PRODUCT INFORMATION
Product Overview
The ABB AI825 3BSE036456R1 is an S800 I/O analog input module. It provides four individually isolated bipolar input channels for current and voltage signals. Each channel can be configured independently as either a voltage input or a current input. Power to the internal input stages is converted directly from the twenty-four volt ModuleBus line.
The module includes a direct current input that withstands voltages up to 6.3 volts DC. An overvoltage protected current input withstands up to positive thirty volts direct current. Internal PTC resistors limit input current to protect signal conditioning circuitry. The analog-to-digital converter delivers fourteen bits of resolution plus sign.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Signal specification | -20..+20 mA, 0(4)..20 mA, -10..+10 V, 0(2)..10V |
|---|
| Number of channels | 4 |
|---|
| HART | No |
|---|
| SOE | No |
|---|
| Redundancy | No |
|---|
| High integrity | No |
|---|
| Intrinsic safety | No |
|---|
| Mechanics | S800 |
|---|
| Resolution | 14 bit plus sign |
|---|
| Input impedance | 10 MΩ (voltage input) 50 Ω (current input) |
|---|
| Isolation | Individually isolated, channel-to-channel and to circuit common |
|---|
| Under/over range | ± 15% |
|---|
| Error | Max. 0.1% |
|---|
| Temperature drift | Max. 47 ppm/°C (0..10V), Max. 34 ppm/°C (±10V), Max. 78 ppm/°C (0..20mA), Max. 57 ppm/°C (±20mA) |
|---|
| Input filter (rise time 0-90%) | 115 ms (voltage input), 130 ms (current input) |
|---|
| Update cycle time | < 10ms |
|---|
| Maximum field cable length | 600 meters (656 yards) |
|---|
| CMRR, 50Hz, 60Hz | 120 dB |
|---|
| NMRR, 50Hz, 60Hz | > 40 dB at 50 Hz, >55 dB at 60 Hz |
|---|
| Rated insulation voltage | 250 V |
|---|
| Dielectric test voltage | 1900 V d.c. ch-ch, 3250 V d.c. ch-ground/system, |
|---|
| Power dissipation | Typ. 2.5 W, Max. 3.2 W |
|---|
| Current consumption +5 V Modulebus | Typ. 70 mA, Max. 100 mA |
|---|
| Current consumption +24 V Modulebus | Typ. 90 mA, Max. 110 mA |
|---|
| Current consumption +24 V external | 0 |
|---|
| Front LED’s | F(ault), R(un), W(arning) |
|---|
| Supervision | Internal Power Supply |
|---|
| Status indication of supervision | Module Error, Module Warning, Channel error |
|---|
| CE mark | Yes |
|---|
| Electrical safety | EN 61010-1, UL 61010-1, EN 61010-2-201, UL 61010-2-201 |
|---|
| Hazardous Location | - |
|---|
| Marine certification | - |
|---|
| Temperature, Operating | 0 to +55 °C (+32 to +131 °F), approvals are issued for +5 to +55 °C |
|---|
| Temperature, Storage | -40 to +70 °C (-40 to +158 °F) |
|---|
| Pollution degree | Degree 2, IEC 60664-1 |
|---|
| Corrosion protection | ISA-S71.04: G3 |
|---|
| Relative humidity | 5 to 95 %, non-condensing |
|---|
| Max ambient temperature | 55 °C (131 °F), for vertical mounting in compact MTU 40 °C (104 °F) |
|---|
| Protection class | IP20 according to IEC 60529 |
|---|
| EMC | EN 61000-6-4, EN 61000-6-2 |
|---|
| Overvoltage categories | IEC/EN 60664-1, EN 50178 |
|---|
| RoHS compliance | EU RoHS, UAE RoHS, CN RoHS |
|---|
| WEEE compliance | DIRECTIVE/2012/19/EU |
|---|
| Use with MTU | TU811, TU813, TU831 |
|---|
| Keying code | DA |
|---|
| Width | 45 mm |
|---|
| Depth | 102 mm, 111 mm including connector |
|---|
| Height | 119 mm |
|---|
| Weight | 0.22 kg |
|---|
TECHNICAL INFORMATION
Features
- Four individually galvanic isolated bipolar channels for voltage or current signals.
- Input resolution of fourteen bits plus sign with an update cycle time under ten milliseconds.
- Channel-to-channel dielectric isolation rated at 1900 volts direct current.
- Channel-to-ground dielectric isolation rated at 3250 volts direct current.
- High input impedance of ten megaohms for voltage inputs and fifty ohms for current.
- Front panel light-emitting diodes indicate Fault, Run, and Warning status.
TECHNICAL INFORMATION
Installation Guidelines
- Insert the module into a compatible terminal unit configured with mechanical keying code DA.
- Maximum ambient operating temperature is fifty-five degrees Celsius for standard mounting.
- Derate maximum ambient temperature to forty degrees Celsius for vertical mounting in compact MTUs.
- Maintain maximum field wiring cable lengths within six hundred meters.
TECHNICAL INFORMATION
Compatibility
- Compatible with ABB Module Termination Units TU811, TU813, and TU831.
- Designed for connection directly onto the ABB S800 ModuleBus backplane interface.
TECHNICAL INFORMATION
Compliance and Certifications
- Electrical safety compliant with EN 61010-1, UL 61010-1, EN 61010-2-201, and UL 61010-2-201.
- Electromagnetic compatibility compliant with EN 61000-6-2 and EN 61000-6-4.
- Corrosion protection conforms to ISA-S71.04 severity level G3.
- Compliant with EU RoHS, CN RoHS, UAE RoHS, and WEEE directives.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSCompatible with ABB Module Termination Units TU811, TU813, and TU831. Designed for connection directly onto the ABB S800 ModuleBus backplane interface.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What signal types can be connected to the ABB AI825 3BSE036456R1 module?
Each channel accepts bipolar or unipolar signals. Supported ranges include +/-20 mA, 0-20 mA, 4-20 mA, +/-10 V, and 0-10 V.
Which Module Termination Units are compatible with the AI825 module?
The AI825 module installs onto ABB TU811, TU813, and TU831 Module Termination Units.
Does the AI825 module require an external twenty-four volt power supply?
No external twenty-four volt power connection is required. The module converts field power directly from the ModuleBus.
What is the isolation level between channels on the AI825?
Channels are individually galvanic isolated. Dielectric test voltage is rated at 1900 volts direct current channel-to-channel.