PRODUCT INFORMATION
Product Overview
The General Electric IC695ALG508 is an RTD Input Module for the PACSystems RX3i platform. It provides eight isolated differential channels for direct temperature sensing or linear resistance inputs. Supported RTD sensor elements include Platinum, Nickel, Copper, and Nickel-Iron. Wiring configurations accommodate 2-wire, 3-wire, or 4-wire sensors. Internal temperature linearization is formulated according to ITS-90 standards.
This module mounts directly into an RX3i universal backplane. It supports Removal and Insertion Under Power during routine maintenance. Internal power draws 400 mA at 3.3 VDC and 200 mA at 5.1 VDC. Field wiring connects using compatible box-style or spring-style terminal blocks. Extended terminal block versions provide extra depth for shielded wiring. Diagnostic LEDs show module operational status and external field power presence.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Weight | 1.31 lbs (0.60 kg) |
|---|
| Product Description | Resistance Temperature Detector (RTD) Input module |
|---|
| Module Type | RTD Input Module |
|---|
| No of Channels | Eight (8), isolated, differential |
|---|
| Number of Inputs | 8 Differential Inputs |
|---|
| RTD Input types | 50, 100, 200, 500, and 1000 ohm Platinum 385 (IEC751 1983, Amend 2 1995; JISC 1604 1997); 50, 100, 200, 500, and 1000 ohm Platinum 391.6 (JISC 1604: 1981); 100 ohm, 200 ohm, 500 ohm, and 1000 ohm Nickel 618 (DIN 43760 Sept. 1987); 120 ohm Nickel 672 (MINCO Application Aid #18, 5/90 Type Ni); 10, 50, and 100 ohm Copper 426 (SAMA RC21-4-1966) and 604 ohm Nickel-Iron 518 |
|---|
| Internal Power | 3.3V @ 400mA and 5.1V @ 200 mA |
|---|
| RTD Wiring | 2, 3, or 4 wire RTD types |
|---|
| Range (Ohms) | 250/500/1000/2000/3000/4000 |
|---|
| Resistance inputs | 0-260, 0-525, 0-1050, 0-2100, 0-3150, 0-4200 ohms |
|---|
| Power Dissapation | 2.5W max |
|---|
| Measurement Units | Degrees C or F, or Ohms |
|---|
| Operating Temperature | 0 to 60 degrees Celsius |
|---|
| Configurable notch filters | 2.3 Hz to 28 Hz |
|---|
| Storage Temperature | -40 to 85 degrees Celsius |
|---|
| Hot-Swap | Supports Removal and Insertion Under Power (RIUP) |
|---|
| Humidity | 5 to 95%, Non-condensing |
|---|
| Data Format | 16-bit integer (in a 32-bit field) or 32-bit real number data for each channel |
|---|
| Module Fault status | Watchdog, RAM Fail, Flash Fail |
|---|
| Current consumption | 3.3V: 400mA; 5V: 200mA |
|---|
TECHNICAL INFORMATION
Features
- Eight isolated differential channels configurable independently for RTD or resistance acquisition.
- Supports Platinum 385, Platinum 391.6, Nickel 618, Nickel 672, Copper 426, and Nickel-Iron 518 sensor types.
- Handles resistance ranges including 0 to 260, 525, 1050, 2100, 3150, and 4200 ohms.
- Configurable notch filter frequency per channel from 2.3 Hz to 28 Hz.
- Selectable data format in 16-bit integer or 32-bit IEEE floating-point values.
- Configurable module reaction holding last state or defaulting on CPU stop or system fault.
- Supports hot-swapping through Removal and Insertion Under Power capabilities.
TECHNICAL INFORMATION
Applications
- PACSystems RX3i industrial temperature acquisition requiring high channel-to-channel isolation.
- Direct interface to 2-wire, 3-wire, or 4-wire RTD temperature probes in process control.
- Resistance measurement across broad ranges up to 4200 ohms without external signal conditioners.
TECHNICAL INFORMATION
Connections / Interfaces
- Compatible with IC694TBB032 box-style terminal blocks.
- Compatible with IC694TBB132 extended box-style terminal blocks.
- Compatible with IC694TBS032 spring-style terminal blocks.
- Compatible with IC694TBS132 extended spring-style terminal blocks.
TECHNICAL INFORMATION
Installation Guidelines
- Install the module into any available slot of an RX3i Universal Backplane.
- Extended terminal blocks are recommended when terminating shielded sensor wiring.
- Ensure terminal blocks are secured to the module face prior to system operation.
- Removal and insertion under power may be performed while the backplane is energized.
TECHNICAL INFORMATION
Configuration Guidelines
- Configure individual channels for specific RTD sensor curves or raw resistance ranges.
- Select engineering units in degrees Celsius, degrees Fahrenheit, or ohms.
- Set data reporting format to either 16-bit integer or 32-bit floating-point data.
- Adjust the programmable notch filter between 2.3 Hz and 28 Hz to reject process noise.
TECHNICAL INFORMATION
Compatibility
- PACSystems RX3i Universal Backplane systems.
- Terminal block assemblies IC694TBB032, IC694TBB132, IC694TBS032, and IC694TBS132.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSPACSystems RX3i Universal Backplane systems. Terminal block assemblies IC694TBB032, IC694TBB132, IC694TBS032, and IC694TBS132.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
How many RTD channels does the IC695ALG508 provide?
The IC695ALG508 features eight isolated differential input channels. Each channel can be configured independently for temperature or resistance sensors.
Which terminal blocks are compatible with the IC695ALG508?
It uses IC694TBB032, IC694TBB132, IC694TBS032, or IC694TBS132 terminal blocks. Extended versions provide additional depth for shielded cables.
Can the IC695ALG508 be replaced while the PACSystems RX3i backplane is powered?
Yes. The IC695ALG508 supports Removal and Insertion Under Power inside compatible PACSystems RX3i backplanes.