PRODUCT INFORMATION
Product Overview
The General Electric IC630MDL325 is a 115V AC/DC input module designed for Series 90-30 control systems. It provides 16 discrete input points split across two isolated input groups. The module accepts input operating frequencies between 48 Hz and 63 Hz. Individual LED indicators display the operational status for each channel. The unit weighs 2.00 lbs and functions in ambient temperatures from 0 to 60 degrees Celsius.
The IC630MDL325 processes alternating and direct current field inputs across specified electrical ranges. Input current measures 7.5 to 14.1 mA for AC and 2.2 to 4.2 mA for DC signals. Off-state voltage thresholds remain below 20V AC and below 30V DC. Input on-stage response delay spans 10 to 40 ms for AC and 6 to 30 ms for DC. The internal battery provides an estimated lifespan of two years.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Weight | 2.00 lbs (0.91 kg) |
|---|
| Module Type | Input Module |
|---|
| Voltage Rating | 115V AC/DC |
|---|
| Operating Frequency | 48 to 63 Hz |
|---|
| Number of Input Points | 16 |
|---|
| Current Range for AC Voltage | 7.5 to 14.1 mA |
|---|
| Current Range for DC Voltage | 2.2 to 4.2 mA |
|---|
| Number of Groups | 2 Input Groups |
|---|
| Indicators | LED Indicators |
|---|
| Off-Stage Voltage for AC Voltage | Less than 20V AC |
|---|
| Off-Stage Voltage for DC Voltage | Less than 30V DC |
|---|
| On-Stage Delay for AC Voltage | 10 to 40 ms |
|---|
| On-Stage Delay for DC Voltage | 6 to 30 ms |
|---|
| Operating Temperatures | 0 to 60°C |
|---|
| Battery Lifespan | 2 Years |
|---|
TECHNICAL INFORMATION
Features
- Provides 16 discrete input channels arranged in two separate electrical groups.
- Supports both AC and DC voltage signals rated at 115V nominal.
- Accommodates line frequency variations between 48 Hz and 63 Hz.
- Includes dedicated LED indicators for real-time channel status verification.
- Features off-stage voltage thresholds under 20V AC and under 30V DC.
TECHNICAL INFORMATION
Applications
- Interfacing 115V AC or DC field sensors to Series 90-30 PLC racks.
- Discrete signal monitoring in industrial automation and process control panels.
TECHNICAL INFORMATION
Connections / Interfaces
- Field wiring connects to 16 input points organized across two separate groups.
- Direct backplane interface into compatible Series 90-30 rack slots.
TECHNICAL INFORMATION
Installation Guidelines
- Operate within the verified temperature range of 0 to 60 degrees Celsius.
- Ensure signal wiring complies with voltage thresholds and separation standards.
TECHNICAL INFORMATION
Configuration Guidelines
- Assign the 16 discrete input points across the two separate input groups in programming software.
- Account for signal on-stage delay timings during logic execution design.
TECHNICAL INFORMATION
Compatibility
- Compatible with General Electric Series 90-30 programmable logic controller racks.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSCompatible with General Electric Series 90-30 programmable logic controller racks.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the voltage rating of the General Electric IC630MDL325?
The IC630MDL325 is rated for 115V AC and 115V DC operations.
How many input points and groups does the IC630MDL325 provide?
The module features 16 discrete input points divided into two separate input groups.
What are the on-stage delay times for AC and DC signals?
The on-stage delay spans 10 to 40 ms for AC signals and 6 to 30 ms for DC signals.
What is the operating temperature range for the IC630MDL325?
The module operates in ambient environmental temperatures ranging from 0 to 60 degrees Celsius.