PRODUCT INFORMATION
Product Overview
The General Electric IC200PNS001 is a VersaMax Remote I/O Profinet Network Interface Unit. This module functions as a PROFINET Slave Version 2.2 Class A IO-Device. It coordinates a VersaMax remote node with an upstream PROFINET IO controller. Compatible systems include PACSystems RX3i, PACSystems RX7i, and Series 90-70 controllers. The module manages input data retrieval and output data delivery across the distributed network.
The IC200PNS001 supports up to eight VersaMax IO modules per remote station. It provides two RJ45 ports with an integrated switch using one IP address. Supported network topologies include star, line, and ring configurations. The module handles 1440 bytes of input data and 1440 bytes of output data. Additionally, it offers 32 input status bits and 32 output control bits for diagnostic monitoring.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Weight | 1.19 lbs (0.54 kg) |
|---|
| Power Consumption | 0.60 Amperes at 5 Volts DC |
|---|
| Product Description | Profinet network interface unit |
|---|
| Supported protocol | PROFINET version Version 2.2 Class A IO-Device |
|---|
| Supported Protocols | PROFINET Slave, Version 2.2 Class A IO-Device |
|---|
| Proficy Machine Edition Version Required | Version 7.0 or later |
|---|
| Supported topologies | Linear, Star, Ring (redundant) |
|---|
| No. of Ports | Two (2) RJ45ports |
|---|
| Module Dimensions | Height: 132mm (5.2 inches), Width: 134mm (5.28 inches) |
|---|
| Distance | 100 m |
|---|
| Number of Port Connectors | Two RJ-45 |
|---|
| Transmission rate | 10/100 mbps |
|---|
| Transmission speed | 10/100 mbps |
|---|
| I/O Discrete Points | 2880 bytes total 1440 bytes of input data 1440 bytes of output data |
|---|
| Maximum cable distance | 100 meters per segment |
|---|
| PNS Status and Control Bits | 32 input status bits and 32 output control bits |
|---|
| I/O Analog Words | 2880 bytes total 1440 bytes of input data 1440 bytes of output data |
|---|
| Mounting | DIN Rail |
|---|
| I/O Data Update on the PROFINET LAN | Configurable: 1ms, 2ms, 4ms, 8ms, 16ms, 32ms, 64ms, 128ms, 256ms and 512ms |
|---|
| No. of modules | Eight (8) modules |
|---|
| No. of supported I/O modules | up to Eight (8) modules |
|---|
| RoHS Compliance | Yes |
|---|
| No. of racks | Not supported |
|---|
| Operating Temperature Range | 0 to 60 degrees Celsius surrounding air temperature without a fan |
|---|
| I/O Update rate | Configurable: 1ms, 2ms, 4ms, 8ms, 16ms, 32ms, 64ms, 128ms, 256ms and 512ms |
|---|
| Compatible controllers | Series 90-70; PACSystem RX7i; PACSystem RX3i |
|---|
| Diagnostic data | 32 input status bits; 32 output control bits |
|---|
| I/O Data update rate | 1ms, 2ms, 4ms, 8ms, 16ms, 32ms, 64ms, 128ms, 256ms and 512ms |
|---|
TECHNICAL INFORMATION
Features
- Operates as a PROFINET Slave Version 2.2 Class A IO-Device.
- Integrated two-port RJ45 Ethernet switch operating under a single IP address.
- Supports linear, star, and redundant ring network topologies.
- Accommodates up to eight VersaMax I/O modules per network interface unit.
- Handles up to 1440 bytes of input data and 1440 bytes of output data.
- Configurable PROFINET LAN update rates ranging from 1 ms to 512 ms.
- Built-in diagnostic capability with 32 input status bits and 32 output control bits.
- Dedicated USB port provided for firmware updates.
TECHNICAL INFORMATION
Applications
- Distributed I/O connectivity for PACSystems RX3i and RX7i controller architectures.
- Remote I/O expansion in industrial Ethernet networks using the PROFINET protocol.
TECHNICAL INFORMATION
Connections / Interfaces
- Two 10/100BASE-T RJ45 ports provide dual-port connectivity with embedded switching.
- The USB port is reserved solely for firmware upgrades.
TECHNICAL INFORMATION
Installation Guidelines
- Mounts directly on standard DIN rail within the control cabinet.
- Operates in ambient temperatures from 0 to 60 degrees Celsius without fan cooling.
- Uses standard 10/100BASE-T copper cabling up to 100 meters per segment.
TECHNICAL INFORMATION
Configuration Guidelines
- Requires Proficy Machine Edition software version 7.0 or later.
- Requires an RX3i CPU running firmware version 7.0 or newer.
- Supports Classless InterDomain Routing with supernetting and subnetting capabilities.
TECHNICAL INFORMATION
Compatibility
- Compatible with PACSystems RX3i, PACSystems RX7i, and Series 90-70 controllers.
- Supports up to eight VersaMax I/O modules and carriers per node.
- Additional expansion racks are not supported by this interface unit.
TECHNICAL INFORMATION
Compliance and Certifications
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSCompatible with PACSystems RX3i, PACSystems RX7i, and Series 90-70 controllers. Supports up to eight VersaMax I/O modules and carriers per node. Additional expansion racks are not supported by this interface unit.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
How many I/O modules does the General Electric IC200PNS001 support?
The IC200PNS001 supports up to eight VersaMax I/O modules and carriers per interface unit.
What network topologies are supported by the IC200PNS001?
The module supports linear, star, and redundant ring PROFINET network topologies.
Which software version is required to configure the IC200PNS001?
Configuration requires Proficy Machine Edition software version 7.0 or later.
What controllers are compatible with the IC200PNS001?
It is compatible with PACSystems RX3i, PACSystems RX7i, and Series 90-70 controllers.