PRODUCT INFORMATION
Product Overview
The ABB PM866AK02 3BSE081637R1 is an AC800M Controller designed for redundant operation. It features a 133 MHz MPC866 microprocessor with 64 MB of total memory. Application programs use 51.389 MB of dedicated RAM. The controller executes 1000 boolean operations in 0.09 ms. Up to 32 tasks and 32 applications run per controller node. Cycle times can be configured down to 1 ms.
Redundant configurations deliver a maximum hardware switchover time of 10 ms. The package includes base mounting hardware with a total weight of 2700 g. Dual RJ-45 ports provide 10 Mbit/s Ethernet connectivity. The unit communicates over CEX bus supporting up to 12 modules. Modulebus connectivity supports up to 84 redundant I/O modules across seven optical clusters. An internal 3.6 V lithium battery provides real-time clock and memory backup.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Processor Type | MPC866 |
|---|
| Clock Frequency | 133 MHz |
|---|
| Performance | 0.09 ms per 1000 boolean operations |
|---|
| System Memory | 64 MB |
|---|
| RAM Available for Application | 51.389 MB |
|---|
| Firmware Storage | 4 MB Flash PROM |
|---|
| Redundancy | Yes |
|---|
| Redundant Switchover Time | Max 10 ms |
|---|
| Power Supply | 24 V DC (19.2 to 30 V DC) |
|---|
| Power Consumption | 210 mA typical, 360 mA maximum at 24 V DC |
|---|
| Power Dissipation | 5.1 W typical, 8.6 W maximum |
|---|
| Backup Battery | Lithium, 3.6 V |
|---|
| Ethernet Channels | 2 x RJ-45 female (10 Mbit/s, IEEE 802.3) |
|---|
| CEX Bus Module Capacity | Up to 12 communication modules |
|---|
| Modulebus Redundant I/O Capacity | Max 84 I/O modules (7 optical clusters) |
|---|
| Operating Temperature | 0 to +55 °C (+32 to +131 °F) |
|---|
| Protection Class | IP20 (EN 60529, IEC 529) |
|---|
TECHNICAL INFORMATION
Features
- Equipped with a 133 MHz MPC866 processor executing 1000 boolean operations in 0.09 ms.
- Provides 64 MB total memory with 51.389 MB dedicated RAM for applications.
- Supports hardware redundancy with a maximum switchover time of 10 ms.
- Expands communication capacity with up to 12 modules via the CEX bus.
- Interfaces with up to 84 I/O modules across seven optical Modulebus clusters.
- Includes dual RJ-45 ports for 10 Mbit/s Ethernet control network communication.
TECHNICAL INFORMATION
Applications
- High-availability process control setups requiring redundant controller hardware.
- Industrial control architectures running high-speed tasks with cycle times down to 1 ms.
- Control networks utilizing MMS protocol and Inter Application Communication.
TECHNICAL INFORMATION
Connections / Interfaces
- Two 8-pole female RJ-45 connectors for 10 Mbit/s Ethernet links.
- Built-in CEX bus connector supplying up to 2.4 A current.
- Optical Modulebus ports supporting up to seven optical I/O clusters.
- Two RS-232C serial ports for communication and service tool connection.
- Dedicated inputs for redundant power supply status monitoring.
- Built-in CompactFlash memory card interface.
TECHNICAL INFORMATION
Installation Guidelines
- Mount the assembly on standard DIN rails within an IP20 operating environment.
- Supply nominal 24 V DC power within the allowable 19.2 to 30 V DC range.
- Ensure ambient operating temperatures remain between 0 and +55 °C.
- Comply with pollution degree 2 limits according to IEC/EN 61131-2.
TECHNICAL INFORMATION
Configuration Guidelines
- Configure up to 32 independent control tasks and 32 applications per node.
- Assign application program cycle times down to 1 ms.
- Maintain controller clock synchronization within 1 ms via CNCP protocol.
- Manage up to 3000 events per OPC client queue.
TECHNICAL INFORMATION
Compatibility
- Integrates into the ABB AC800M controller hardware family.
- Supports ABB AC800M communication modules on the CEX expansion bus.
- Connects to optical Modulebus clusters for local and remote I/O expansion.
TECHNICAL INFORMATION
Compliance and Certifications
- CE Mark certified under EN 61000-6-2 and EN 61000-6-4 standards.
- Electrical safety certified per EN 50178, IEC 61131-2, and UL 61010-1.
- Hazardous location certified for cULus Class 1, Zone 2, Ex nA IIC T4 Gc X.
- ISA Secure certified and compliant with ISA 71.04 G3 corrosion protection.
- Marine certifications granted by ABS, BV, DNV, LR, and CCS.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSIntegrates into the ABB AC800M controller hardware family. Supports ABB AC800M communication modules on the CEX expansion bus. Connects to optical Modulebus clusters for local and remote I/O expansion.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the redundant switchover time for the ABB PM866AK02?
The switchover time between redundant processors is a maximum of 10 ms.
How much memory is available for user applications on the PM866AK02?
The controller provides 64 MB of total memory with 51.389 MB dedicated to application execution.
How many I/O modules does the PM866AK02 support in redundant mode?
In redundant mode, the unit supports up to 84 I/O modules across seven optical Modulebus clusters.
What are the input power ratings for the PM866AK02 controller?
It operates on 24 V DC within a 19.2 to 30 V DC range, consuming 210 to 360 mA.