PRODUCT INFORMATION
Product Overview
The General Electric IC693MDL230 is an isolated input module designed for Series 90-30 systems. This unit provides eight isolated input points featuring reactive input circuits. It operates at a rated voltage of 120 V AC at 50/60 Hz. The module functions strictly on AC power and does not operate using DC sources. Field-side to logic-side isolation is rated at 1500 V RMS. Users must provide an external AC power source to operate connected field devices.
A single common power input terminal delivers power across all eight input points. An LED block on top of the module contains eight status indicators. These LEDs illuminate green during normal operation and show red during a system fault. A hinged door houses an insertable card to record circuit identification data. Red edge striping on the card signifies that the module is a high-voltage unit. The module mounts directly into any available I/O slot in a Series 90-30 baseplate.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| AC Power | Yes |
|---|
| Compatible with | Programmable Logic Controllers |
|---|
| DC Power | No |
|---|
| Frequency | 50/60 Hertz |
|---|
| Input Current at a Rated Speed | 14.5 mA |
|---|
| Inputs | 8 |
|---|
| Isolation between field side and logic side | 1500 V RMS |
|---|
| LED Indicators | 8 |
|---|
| Product Line | Series 90-30 |
|---|
| Voltage | 120 V AC |
|---|
| Weight | 1.50 lbs (0.68 kg) |
|---|
TECHNICAL INFORMATION
Features
- Eight isolated discrete input points with reactive input circuitry.
- Rated input voltage of 120 V AC at 50/60 Hz frequency.
- Field-side to logic-side electrical isolation rated at 1500 V RMS.
- Input current rated at 14.5 mA.
- Top LED status block with eight indicators showing normal and fault conditions.
- Single common power input terminal distributing AC power to all points.
- Hinged front door with red-striped circuit identification card.
- Direct compatibility with any Series 90-30 baseplate I/O slot.
TECHNICAL INFORMATION
Applications
- Interfacing 120 V AC pushbuttons with Series 90-30 controllers.
- Connecting mechanical limit switches in industrial automation setups.
- Monitoring electronic proximity switches that supply 120 V AC signals.
TECHNICAL INFORMATION
Connections / Interfaces
- One common power input terminal for external AC power distribution.
- Eight isolated input wiring terminals behind the protective door.
TECHNICAL INFORMATION
Installation Guidelines
- Insert the module into any available I/O slot in a Series 90-30 baseplate.
- Provide an external 120 V AC power source to operate the field circuits.
- Record field circuit identification details on the outer face of the door card.
TECHNICAL INFORMATION
Compatibility
- Series 90-30 baseplate I/O slots.
- 120 V AC pushbuttons, limit switches, and electronic proximity switches.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSSeries 90-30 baseplate I/O slots. 120 V AC pushbuttons, limit switches, and electronic proximity switches.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
Can the IC693MDL230 module operate using a DC power source?
No. The IC693MDL230 module operates exclusively on AC power and cannot function with DC power.
What electrical isolation does the IC693MDL230 module provide?
The module provides 1500 V RMS isolation between the field side and the logic side.
Which baseplate slots can host the IC693MDL230 module?
It installs into any available I/O slot in a Series 90-30 baseplate.
What do the module LED status indicators signal?
The eight LEDs turn green during normal operation and display red when a fault occurs.