PRODUCT INFORMATION
Product Overview
The General Electric IC697CPU780 is a Series 90-70 Processor Module for programmable logic controllers. It installs directly into slot 1 of rack 0. The unit uses a 16 megahertz 80386DX microprocessor for system operations. Boolean functions execute at a speed of 0.4 microseconds per function. The module supports floating-point math calculations for complex automation control tasks.
This processor module supports redundant hot standby architectures to prevent system downtime. In redundant setups, one CPU operates as primary while a second CPU acts as secondary. Control transfer occurs through bumpless switching within a single scan cycle. The architecture supports CPU synchronization, scan extension up to 20 milliseconds, and online repairs. System memory configurations range up to 512 kilobytes, with support for battery-backed RAM and non-volatile flash.
TECHNICAL DATA
Technical Specifications
| Parameter | Specification |
|---|
| Weight | 1.00 lbs (0.45 kg) |
|---|
| Compatibility | GE Fanuc 9-70 PLCs |
|---|
| Product Description | Single slot CPU |
|---|
| Hot standby operation | Yes |
|---|
| Specific Application | Hot Standby configuration |
|---|
| Clock speed | 16 megahertz |
|---|
| Processor type | 80386DX microprocessor |
|---|
| Microprocessor | 80386DX |
|---|
| Discrete I/O memory | 12 KB |
|---|
| Maximum memory | 512 kilobytes |
|---|
| Analog I/O memory | 8 KB |
|---|
| Current draw | 1.6 Amps |
|---|
| Boolean Execution speed | 0.4 microseconds per boolean function |
|---|
| Voltage input | 5 Volts DC |
|---|
| Floating Point math | Supported |
|---|
| Communication port | RS485 interface |
|---|
| LED indicators | Module OK, RUN, Outputs enabled |
|---|
| Lithium Battery | IC697ACC701 |
|---|
| Module location | slot 1 of rack 0 |
|---|
| VME | System designed to support the VME standard C.1 |
|---|
TECHNICAL INFORMATION
Features
- Single-slot Central Processing Unit based on an 80386DX microprocessor running at 16 megahertz.
- Boolean execution speed of 0.4 microseconds per boolean instruction.
- Memory configurations available up to 512 kilobytes total capacity.
- Supports up to 12 kilobytes of discrete I/O and 8 kilobytes of analog I/O.
- Hot standby redundancy capability with bumpless, single-scan control transfer.
- Built-in RS-485 serial communication port with a 15-pin D-connector.
- Four front-panel status LED indicators showing module and system operational states.
- Integrated lithium battery IC697ACC701 with ten-year shelf life at 20 degrees Celsius.
TECHNICAL INFORMATION
Applications
- Industrial automation processes requiring high availability and continuous uptime.
- Hot standby redundant control configurations using primary and secondary Series 90-70 racks.
- High-capacity discrete and analog input and output signal management.
- VME standard C.1 industrial automation architectures.
TECHNICAL INFORMATION
Connections / Interfaces
- RS-485 serial interface accessible through an embedded 15-pin D-connector.
- Serial connection supports communication with a programming computer.
- Direct backplane connection designed to support the VME standard C.1.
- Inter-rack communication achieved through bus transmitter modules and redundancy communication modules.
TECHNICAL INFORMATION
Installation Guidelines
- Install the CPU module into slot 1 of rack 0 in the PLC chassis.
- Verify that the backplane delivers 5 Volts DC at 1.6 Amps before insertion.
- Connect the IC697ACC701 lithium battery to maintain RAM memory backup.
- Secure the module firmly in the rack to ensure stable electrical connections.
TECHNICAL INFORMATION
Configuration Guidelines
- Configure controller settings through compatible Series 90-70 programming software.
- Assign discrete I/O up to 12 kilobytes and analog I/O up to 8 kilobytes.
- Designate one unit as the primary CPU and the second as the secondary CPU.
- Enable password-controlled access to protect critical program logic and memory registers.
TECHNICAL INFORMATION
Compatibility
- Compatible with GE Fanuc Series 90-70 rack systems and standard backplanes.
- Works with Series 90-70 redundancy communication modules and bus transmitter modules.
- Uses IC697ACC701 lithium battery packs for RAM data retention.
TECHNICAL INFORMATION
Lifecycle / Replacement Information
- Originally manufactured by GE Fanuc under the Series 90-70 platform.
- The product line is now maintained under Emerson Automation.
COMPATIBILITY
Compatibility & Replacement
COMPATIBLE MODELSCompatible with GE Fanuc Series 90-70 rack systems and standard backplanes. Works with Series 90-70 redundancy communication modules and bus transmitter modules. Uses IC697ACC701 lithium battery packs for RAM data retention.
Verify compatibility against the exact Part Number, revision and manufacturer documentation before ordering.
PART VERIFICATION
Before You Order
Industrial automation parts can share similar model names, suffixes and revisions. Confirm the complete manufacturer Part Number before purchase.
01Check Part NumberMatch the complete ordering code on the existing unit.
02Confirm RevisionCheck suffix, hardware or firmware when applicable.
03Send a Label PhotoWe can review a clear label photo when identification is uncertain.
ORDERING PROCESS
From RFQ to Dispatch
1Submit Part Number2Verify Product Identity3Confirm Stock & Condition4Issue Quotation5Dispatch & Tracking
PRODUCT FAQ
Frequently Asked Questions
What is the primary role of the IC697CPU780 module?
The IC697CPU780 serves as a CPU in Series 90-70 PLCs, specialized for redundant hot standby systems.
What processor and execution speed does the IC697CPU780 feature?
It features a 16 MHz 80386DX processor with a Boolean execution speed of 0.4 microseconds per function.
What battery is used for memory backup on the IC697CPU780?
It uses an IC697ACC701 lithium battery, retaining RAM data for six months.
What is the indicative market price for an IC697CPU780 module?
Pricing varies based on condition and stock; figures represent indicative market reference pricing only and are not a final quotation.