PRODUCT INFORMATION
Product Overview
The ABB DI840 3BSE020836R1 is a 16-channel 24 V d.c. Digital Input Module for the S800 I/O platform. It supports single or redundant architectures in distributed automation setups. Each channel operates as a current-sinking input drawing 7 mA at 24 V d.c. Optical isolation barriers and EMC protection components protect internal circuitry from field interference.
Integrated sequence of events recording collects digital transitions with 1 ms resolution. The internal event queue holds up to 257 events with an integrated shutter filter. Field transducer power is supervised and current-limited with one output per two input channels. Diagnostic LEDs on the front indicate module errors, warnings, run state, and individual channel status.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Signal specification | 24 V d.c. |
|---|
| Number of channels | 16 |
|---|
| Signal type | Current sinking |
|---|
| HART | No |
|---|
| SOE | Yes |
|---|
| Redundancy | Yes |
|---|
| High integrity | No |
|---|
| Intrinsic safety | No |
|---|
| Mechanics | S800 |
|---|
| Input voltage range, "0" | -30..+5 V |
|---|
| Input voltage range, "1" | 11..30 V |
|---|
| Input impedance | 3.3 kΩ |
|---|
| Isolation | Groupwise isolated from ground |
|---|
| Filter times (digital, selectable) | 0 to 127 ms |
|---|
| Current limiting | Built in current limited sensor power |
|---|
| Maximum field cable length | 600 meters (656 yards) |
|---|
| Event recording accuracy | 0 ms / +1.3 ms |
|---|
| Event recording resolution | 1 ms |
|---|
| Rated insulation voltage | 50 V |
|---|
| Dielectric test voltage | 500 V a.c. |
|---|
| Power dissipation | Typ. 2.7 W |
|---|
| Current consumption +5 V Modulebus | 100 mA |
|---|
| Current consumption +24 V external | 15 mA + transducer power, Max 335 mA |
|---|
| Front LED’s | F(ault), R(un), W(arning), Channel 1-16 Status |
|---|
| Supervision | Process power, Internal circuitry |
|---|
| Status indication of supervision | Module Error, Module Warning, Channel error |
|---|
| CE mark | Yes |
|---|
| Electrical safety | EN 61010-1, UL 61010-1, EN 61010-2-201, UL 61010-2-201 |
|---|
| Hazardous Location | C1 Div 2 cULus, C1 Zone 2 cULus, ATEX Zone 2 |
|---|
| Marine certification | ABS, BV, DNV, LR, CCS |
|---|
| Temperature, Operating | 0 to +55 °C (+32 to +131 °F), approvals are issued for +5 to +55 °C |
|---|
| Temperature, Storage | -40 to +70 °C (-40 to +158 °F) |
|---|
| Pollution degree | Degree 2, IEC 60664-1 |
|---|
| Corrosion protection | ISA-S71.04: G3 |
|---|
| Relative humidity | 5 to 95 %, non-condensing |
|---|
| Max ambient temperature | 55 °C (131 °F), for vertical mounting in compact MTU 40 °C (104 °F) |
|---|
| Protection class | IP20 according to IEC 60529 |
|---|
| EMC | EN 61000-6-4 and EN 61000-6-2 |
|---|
| Overvoltage categories | IEC/EN 60664-1, EN 50178 |
|---|
| RoHS compliance | EU RoHS, UAE RoHS, CN RoHS |
|---|
| WEEE compliance | DIRECTIVE/2012/19/EU |
|---|
| Use with MTU | TU810, TU812, TU814, TU818, TU830, TU833, TU838, TU842, TU843, TU852 |
|---|
| Keying code | CD |
|---|
| Width | 45 mm |
|---|
| Depth | 102 mm, 111 mm including connector |
|---|
| Height | 119 mm |
|---|
| Weight | 0.15 kg |
|---|
TECHNICAL INFORMATION
Features
- Sixteen current-sinking digital input channels rated for 24 V d.c. operation.
- Support for single and redundant module configurations in S800 I/O stations.
- Sequence of events recording with 1 ms resolution and 257-event buffer.
- Supervised, current-limited transducer power distribution for field sensors.
- Selectable digital input filtering from 0 to 127 ms.
- Groupwise electrical isolation tested to 500 V a.c. against ground.
- Comprehensive front-panel LED indicators for channel status and internal supervision.
TECHNICAL INFORMATION
Applications
- Industrial plant sequence of events monitoring requiring 1 ms time stamping.
- Redundant digital input acquisition in ABB S800 distributed control nodes.
- Machinery status detection and digital interlock monitoring in harsh process areas.
- Marine and offshore systems requiring certified automation hardware.
TECHNICAL INFORMATION
Connections / Interfaces
- Mounts onto compatible S800 Module Termination Units (MTUs) via mechanical keying code CD.
- Communicates over the +5 V Modulebus backplane interface drawing up to 100 mA.
- Provides supervised 24 V d.c. sensor power outputs paired per two input channels.
TECHNICAL INFORMATION
Installation Guidelines
- Install on compatible MTU bases including TU810, TU812, TU814, TU830, TU842, or TU852.
- Verify mechanical keying code CD matches the destination slot before insertion.
- Limit ambient operating temperature to 40 °C when mounting vertically in compact MTUs.
- Ensure field wiring runs do not exceed the 600-meter maximum cable limit.
TECHNICAL INFORMATION
Configuration Guidelines
- Configure digital input filter times between 0 and 127 ms per application needs.
- Enable sequence of events queue and adjust the shutter filter to suppress contact bounce.
- Assign redundant channel pairs within engineering tools when dual modules are utilized.
TECHNICAL INFORMATION
Compatibility
- ABB S800 I/O Module Termination Units TU810, TU812, TU814, TU818, and TU830.
- Redundant MTU bases TU833, TU838, TU842, TU843, and TU852.
- ABB S800 I/O communication interfaces and controllers supporting Modulebus.
TECHNICAL INFORMATION
Lifecycle / Replacement Information
- Maintained as standard hardware within the ABB S800 I/O system family.
- Can replace defective units directly on matched MTU bases without rewiring.
TECHNICAL INFORMATION
Compliance and Certifications
- CE Mark
- EN 61010-1, UL 61010-1, EN 61010-2-201, UL 61010-2-201
- Class I, Division 2 cULus, Class I, Zone 2 cULus, ATEX Zone 2
- Marine certifications: ABS, BV, DNV, LR, CCS
- EU RoHS, UAE RoHS, CN RoHS, and WEEE Directive 2012/19/EU
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSABB S800 I/O Module Termination Units TU810, TU812, TU814, TU818, and TU830. Redundant MTU bases TU833, TU838, TU842, TU843, and TU852. ABB S800 I/O communication interfaces and controllers supporting Modulebus.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the primary function of the ABB DI840 module?
The DI840 3BSE020836R1 acquires sixteen 24 V d.c. sinking digital inputs for S800 I/O systems.
Does the DI840 support Sequence of Events recording?
Yes, it records events with 1 ms resolution and stores up to 257 transitions.
Can the DI840 be used in redundant configurations?
Yes, it supports redundant deployment using dual modules on compatible termination units like TU842.
Which termination units are compatible with the DI840?
It fits MTUs including TU810, TU812, TU814, TU818, TU830, TU833, TU838, TU842, TU843, and TU852.
What is the market reference price for the ABB DI840 3BSE020836R1?
Observed market reference pricing is around $379 USD. This is an indicative reference price only and not a final quotation.