PRODUCT INFORMATION
Product Overview
The General Electric IC697ALG440 is an analog input expander module for Series 90-70 programmable logic controllers. It features 16 current input channels supporting a range of 4 to 20 milliamps. This expander functions with a base converter module to form an analog input subsystem. Systems can combine expander modules with the base converter for up to 120 input channels. The unit converts signals and presents converted data in two's complement format.
An internal analog multiplexer connects inputs sequentially to the analog-to-digital converter circuit. Diagnostic facilities provide status indicator LEDs, expander channel response detection, and module health monitoring. The module draws 0.4 Amps at 5 Volts DC from the backplane. It provides 16-bit resolution with an analog update rate of 2.4 milliseconds. This module must reside in the same rack adjacent to related subsystem modules.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Accuracy | +/- 0.07% of full scale, +/-0.1% of value |
|---|
| Calibration | Factory set at 10 Volts +/- 2 mV |
|---|
| Current Input Range | 4 to 20 milliamps |
|---|
| No. of Inputs | 16 Inputs |
|---|
| Power Requirement | 0.4 Amps (2 watts) at +5 Volts |
|---|
| Product Description | Current Expander Module |
|---|
| Product Line | Series 90-70 |
|---|
| Resolution | 16 bit |
|---|
| Update Rate | 2.4 ms |
|---|
| Weight | 1.44 lbs (0.65 kg) |
|---|
TECHNICAL INFORMATION
Features
- Provides 16 current input channels with an operating range of 4 to 20 milliamps.
- Operates with a base converter module to expand subsystems up to 120 channels.
- Delivers 16-bit analog-to-digital conversion resolution.
- Features an update rate of 2.4 milliseconds.
- Uses an analog multiplexer switching circuit to connect inputs one at a time.
- Includes status indicator LEDs and module health diagnostic facilities.
- Provides expander channel response detection and error detection facilities.
- Offers factory calibration set at 10 Volts with plus or minus 2 mV tolerance.
TECHNICAL INFORMATION
Applications
- Analog input expansion in General Electric Series 90-70 PLC subsystems.
TECHNICAL INFORMATION
Connections / Interfaces
- Analog expansion signals connect to base converter module terminals 36 and 38.
- Differential data bus connections link to base converter terminals 37 and 39.
- Terminals 37 and 39 function as serial communication ports.
- Optional cable shield ground connects to terminal 35.
TECHNICAL INFORMATION
Installation Guidelines
- Install the expander module in the same rack as the base converter module.
- Position the expander module in a slot adjacent to connected subsystem modules.
- Verify cable polarity prior to terminating expansion signal wiring.
- Connect the shield ground to terminal 35 when shielded cabling is utilized.
TECHNICAL INFORMATION
Configuration Guidelines
- Combine base converter and expander modules up to a maximum of 120 input channels.
- Input data is represented digitally in two's complement format.
TECHNICAL INFORMATION
Compatibility
- General Electric Series 90-70 programmable logic controller racks.
- Series 90-70 analog base converter modules.
- Series 90-70 voltage expander modules.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSGeneral Electric Series 90-70 programmable logic controller racks. Series 90-70 analog base converter modules. Series 90-70 voltage expander modules.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
Can the IC697ALG440 operate without a base converter module?
No. The IC697ALG440 requires a Series 90-70 base converter module to function.
What is the maximum channel capacity supported by the subsystem?
The base converter and expander module combination supports up to 120 input channels.
Where must the IC697ALG440 be placed in the rack?
It must be installed in the same rack adjacent to related subsystem modules.