PRODUCT INFORMATION
Product Overview
The General Electric IC200BEM002 is a VersaMax Communication Module serving as a PROFIBUS-DP slave device. It enables data transfer across industrial networks at speeds from 9.6 Kbaud up to 12 Mbaud. The unit provides automatic baud rate detection to streamline commissioning on active fieldbus installations.
This interface module handles up to 384 bytes of input and output data on the bus. It operates on a 5 V supply rating and draws an operating current of 460 mA. The device connects using a standard 9-pin D-sub interface and installs directly on a DIN rail.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Weight | 0.50 lbs (0.23 kg) |
|---|
| Network Protocol | PROFIBUS-DP Slave |
|---|
| Network Data Rate | 9.6 Kbaud to 12 Mbaud |
|---|
| Baud Rate Detection | Automatic |
|---|
| Number of Stations | 32 without repeaters, up to 125 with repeaters |
|---|
| I/O Data | 384 bytes |
|---|
| Connector Type | 9-pin D-sub connector |
|---|
| Network Topology | Linear bus, terminated at both ends |
|---|
| Transmission Media | Shielded, twisted pair cable |
|---|
| Current Rating | 460 mA |
|---|
| Voltage Rating | 5 V |
|---|
| Input Impedance | 135 to 165 Ohms |
|---|
| Mounting Format | DIN Rail |
|---|
| Indicators | Power LED and Communication (COM) LED |
|---|
TECHNICAL INFORMATION
Features
- Operates as a PROFIBUS-DP slave interface.
- Supports transmission rates from 9.6 Kbaud to 12 Mbaud with automatic detection.
- Manages up to 384 bytes of network I/O data.
- Provides integrated Power and Communication status LEDs.
- Standard 9-pin D-sub connection interface.
- Designed for standard DIN rail mounting.
TECHNICAL INFORMATION
Applications
- VersaMax I/O station integration into PROFIBUS-DP industrial control networks.
- Distributed fieldbus communication in automated manufacturing systems.
TECHNICAL INFORMATION
Connections / Interfaces
- Connects to the network via a 9-pin D-sub connector.
- Requires shielded, twisted pair cable across a linear bus topology terminated at both ends.
TECHNICAL INFORMATION
Installation Guidelines
- Mount the module securely on a DIN rail inside an industrial enclosure.
- Ensure both physical ends of the linear PROFIBUS network segment include active bus termination.
TECHNICAL INFORMATION
Configuration Guidelines
- Network baud rate is detected automatically by the module upon connection to an active master.
- Configure I/O allocation within the maximum capacity of 384 bytes.
TECHNICAL INFORMATION
Compatibility
- Compatible with General Electric VersaMax I/O systems and standard PROFIBUS-DP master devices.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSCompatible with General Electric VersaMax I/O systems and standard PROFIBUS-DP master devices.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What network protocol does the IC200BEM002 module support?
The module functions as a PROFIBUS-DP slave device on industrial automation networks.
What is the maximum station capacity for this module on a network?
It supports up to 32 stations without repeaters and up to 125 stations when using repeaters.
What are the electrical power requirements of the IC200BEM002?
The module operates at a 5 V rating and requires a current of 460 mA.
What physical connection does the module use for fieldbus wiring?
It uses a 9-pin D-sub connector over shielded, twisted pair cabling.