HomeABBMOD 300Source I/O Block 16 CircuitsABB 6240BP10411 MOD 300 Source I/O Block 16 Circuits
ABB•Source I/O Block 16 Circuits

ABB 6240BP10411 MOD 300 Source I/O Block 16 Circuits

Pricing
Request Pricing
Contact us for current price and availability.

The ABB 6240BP10411 is a MOD 300 Source I/O Block 16 Circuits complete unit. It operates on an 18 to 30 VDC power supply. The unit provides 16 discrete circuits. Each circuit can be configured independently as an input or an output. The block sources direct current to connected field loads.

ManufacturerABB
Part Number6240BP10411
Product TypeSource I/O Block 16 Circuits
ConditionNew
Warranty12 Months
Lifecycle StatusPart number 6240BP10411 designates the complete 24 VDC source unit. The replacement electronics assembly alone is part number 6240BP10421. The replacement terminal assembly alone is part number 6240BP10431.
AvailabilityRequest current stock
12-Month Warranty30-Day Return Request WindowGlobal Shipping Support
✓
12 Months WarrantyCommercial warranty confirmed with quotation.
↩
30-Day Return RequestEligible returns subject to authorization.
✈
Worldwide ShippingCourier and freight options for international orders.
#
Part Number VerificationSend a label photo when suffix or revision is uncertain.
PRODUCT INFORMATION

Product Overview

The ABB 6240BP10411 is a MOD 300 Source I/O Block 16 Circuits complete unit. It operates on an 18 to 30 VDC power supply. The unit provides 16 discrete circuits. Each circuit can be configured independently as an input or an output. The block sources direct current to connected field loads.

This complete unit includes both the electronics assembly and the terminal assembly. Field wiring terminals accommodate one 12 AWG or two 14 AWG conductors. Built-in diagnostics monitor for short circuits, overloads, and failed switches. The block also detects no-load conditions and circuit overtemperature states. Electrical isolation between blocks is rated at 1500 V.

TECHNICAL DATA

Technical Specifications

ParameterSpecification
Configuration24 VDC source, complete unit
Discrete I/O circuits16; individually configured as inputs or outputs
Operating voltage18–30 VDC for the 24 VDC block
Supply ripple maximum10%
Operational current excluding loads150 mA typical; 300 mA maximum
Supply dropout time10 ms
Block-to-block isolation1500 V
Insulation resistance2.2 Mohm minimum
Terminal wiringOne 12 AWG conductor or two 14 AWG conductors
Weight1.8 kg
Operating temperature0–60 °C
Storage temperature-40 to +100 °C
Relative humidity5–95%, non-condensing
Input impedance1.8 kohm for the 24 VDC block
Input processing time1.7 ms typical plus selected filter delay
Input filter5–100 ms selectable
Output current per circuit2 A steady state
Output inrush current10 A for up to 10 ms
Total block output current15 A at 35 °C
Output off-state leakage1.0 mA
Output turn-on delay1 ms maximum
Output diagnosticsShort circuit, overload, no load, failed switch and overtemperature
TECHNICAL INFORMATION

Features

  • Provides 16 discrete circuits individually configurable as inputs or outputs.
  • Delivers 2 A steady-state output current per circuit.
  • Handles output inrush currents up to 10 A for 10 ms.
  • Supports a total block output load of 15 A at 35 °C.
  • Offers selectable input filter times from 5 to 100 ms.
  • Provides integrated diagnostics for overload, short circuit, and overtemperature conditions.
TECHNICAL INFORMATION

Applications

  • MOD 300 distributed control system discrete field device interfacing.
  • Process automation requiring mixed discrete DC inputs and outputs.
  • Switching discrete field loads such as coils, indicators, and actuators.
TECHNICAL INFORMATION

Connections / Interfaces

  • Terminals 1 through 4 provide connections for the TRIO block field bus.
  • Screw terminals accept one 12 AWG or two 14 AWG field wires.
  • Unit OK and I/O Enabled LEDs show general block operating status.
  • Individual load-side LED indicators display status for each discrete circuit.
TECHNICAL INFORMATION

Installation Guidelines

  1. Operate the block within an ambient temperature range of 0 to 60 °C.
  2. Verify that power supply ripple remains below 10 percent.
  3. Ensure total block output current does not exceed 15 A at 35 °C.
  4. Account for maximum heat dissipation of 68.8 W during enclosure thermal planning.
TECHNICAL INFORMATION

Configuration Guidelines

  1. Configure each of the 16 circuits independently as an input or an output.
  2. Select input filter delay times between 5 and 100 ms.
  3. Enable no-load diagnostics when connected output loads exceed 50 mA.
TECHNICAL INFORMATION

Compatibility

  • Compatible with ABB MOD 300 architectures using TRIO and Genius field bus networks.
TECHNICAL INFORMATION

Lifecycle / Replacement Information

  • Part number 6240BP10411 designates the complete 24 VDC source unit.
  • The replacement electronics assembly alone is part number 6240BP10421.
  • The replacement terminal assembly alone is part number 6240BP10431.
TECHNICAL RESOURCES

Documentation

COMPATIBILITY

Compatibility & Replacement

COMPATIBLE MODELSCompatible with ABB MOD 300 architectures using TRIO and Genius field bus networks.

Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.

PART VERIFICATION

Before You Order

Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.

01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS

From RFQ to Dispatch

1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ

Frequently Asked Questions

What is the configuration of the ABB 6240BP10411 block?
The 6240BP10411 is a complete 24 VDC source unit. It provides 16 discrete circuits configurable as inputs or outputs.
What are the output ratings for the 6240BP10411 block?
Each circuit supplies 2 A steady-state current. Maximum total block output current is 15 A at 35 °C.
What diagnostic features are supported on the block?
The block detects short circuits, overloads, and failed switches. It also flags open wires, no-load conditions, and overtemperature.
What is the block-to-block electrical isolation rating?
The unit provides 1500 V electrical isolation between blocks. Minimum insulation resistance is 2.2 megohms.
What input filter delay settings are selectable?
Input filter times can be configured from 5 to 100 ms. Typical base input processing time is 1.7 ms.
Condition Confirmed Before OrderQuoted condition is confirmed before payment and dispatch.
Warranty & Returns12 Months standard warranty and 30-day return request period.International DeliveryShipping method is selected according to destination and shipment size.
Technical Source PolicySpecifications are published only when supported by product or manufacturer references.
NEED THIS PART?

6240BP10411

Send the quantity and destination country. We will confirm stock, condition, price and lead time.

Get Product Updates and Stock Availability Alerts

    REQUEST A QUOTE

    Check Price & Availability

    ProductABB 6240BP10411 MOD 300 Source I/O Block 16 Circuits
    Part Number: 6240BP10411

      Request a Quote

      Send us the required quantity and destination. We will reply with current availability, lead time and final pricing.

      Home
      Products
      Account