PRODUCT INFORMATION
Product Overview
The General Electric IC695PBM300 is a PROFIBUS Master Module designed for the PACSystems RX3i control platform. This single-slot module occupies a universal backplane location using the RX3i PCI bus interface. It enables the RX3i central processor to exchange cyclic and acyclic data across a standard PROFIBUS-DP network. Internal power consumption from the backplane is rated at 440 mA at 3.3 VDC.
This communication interface supports network management for up to 125 PROFIBUS-DP slave devices. The module accommodates up to 244 bytes of input data and 244 bytes of output data per slave. Total data exchange reaches up to 3584 bytes of input data and 3584 bytes of output data. Operating temperatures span from 0 to 60 degrees Celsius for industrial field installations.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Weight | 0.56 lbs (0.26 kg) |
|---|
| Product Description | Profibus Master Module |
|---|
| Communication interface | One (1) Profibus Master Port |
|---|
| Communication protocol | ProfiBus |
|---|
| Catalog | IC695 |
|---|
| No. of supported DP slave | 125 |
|---|
| Input data | 244 Bytes |
|---|
| Number of Slots | 1 (single slot) |
|---|
| Output data | 244 Bytes |
|---|
| Backplane Support | Universal |
|---|
| Baud rates | 9.6K, 19.2K, 93.75K, 187.5K, 500K, 1.5M, 3M, 6M and 12M Baud |
|---|
| Protocol Support | Up to 125 PROFIBUS-DP slaves |
|---|
| Mounting location | RX3i PCI |
|---|
| Communication Ports | RS-232 |
|---|
| Status information | Slave Status Bit Array table; Network diagnostic counters; DP master diagnostic counters; Slave Diagnostic Address |
|---|
| Internal Power at 3.3 V DC | 440 mA |
|---|
| Operating Temperature | 0 to 60 degrees Celsius |
|---|
| Backplane Compatibility | RX3i PCI |
|---|
| Current draw | 440 mA @ 3.3 VDC |
|---|
| Storage Temperature | -40 to 85 degrees Celsius |
|---|
| Product Lifecycle Status | Active |
|---|
TECHNICAL INFORMATION
Features
- Connects up to 125 PROFIBUS-DP slave devices on a single network segment.
- Handles up to 3584 bytes of total input data and 3584 bytes of total output data.
- Allows 244 bytes of input data and 244 bytes of output data per connected slave.
- Supports transmission rates from 9.6 kBit/s up to 12 MBit/s.
- Provides DP-V1 read, write, and alarm messaging capabilities.
- Includes sync and freeze operating modes for synchronized slave control.
- Delivers diagnostic counters for network operations, DP master functions, and slave address status.
- Features front-panel LED indicators for network state, module operation, and PROFIBUS OK status.
TECHNICAL INFORMATION
Applications
- PACSystems RX3i distributed automation architectures utilizing fieldbus instrumentation.
- Centralized integration of third-party PROFIBUS-DP motor drives, field sensors, and valve islands.
- Process control installations requiring high-speed data exchange with cyclic and acyclic telemetry.
TECHNICAL INFORMATION
Connections / Interfaces
- One 9-pin Sub-D connector for PROFIBUS-DP network bus cable integration.
- One RS-232 serial communication port.
- Direct RX3i PCI edge connection for communication across the universal backplane.
TECHNICAL INFORMATION
Installation Guidelines
- Install the module into any available PCI slot within an RX3i universal backplane.
- Maintain ambient operational temperatures between 0 and 60 degrees Celsius.
- Secure fieldbus wiring to the 9-pin Sub-D connector to prevent communication dropouts.
TECHNICAL INFORMATION
Configuration Guidelines
- Configure the master module using Machine Edition SP2 Logic Developer PLC software version 5.0 or later.
- Verify the host PACSystems RX3i CPU operates on firmware version 2.9 or higher.
- Transfer field firmware updates via the host controller utilizing the WinLoader software utility.
TECHNICAL INFORMATION
Compatibility
- PACSystems RX3i universal backplanes with PCI support.
- PACSystems RX3i CPU units with firmware version 2.9 or later.
- Standard PROFIBUS-DP and DP-V1 compliant slave devices.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSPACSystems RX3i universal backplanes with PCI support. PACSystems RX3i CPU units with firmware version 2.9 or later. Standard PROFIBUS-DP and DP-V1 compliant slave devices.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the primary function of the IC695PBM300 module?
The IC695PBM300 functions as a PROFIBUS-DP master module for the PACSystems RX3i controller platform.
How many slave devices can the IC695PBM300 support?
The module supports up to 125 PROFIBUS-DP slave devices across the fieldbus network.
What controller firmware is required to operate the IC695PBM300?
The host PACSystems RX3i CPU requires firmware version 2.9 or later.