PRODUCT INFORMATION
Product Overview
The General Electric IC200ALG240 is an Analog Input Module belonging to the VersaMax series. This device provides eight distinct current input channels for process automation tasks. Each channel accepts signals across a 4 to 20 mA operating range. Factory calibration ensures accurate measurement directly upon installation. The unit processes input data across eight allocated memory words. An update rate of 20 milliseconds enables rapid analog value acquisition.
The module provides channel-to-channel isolation to prevent electrical interference between connected field transmitters. Internal signal conversion utilizes a 16-bit resolution architecture for precise digital representation. Integrated 50/60 Hz notch filtering suppresses common alternating-current line noise. Active open wire detection alerts the controller when field circuit loops disconnect. Front-panel OK and Field Power status indicators confirm module health and external field supply integrity.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Weight | 1.31 lbs (0.60 kg) |
|---|
| UPC | 991289200208 |
|---|
| Input Isolation | Channel isolated |
|---|
| Number of Inputs | 8 inputs |
|---|
| Current Input Range | 4–20 mA |
|---|
| Update Rate | 20 ms |
|---|
| Status Indicators | OK, Field Power |
|---|
| Resolution | 16-bit |
|---|
| Input Data Size | 8 words |
|---|
| Calibration | Factory calibrated |
|---|
| Input Filtering | 50/60 Hz notch |
|---|
| Power Consumption | 15 mA at 5 V |
|---|
| Open Wire Detection | Yes |
|---|
TECHNICAL INFORMATION
Features
- Eight isolated analog input channels supporting 4 to 20 mA current loops.
- High-precision 16-bit analog-to-digital signal conversion.
- Channel-to-channel isolation protecting control logic from ground loops.
- Hardware 50/60 Hz notch filtering for electrical noise suppression.
- Integrated open wire detection to monitor loop circuit continuity.
- Low backplane power consumption rated at 15 mA at 5 VDC.
- Visual diagnostic feedback via OK and Field Power status LEDs.
TECHNICAL INFORMATION
Applications
- Industrial process monitoring with 4 to 20 mA field transmitters.
- Analog data acquisition in VersaMax I/O stations.
- Current loop sensing requiring channel-to-channel electrical isolation.
TECHNICAL INFORMATION
Connections / Interfaces
- Interconnects with standard VersaMax carrier bases.
- Accepts eight isolated 4 to 20 mA current loop connections.
- Uses eight data words for controller input image mapping.
TECHNICAL INFORMATION
Installation Guidelines
- Mount the module onto a compatible VersaMax carrier base.
- Ensure field power is disconnected before module insertion or removal.
- Confirm external field power supply wiring before operational power-up.
TECHNICAL INFORMATION
Configuration Guidelines
- Configure module addressing in the PLC programming software for eight input words.
- Select appropriate software scaling for the 16-bit analog data range.
- Monitor fault tables for diagnostic alerts related to open wire conditions.
TECHNICAL INFORMATION
Compatibility
- Compatible with General Electric VersaMax I/O station carriers.
- Integrates with VersaMax PLC CPUs and network interface units.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSCompatible with General Electric VersaMax I/O station carriers. Integrates with VersaMax PLC CPUs and network interface units.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What input signals does the General Electric IC200ALG240 support?
The IC200ALG240 supports eight isolated current input channels operating within the 4 to 20 mA range.
What is the conversion resolution and update speed of the IC200ALG240?
The module operates with a 16-bit resolution and provides a channel update rate of 20 milliseconds.
Does the IC200ALG240 module provide diagnostic status indicators?
Yes. The module includes dedicated front-panel LED indicators for OK and Field Power operational status.
How does the IC200ALG240 handle noise and loop fault conditions?
It features 50/60 Hz notch filtering for line noise suppression and supports automatic open wire detection.