Product Overview
The Allen-Bradley 2711-B5A2L1 is a PanelView 550 Monochrome, Keypad & Touch terminal. This operator terminal features a 5.5-inch blue mode monochrome liquid crystal display. The screen provides a resolution of 256 by 128 pixels across a 120 by 60 millimeter area. Operator entry uses a 128-cell touch membrane and a keypad with ten function keys. Both operator input interfaces support up to one million actuations.
The unit operates on a direct-current supply from 18 to 32 Volts DC. Nominal input voltage is 24 Volts DC with an 18 Watt maximum power draw. Internal memory provides 170 kilobytes of runtime storage and 240 kilobytes of nonvolatile memory. Communication operates through an integrated DH-485 port. The terminal dissipates approximately 20 Watts of heat during standard operation.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Product Line | Panelview 550 |
|---|
| UPC | 662468697002 |
|---|
| Weight | 3.75 lbs (1.70 kg) |
|---|
| Backlight | 100,000 hr LED backlight life |
|---|
| Input Type | Keypad / Touch |
|---|
| Display Type | Monochrome LCD blue mode display |
|---|
| Display Area | 120 x 60 mm (4.75 x 2.38 in.) |
|---|
| Resolution | 256 x 128 |
|---|
| Touchscreen | Touch cells: 128 Actuation: 1 million presses |
|---|
| Keypad function keys | 10 function keys (F1…F10) |
|---|
| Application memory | 170 KB application runtime; 240 KB nonvolatile memory (application objects plus text and bitmaps) |
|---|
| Communication ports | DH485 |
|---|
| Input Voltage range | 18…32V DC (24V DC nom) |
|---|
| Accessories | function key legend inserts; Anti-glare overlays; backlight replacements; Real-time clock replacements; Mounting hardware; Power supply and terminal block; interface modules; |
|---|
| Display Size | 5.5 in. |
|---|
| Display Color | Monochrome LCD blue mode |
|---|
| Communication | DH-485 Communication Ports |
|---|
| Input Power | 24V DC |
|---|
| Memory | 170 KB application runtime |
|---|
| Communication Cable | 1747-C10 |
|---|
| Product Lifecycle Status* | Discontinued/Obsolete |
|---|
TECHNICAL INFORMATION
Features
- Dual operator interface combines a 128-cell touch membrane with ten function keys and numeric entry keys.
- Both keypad buttons and touch cells deliver an operational rating of one million actuations.
- Blue monochrome LCD provides 256 by 128 resolution across a 5.5-inch viewing area.
- The LED backlight assembly delivers an operational service life of approximately 100,000 hours.
- A battery-backed real-time clock timestamps operational application data.
- Direct-current power supply accepts input voltages from 18 to 32 Volts DC.
TECHNICAL INFORMATION
Connections / Interfaces
- One DH-485 communication port provides point-to-point data exchange with compatible controllers.
- The terminal connects to DH-485 networks using a 1747-C10 communication cable.
- Network expansion options include connections using a 1747-AIC isolated link coupler.
- Serial communication converter support includes the 1747-PIC interface unit.
- The unit interfaces with MicroLogix controllers via a 1761-NET-AIC interface converter.
TECHNICAL INFORMATION
Installation Guidelines
- Mount the unit in enclosures rated NEMA Type 12, NEMA Type 4X indoor, IP54, or IP65.
- Maintain operating ambient temperatures between 0 and 55 degrees Celsius.
- Keep storage ambient temperatures between -20 and 70 degrees Celsius.
- Install the hardware at an operating altitude below 2000 meters above sea level.
TECHNICAL INFORMATION
Lifecycle / Replacement Information
- Rockwell Automation has categorized the Bulletin 2711 PanelView 550 family as discontinued and obsolete.
- The PanelView Plus terminal family represents a newer generation of operator interface hardware.
TECHNICAL RESOURCES
Documentation
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What communication interface does the 2711-B5A2L1 terminal provide?
The terminal features an integrated DH-485 port for controller communication. It uses a 1747-C10 cable.
What input power does the 2711-B5A2L1 require?
The unit requires 24 Volts DC nominal power. Its supported operating range is 18 to 32 Volts DC.
How does the operator enter data on this terminal?
Users enter data using a 128-cell touch screen and a keypad with ten function keys.
What is the lifecycle status of the 2711-B5A2L1?
Rockwell Automation has classified this legacy PanelView 550 terminal as discontinued and obsolete.