PRODUCT INFORMATION
Product Overview
The ABB AI835A 3BSE051306R1 is an S800 I/O Analog Input Module designed for temperature and voltage monitoring. It provides eight differential input channels configurable for millivolt or thermocouple measurements. Supported sensors include thermocouple types B, C, D, E, J, and K. Types L, N, R, S, T, and U are also supported. It also accepts linear inputs ranging from -30 mV to +75 mV.
Channel 8 can be configured for cold junction temperature measurement to serve channels 1 through 7. The junction temperature can be acquired locally on module termination unit terminals or remotely. Alternatively, fixed junction temperatures can be assigned through parameters or the control application. When cold junction compensation is unneeded, channel 8 operates as a standard differential input.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Signal specification | -30..75 mV linear; TC types B, C, D, E, J, K, L, N, R, S, T and U |
|---|
| Number of channels | 8 |
|---|
| Signal type | See table in S800 Modules and Termination Units, 3BSE020924 |
|---|
| HART | No |
|---|
| SOE | No |
|---|
| Redundancy | No |
|---|
| High integrity | No |
|---|
| Intrinsic safety | No |
|---|
| Mechanics | S800 |
|---|
| Resolution | 15 bits |
|---|
| Input impedance | > 1 MΩ |
|---|
| Isolation | Groupwise isolated from ground |
|---|
| Error | Max. 0.1% |
|---|
| Temperature drift | Typ. 5 ppm/°C, Max. 7 ppm/°C |
|---|
| Update cycle time | 280 + 80 * (number of active channels) ms at 50 Hz; 250 + 70 * (number of active channels) ms at 60 Hz |
|---|
| Maximum field cable length | 600 meters (656 yards) |
|---|
| CMRR, 50Hz, 60Hz | 120 dB |
|---|
| NMRR, 50Hz, 60Hz | > 60 dB |
|---|
| Rated insulation voltage | 50 V |
|---|
| Dielectric test voltage | 500 V a.c. |
|---|
| Power dissipation | 1.6 W |
|---|
| Current consumption +5 V Modulebus | 75 mA |
|---|
| Current consumption +24 V Modulebus | 50 mA |
|---|
| Current consumption +24 V external | 0 |
|---|
| Front LED’s | F(ault), R(un), W(arning) |
|---|
| Supervision | Module error´: reference channels, power supply low Channel error: open-circuit CJ-channel (ch 8): < -40 °C (-40°F) and > 100 °C (212°F) |
|---|
| Status indication of supervision | Module Error, Module Warning, Channel error (8) |
|---|
| CE mark | Yes |
|---|
| Electrical safety | EN 61010-1, UL 61010-1, EN 61010-2-201, UL 61010-2-201 |
|---|
| Hazardous Location | C1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2 |
|---|
| Marine certification | ABS, BV, DNV, LR, CCS |
|---|
| Temperature, Operating | 0 to +55 °C (+32 to +131 °F), approvals are issued for +5 to +55 °C |
|---|
| Temperature, Storage | -40 to +70 °C (-40 to +158 °F) |
|---|
| Pollution degree | Degree 2, IEC 60664-1 |
|---|
| Corrosion protection | ISA-S71.04: G3 |
|---|
| Relative humidity | 5 to 95 %, non-condensing |
|---|
| Max ambient temperature | 55 °C (131 °F), for vertical mounting in compact MTU 40 °C (104 °F) |
|---|
| Protection class | IP20 according to IEC 60529 |
|---|
| EMC | EN 61000-6-4 and EN 61000-6-2 |
|---|
| Overvoltage categories | IEC/EN 60664-1, EN 50178 |
|---|
| RoHS compliance | EU RoHS, UAE RoHS, CN RoHS |
|---|
| WEEE compliance | DIRECTIVE/2012/19/EU |
|---|
| Use with MTU | TU810, TU812, TU814, TU818, TU830, TU833 |
|---|
| Keying code | BA |
|---|
| Width | 45 mm |
|---|
| Depth | 102 mm, 111 mm including connector |
|---|
| Height | 119 mm |
|---|
| Weight | 0.22 kg |
|---|
TECHNICAL INFORMATION
Features
- Eight differential input channels supporting linear millivolt and twelve thermocouple types.
- Configurable cold junction compensation on channel 8 or via fixed temperature parameters.
- 15-bit resolution with maximum measurement error limited to 0.1 percent.
- Groupwise isolation from ground with 500 V AC dielectric test voltage rating.
- Internal supervision for open circuits, reference channels, and power supply levels.
- Modulebus current draw of 75 mA at 5 V and 50 mA at 24 V.
- Certified for Class 1 Division 2, Zone 2, and ATEX Zone 2 hazardous locations.
- Marine certifications from ABS, BV, DNV, LR, and CCS.
TECHNICAL INFORMATION
Applications
- Temperature monitoring in industrial automation processes using thermocouples.
- Millivolt signal acquisition from low-voltage field sensors and transducers.
- Distributed I/O setups in marine and hazardous industrial environments.
TECHNICAL INFORMATION
Connections / Interfaces
- Mounts on compatible Module Termination Units including TU810, TU812, TU814, TU818, TU830, and TU833.
- Communicates over the S800 Modulebus backplane interface.
- Field connections support cable runs up to 600 meters.
TECHNICAL INFORMATION
Installation Guidelines
- Insert the module into a compatible MTU with mechanical keying code BA.
- Operate within ambient temperatures up to 55 °C for standard mounting.
- Limit maximum ambient temperature to 40 °C when mounting vertically in compact MTUs.
- Maintain clean operating conditions conforming to IEC 60664-1 pollution degree 2.
TECHNICAL INFORMATION
Configuration Guidelines
- Configure individual input ranges per channel for linear millivolts or specific thermocouple types.
- Assign channel 8 as the cold junction reference channel if ambient compensation is needed.
- Set fixed cold junction values via software parameters when using external compensation.
TECHNICAL INFORMATION
Compatibility
- Compatible with ABB Module Termination Units TU810, TU812, TU814, TU818, TU830, and TU833.
- Interfaces with ABB S800 I/O communication interfaces via Modulebus.
TECHNICAL INFORMATION
Compliance and Certifications
- CE Marked
- Electrical Safety: EN 61010-1, UL 61010-1, EN 61010-2-201, UL 61010-2-201
- Hazardous Locations: C1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2
- Marine: ABS, BV, DNV, LR, CCS
- EMC: EN 61000-6-4, EN 61000-6-2
- Environmental: RoHS (EU, UAE, CN), WEEE 2012/19/EU, ISA-S71.04 G3
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSCompatible with ABB Module Termination Units TU810, TU812, TU814, TU818, TU830, and TU833. Interfaces with ABB S800 I/O communication interfaces via Modulebus.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What sensor types work with the ABB AI835A 3BSE051306R1 module?
The module accepts linear -30 to +75 mV signals. It supports thermocouple types B, C, D, E, J, and K. Channels also accept types L, N, R, S, T, and U.
How does cold junction compensation function on the AI835A?
Channel 8 can measure junction temperature locally on MTU terminals or remotely. Fixed values can also be assigned.
Which termination units support the ABB AI835A?
The module mounts on ABB MTU models TU810, TU812, TU814, TU818, TU830, and TU833 with key code BA.
What is the market reference price for the ABB AI835A 3BSE051306R1?
Observed market reference pricing spans $697.00 to $1270.00 depending on condition. These figures are indicative market reference pricing only and are not a final quotation.