 1756-A17. Series A and Series B versions are compatible with RSLinx software. Supported by battery part numbers 1756-BA1, 1756-BATM, and 1756-BATA.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the memory capacity of the Allen-Bradley 1756-L62 controller?
The 1756-L62 includes 4 MB of integrated user memory and 478 KB of dedicated I/O memory.
What is the functional replacement for the discontinued 1756-L62?
The official functional replacement model for the discontinued 1756-L62 is the ControlLogix 1756-L72 processor module.
Which chassis models support the 1756-L62 processor?
The 1756-L62 is compatible with Allen-Bradley 1756-A4, 1756-A7, 1756-A10, 1756-A13, and 1756-A17 chassis models.
What protocols does the 1756-L62 serial port support?
The RS-232 port supports ASCII, DF1 full/half-duplex, DF1 radio modem, DH-485, and Modbus via logic.