The ABB CI801 3BSE022366R1 Communication Interface Module connects distributed S800 I/O clusters to AC800M controllers. It communicates over industry-standard PROFIBUS-DPV1 fieldbus networks. The module operates as a dedicated PROFIBUS DP-V1 slave unit.

ManufacturerABB
Part Number3BSE022366R1
ModelCI801
Product TypeCommunication Interface Module
ConditionNew
Warranty12 Months
AvailabilityRequest current stock
12-Month Warranty30-Day Return Request WindowGlobal Shipping Support
✓
12 Months WarrantyCommercial warranty confirmed with quotation.
↩
30-Day Return RequestEligible returns subject to authorization.
✈
Worldwide ShippingCourier and freight options for international orders.
#
Part Number VerificationSend a label photo when suffix or revision is uncertain.
PRODUCT INFORMATION

Product Overview

The ABB CI801 3BSE022366R1 Communication Interface Module connects distributed S800 I/O clusters to AC800M controllers. It communicates over industry-standard PROFIBUS-DPV1 fieldbus networks. The module operates as a dedicated PROFIBUS DP-V1 slave unit.

This interface manages signal processing, module supervision, and Output Set as Predetermined functions. It supports Hot Configuration In Run and HART pass-through data transfer. The hardware features IP20 protection and ISA-S71.04 G3 corrosion resistance.

TECHNICAL DATA

Technical Specifications

ParameterSpecification
Communication protocolPROFIBUS DP-V1
Master or slaveSlave
Line redundancyNo
Module redundancyNo
Hot SwapNo
Used together with HI ControllerYes
24 V consumption typ.140 mA
CE- markingYes
Electrical SafetyEN 61010-1, UL 61010-1, EN 61010-2-201, UL 61010-2-201
Hazardous locationC1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2
Marine certificatesABS, BV, DNV, LR, CCS
Temperature, Operating0 to +55 °C (+32 to +131 °F), approvals are issued for +5 to +55 °C
Temperature, Storage-40 to +70 °C (-40 to +158 °F)
Pollution degreeDegree 2, IEC 60664-1
Corrosion protectionISA-S71.04: G3
Relative humidity5 to 95 %, non-condensing
Max ambient temperature55 °C (131 °F), for vertical mounting 40 °C (104 °F)
Protection classIP20 according to EN60529, IEC 529
RoHS complianceEU RoHS, UAE RoHS, CN RoHS
WEEE complianceDIRECTIVE/2012/19/EU
Width85.8 mm
Height136 mm, including latch
Depth58.5 mm
Weight0.3 kg
TECHNICAL INFORMATION

Features

  • Operates as a PROFIBUS DP-V1 slave communication interface.
  • Executes localized signal processing and S800 I/O supervision.
  • Supports Hot Configuration In Run and HART pass-through communication.
  • Provides Output Set as Predetermined fault-handling capabilities.
  • Qualified for use alongside High Integrity safety controllers.
  • Resists severe environmental corrosion per ISA-S71.04 severity level G3.
TECHNICAL INFORMATION

Applications

  • Distributed process automation architectures using S800 I/O hardware.
  • Industrial fieldbus communication interfacing via PROFIBUS DP-V1.
  • Hazardous industrial areas requiring Class I Division 2 or ATEX Zone 2 approval.
  • Marine automation and monitoring systems requiring classification society certifications.
TECHNICAL INFORMATION

Connections / Interfaces

  • Fieldbus connection interfaces directly to PROFIBUS DP-V1 networks.
  • Internal bus links communication directly to adjacent S800 I/O modules.
  • Requires an external 24 V DC power supply drawing 140 mA typically.
TECHNICAL INFORMATION

Installation Guidelines

  1. Install the unit in a clean cabinet providing IP20 protection.
  2. Observe ambient limit of 55 °C for standard horizontal mounting.
  3. Derate maximum ambient operating temperature to 40 °C when mounting vertically.
  4. Maintain non-condensing relative humidity between 5 and 95 percent.
  5. Do not remove or insert the module while power is applied.
TECHNICAL INFORMATION

Configuration Guidelines

  1. Configure module operating parameters through compatible engineering station software.
  2. Set slave address and bus parameters per project PROFIBUS network schedules.
  3. Enable HART pass-through routing for connected smart field transmitters.
TECHNICAL INFORMATION

Compatibility

  • Compatible with ABB AC800M controller platforms.
  • Integrates directly with ABB High Integrity safety controllers.
  • Connects and supervises standard S800 I/O module families.
TECHNICAL INFORMATION

Compliance and Certifications

  • Electrical Safety: EN 61010-1, UL 61010-1, EN 61010-2-201, UL 61010-2-201
  • Hazardous Locations: Class I Div 2 cULus, Class I Zone 2 cULus, ATEX Zone 2
  • Marine Standards: ABS, BV, DNV, LR, CCS
  • Directives: CE marked, EU RoHS, UAE RoHS, CN RoHS, WEEE 2012/19/EU
COMPATIBILITY

Compatibility & Replacement

COMPATIBLE MODELSCompatible with ABB AC800M controller platforms. Integrates directly with ABB High Integrity safety controllers. Connects and supervises standard S800 I/O module families.

Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.

PART VERIFICATION

Before You Order

Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.

01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS

From RFQ to Dispatch

1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ

Frequently Asked Questions

What is the primary role of the ABB CI801 3BSE022366R1?
The CI801 3BSE022366R1 serves as a PROFIBUS DP-V1 slave communication interface module for S800 I/O systems.
Does the CI801 communication interface support hot swapping?
No, the CI801 does not support hot swapping while the module station is energized.
Can the CI801 module be installed in hazardous locations?
Yes, it is certified for Class I Division 2, Class I Zone 2, and ATEX Zone 2 environments.
What is the observed market price for the CI801 3BSE022366R1?
Observed market reference pricing is approximately $887. This figure is an indicative market reference only and is not a final quotation.
Condition Confirmed Before OrderQuoted condition is confirmed before payment and dispatch.
Warranty & Returns12 Months standard warranty and 30-day return request period.International DeliveryShipping method is selected according to destination and shipment size.
Technical Source PolicySpecifications are published only when supported by product or manufacturer references.
NEED THIS PART?

3BSE022366R1

Send the quantity and destination country. We will confirm stock, condition, price and lead time.

Get Product Updates and Stock Availability Alerts

    REQUEST A QUOTE

    Check Price & Availability

    ProductABB CI801 3BSE022366R1 AC800M Communication Interface Module
    Part Number: 3BSE022366R1

      Request a Quote

      Send us the required quantity and destination. We will reply with current availability, lead time and final pricing.

      Home
      Products
      Account