PRODUCT INFORMATION
Product Overview
The General Electric DS200TCCAG1BAA is an analog I/O module designed for Mark V turbine control systems. It functions as a TC2000 I/O analog board within Speedtronic turbine drive assemblies. The board processes analog signals for compatible gas, steam, and wind turbine applications. An onboard 80196 microprocessor executes control logic with a programmable logic device. Programmable read-only memory modules store dedicated operational firmware and system instructions.
The circuit board integrates dedicated interface connectors for signal wiring and internal power distribution. Two 50-pin connectors designated JCC and JDD interface directly with TBCA terminal boards. These connections route resistance temperature detector signals into the board. A side-view status light-emitting diode provides direct visual feedback during routine system operation. Normal conformal coating protects board components across standard industrial operating environments.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| PCB Coating | Normal Coating |
|---|
| 1st Functional Revision | B |
|---|
| 2nd Functional Revision | A |
|---|
TECHNICAL INFORMATION
Features
- Features an 80196 microprocessor and a programmable logic device.
- Includes socketed PROM modules that store erasable firmware and instructions.
- Provides one status LED visible from the side of the board.
- Contains two 50-pin connectors labeled JCC and JDD for RTD signals.
- Applies normal PCB coating across the assembled circuit board.
TECHNICAL INFORMATION
Applications
- Speedtronic Mark V gas turbine control panels.
- Steam turbine automated drive assemblies.
- Compatible wind turbine management systems.
TECHNICAL INFORMATION
Connections / Interfaces
- 2PL connector routes DC power distribution from the TCPS board.
- 3PL connector transfers conditioned data bus signals with STCA, TCCA, and TCCB boards.
- JAA connector transmits 4-20 mA output signals to the CTBA terminal board.
- JBB connector receives 4-20 mA input signals from the CTBA terminal board.
- JCC 50-pin connector receives RTD temperature inputs from the TBCA terminal board.
- JDD 50-pin connector receives secondary RTD inputs from the TBCA terminal board.
- JAR, JAS, and JAT connectors receive input signals from the TBQA terminal board.
- JC connector transfers power supply diagnostic signals to the TCPS board.
- JEE connector remains an unaccessed connection during standard operation.
TECHNICAL INFORMATION
Installation Guidelines
- Always wear an ESD protective device such as a wrist strap during maintenance.
- Electrostatic discharge can corrupt or destroy firmware stored on socketed memory modules.
- Use a flat-bladed screwdriver under one end to gently lift socketed PROM modules.
- Repeat the action at the other end to pop the module free.
- Place extracted memory modules immediately into static protective bags.
- Align replacement PROM module pins carefully with the socket before pressing down.
- Transfer original modules to the replacement board to preserve firmware instructions.
TECHNICAL INFORMATION
Configuration Guidelines
- Firmware and control code reside on erasable socketed PROM modules.
- Newer code versions can be erased and stored on the PROM chips.
- Migrate socketed PROMs from the previous board to maintain identical functional code.
TECHNICAL INFORMATION
Compatibility
- Interfaces with Mark V Speedtronic turbine automated drive systems.
- Directly connects to CTBA, TBCA, TBQA, and TCPS terminal and power boards.
- Links with STCA, TCCA, and TCCB boards over conditioned data bus connections.
TECHNICAL INFORMATION
Lifecycle / Replacement Information
- Serves as a revision of the parent DS200TCCAG1 analog board.
- Includes first functional revision B and second functional revision A updates.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSInterfaces with Mark V Speedtronic turbine automated drive systems. Directly connects to CTBA, TBCA, TBQA, and TCPS terminal and power boards. Links with STCA, TCCA, and TCCB boards over conditioned data bus connections.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the primary function of the GE DS200TCCAG1BAA board?
It serves as a TC2000 analog I/O board in General Electric Mark V systems. It processes RTD and 4-20 mA inputs.
How are firmware settings transferred to a replacement DS200TCCAG1BAA board?
Firmware resides on removable PROM modules seated in onboard sockets. Technicians extract these modules from the old board using ESD precautions. Installing them on the new board preserves exact operational firmware.
Which terminal boards connect directly to the DS200TCCAG1BAA analog module?
The board connects to CTBA terminal boards for 4-20 mA inputs and outputs. It links to TBCA terminal boards for RTD temperature signals. It also interfaces with TBQA terminal boards for additional signal inputs.