PRODUCT INFORMATION
Product Overview
General Electric IC695ECM850 is a PACSystems RX3i Ethernet module designed for IEC 61850 communication networks. It connects PACSystems controllers to substation automation networks. This unit allows the controller to function as an IEC 61850 client. It interfaces directly with remote IEC 61850 server devices across the system. The module features four switched Ethernet ports. Connectivity options include two RJ-45 ports and two SFP cages.
The IC695ECM850 module supports both star and linear network topologies. It accommodates copper and single-mode or multi-mode fiber connections. Transmission speeds include 10, 100, and 1000 Mbps. Each module supports one IP address and up to five MAC addresses. The hardware provides hot-swappable capability for maintenance ease. An onboard mini USB connector enables access to a command-line interface. An SD card slot provides removable storage support.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Weight | 1.63 lbs (0.74 kg) |
|---|
| Switched Ports | 4 |
|---|
| Media Supported | Copper, Single-mode / Multi-mode fiber |
|---|
| Data Rates Aupported | 10/100/1000 Mbps |
|---|
| IP Addresses per Module | 1 |
|---|
| MAC Addresess per Module | 5 |
|---|
| Maximum Number of Modules per RX3i CPU | 4 |
|---|
| Hot-swappable | Yes |
|---|
| SNTP | Yes |
|---|
| Operating Temperature | 0 to 60 degrees Celsius |
|---|
TECHNICAL INFORMATION
Features
- Features four switched Ethernet ports combining two RJ-45 ports and two SFP cages.
- Supports IEC 61850 client communications for electrical substation automation.
- Provides data transmission rates of 10/100/1000 Mbps across copper and fiber media.
- Enables SNTP time synchronization across connected network nodes.
- Allows hot-swappable replacement during system operation.
- Offers a dedicated mini USB port for command line interface access.
- Includes an integrated SD card slot for external storage cards.
TECHNICAL INFORMATION
Applications
- IEC 61850 electrical substation automation architectures.
- PACSystems RX3i industrial Ethernet supervisory networks.
- Substation client-to-server communications in power distribution systems.
TECHNICAL INFORMATION
Connections / Interfaces
- Two RJ-45 Ethernet ports for twisted-pair copper cabling.
- Two SFP cages supporting single-mode and multi-mode optical transceivers or copper transceivers.
- One mini USB port for direct computer connection and command line configuration.
- One SD card slot for removable memory media.
TECHNICAL INFORMATION
Installation Guidelines
- Install up to four IC695ECM850 modules exclusively in the RX3i main rack.
- Module supports hot-swapping into active backplanes without powering down the rack.
- Operate within the 0 to 60 degrees Celsius temperature range.
- Derate the maximum operating temperature to 57 degrees Celsius when using 100 Mbps or 1 Gbps copper SFPs.
TECHNICAL INFORMATION
Configuration Guidelines
- Configure the network hardware using Proficy Machine Edition 8.0 SIM7 or higher.
- Establish connection via the mini USB interface using a standard command line interface.
TECHNICAL INFORMATION
Compatibility
- Compatible with PACSystems RX3i CPUs running firmware version 8.05 or higher.
- Supported CPUs include CPE305, CPE310, CPU315, CPU320, and CRU320 models.
- Requires Proficy Machine Edition 8.0 SIM7 software.
TECHNICAL INFORMATION
Compliance and Certifications
- IEC 61850 communication standard for electrical substation automation.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSCompatible with PACSystems RX3i CPUs running firmware version 8.05 or higher. Supported CPUs include CPE305, CPE310, CPU315, CPU320, and CRU320 models. Requires Proficy Machine Edition 8.0 SIM7 software.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What network protocol does the General Electric IC695ECM850 support for substations?
The IC695ECM850 supports the IEC 61850 protocol. It operates as an IEC 61850 client communicating with substation server devices.
How many IC695ECM850 modules can be installed with a single RX3i CPU?
Up to four IC695ECM850 modules can be used per RX3i CPU. All four modules must be installed in the main rack.
Which RX3i CPUs are compatible with the IC695ECM850 module?
The module requires CPU firmware version 8.05 or higher. Compatible controllers include CPE305, CPE310, CPU315, CPU320, and CRU320.
What are the power requirements for the IC695ECM850 module?
The module draws 1.2 A at 3.3 VDC without SFPs. With two SFPs, current reaches 1.9 A at 3.3 VDC and 1.1 A at 5 VDC.