PRODUCT INFORMATION
Product Overview
The General Electric IC200ALG230 is an Analog Input Module from the VersaMax platform. It provides four individually configurable single-ended analog input channels arranged in one group. Supported input signals include unipolar 0 to 10 VDC, bipolar +/-10 VDC, and 4 to 20 mA. Analog to digital conversion provides a resolution of 12 bits across all supported ranges. Two front LEDs indicate internal power and backplane power status.
The module draws operating power directly from the VersaMax backplane at 125 mA and 5 VDC. Two carrier hardware jumpers configure current mode, voltage mode, and unipolar or bipolar voltage operation. Configurable error responses permit the module to hold last state or transition to a preset value. The unit provides optical isolation rated at 250 VAC continuous and 1500 VAC for one minute.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Weight | 1.19 lbs (0.54 kg) |
|---|
| Product Description | Analog input module |
|---|
| Voltage Type | Bipolar or Unipolar |
|---|
| No of Channels | Four (4) analog input |
|---|
| Default Voltage Type | Bipolar |
|---|
| Analog input signal | Analog input signal |
|---|
| Number of Inputs | 4 |
|---|
| Analog input resolution | 12 bits |
|---|
| Input Type | Single-Ended |
|---|
| Response times | 5.0 ms |
|---|
| Configuration Type | 2 Jumpers |
|---|
| Update rate | 0.4 ms |
|---|
| Backplane Current | 125 milliamps at 5 Volts Output |
|---|
| Backplane current consumption | 125 mA at 5VDC |
|---|
| Configuration parameters | Range select, Mode select |
|---|
| Diagnostics | Loss of internal power |
|---|
| LED indicators | INT PWR LED; OK |
|---|
| Reaction to module error | Hold last state; Go to pre-defined value |
|---|
| Optical isolation | 250VAC continuous; 1500VAC for 1 minute |
|---|
TECHNICAL INFORMATION
Features
- Provides four single-ended analog input channels configurable for voltage or current signals.
- Supports 0 to 10 VDC unipolar, +/-10 VDC bipolar, and 4 to 20 mA input ranges.
- Employs two carrier jumpers to set voltage or current and unipolar or bipolar operation.
- Draws 125 mA at 5 VDC backplane current directly from the VersaMax backplane.
- Features INT POWER and OK status LEDs for internal and backplane power monitoring.
- Configures channel behavior on error to hold last state or enter pre-defined values.
- Delivers optical isolation rated at 250 VAC continuous and 1500 VAC for one minute.
TECHNICAL INFORMATION
Applications
- Interfacing analog sensors and transmitters within VersaMax programmable logic controller systems.
- Commercial and industrial control installations requiring mixed voltage or 4 to 20 mA instrumentation.
TECHNICAL INFORMATION
Connections / Interfaces
- Mounts onto terminal-style carriers IC200CHS001, IC200CHS002, or IC200CHS005.
- Compatible with compact terminal carriers IC200CHS022 and IC200CHS025, or connector carrier IC200CHS003.
- Supports auxiliary I/O terminal strips with catalog numbers IC200TBM001, IC200TBM002, or IC200TBM005.
- Provides four single-ended analog input channels grouped together on one common return.
TECHNICAL INFORMATION
Installation Guidelines
- Seat the module onto the compatible VersaMax carrier terminal base.
- Ground signal cables directly at the field source device when possible.
- Ground the cable shield at the source device or at the module carrier.
TECHNICAL INFORMATION
Configuration Guidelines
- Use the two carrier jumpers to select voltage mode or 4 to 20 mA current mode.
- Configure unipolar or bipolar operation using the jumper when voltage mode is active.
- Select fault reaction parameters in software to hold last state or use predefined values.
TECHNICAL INFORMATION
Compatibility
- Operates in General Electric VersaMax PLC and distributed I/O systems.
- Mounts on carrier models IC200CHS001, IC200CHS002, IC200CHS003, IC200CHS005, IC200CHS022, and IC200CHS025.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSOperates in General Electric VersaMax PLC and distributed I/O systems. Mounts on carrier models IC200CHS001, IC200CHS002, IC200CHS003, IC200CHS005, IC200CHS022, and IC200CHS025.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What input signals are supported by the General Electric IC200ALG230?
The IC200ALG230 supports 0 to 10 VDC unipolar, +/-10 VDC bipolar, and 4 to 20 mA signals.
What do the LED indicators on the IC200ALG230 report?
The INT POWER LED indicates internal power, and the OK LED indicates backplane power supply.
Does the IC200ALG230 module require an external power supply?
No external power supply is needed because it draws 125 mA at 5 VDC from the backplane.
How is the input range configured on the IC200ALG230?
Two jumpers on the carrier configure voltage, current, unipolar, and bipolar operating modes.